Performance<br />

Data<br />

(25 Ton)<br />

Standard Efficiency<br />

Table PD-21 — Evaporator Fan Performance — 25 Ton — TC*300B<br />

External Static Pressure (Inches of Water)<br />

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

7.5 HP Standard Motor & Low Static Drive Accessory 7.5 HP Standard Motor & Sheaves<br />

7000 — — — — 593 2.42 619 2.62 643 2.80 667 2.98 690 3.16 712 3.35 733 3.53 754 3.73<br />

7500 — — 595 2.66 624 2.88 649 3.10 673 3.31 695 3.50 717 3.68 738 3.88 759 4.08 779 4.28<br />

8000 595 2.92 627 3.16 655 3.39 679 3.63 702 3.86 724 4.07 745 4.28 766 4.48 786 4.68 805 4.90<br />

8500 628 3.47 659 3.73 686 3.97 710 4.23 732 4.47 754 4.71 774 4.94 794 5.15 813 5.36 832 5.58<br />

9000 661 4.08 691 4.36 717 4.62 741 4.89 763 5.15 784 5.41 803 5.66 822 5.89 841 6.12 859 6.35<br />

9500 695 4.76 723 5.06 749 5.34 772 5.62 794 5.90 814 6.18 833 6.45 852 6.71 870 6.95 887 7.19<br />

10000 729 5.52 755 5.84 781 6.13 804 6.42 825 6.72 844 7.01 863 7.31 881 7.59 899 7.86 916 8.11<br />

10500 762 6.35 788 6.69 812 7.00 835 7.31 856 7.62 875 7.93 894 8.24 911 8.54 — — — —<br />

11000 796 7.27 821 7.63 844 7.96 867 8.3 887 8.60 — — — — — — — — — —<br />

7.5 HP Standard Motor & Sheaves<br />

7.5 HP Standard Motor & High Static Drive Accessory<br />

Table PD-21 — Evaporator Fan Performance — 25 Ton — TC*300B — Continued<br />

External Static Pressure (Inches of Water)<br />

1.10 1.20 1.30 1.40 1.50<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

7.5 HP Standard Motor & Sheaves<br />

7000 776 3.95 798 4.18 820 4.40 841 4.62 862 4.84<br />

7500 798 4.48 818 4.71 839 4.95 860 5.19 880 5.42<br />

8000 824 5.11 842 5.32 860 5.55 880 5.80 899 6.06<br />

8500 850 5.81 868 6.03 885 6.26 902 6.49 920 6.74<br />

9000 877 6.58 894 6.81 911 7.05 928 7.29 944 7.53<br />

9500 904 7.43 921 7.67 938 7.92 954 8.17 970 8.42<br />

10000 933 8.36 949 8.62 — — — — — —<br />

10500 — — — — — — — — — —<br />

11000 — — — — — — — — — —<br />

7.5 HP Standard Motor & High Static Drive Accessory<br />

For Standard Evaporator Fan Speed (RPM), reference Table PD-31.<br />

For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.<br />

For Standard Motor & Low Static Drive Accessory Fan Speed (RPM), reference Table PD-34.<br />

Fan motor heat (MBH) = 3.15 x Fan BHP<br />

Data includes pressure drop due to wet coils and filters.<br />

No accessories or options are included in pressure drop<br />

data. Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.<br />

Note:<br />

1. For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/Fan<br />

Speed” tables to determine operating range.<br />

Factory supplied motors, in commercial equipment, are<br />

definite purpose motors, specifically designed and tested<br />

to operate reliably and continuously at all cataloged<br />

conditions. Using the full horsepower range of our fan<br />

motors as shown in our tabular data will not result in<br />

nuisance tripping or premature motor failure. Our<br />

product’s warranty will not be affected.<br />

*Indicates both downflow and horizontal units.<br />