Performance<br />

Data<br />

(17½Ton)<br />

Standard Efficiency<br />

Table PD-19 — Evaporator Fan Performance — 17½ Ton — TC*210C<br />

External Static Pressure (Inches of Water)<br />

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

5 HP Standard Motor <strong>with</strong> Low Static Drive Accessory<br />

5600 — — — — 735 2.34 759 2.46 783 2.60 807 2.74 830 2.89 852 3.03 875 3.18 898 3.33<br />

6300 765 2.96 788 3.10 810 3.23 831 3.36 852 3.50 874 3.65 895 3.81 917 3.97 937 4.13 956 4.29<br />

7000 845 4.02 866 4.18 886 4.33 906 4.48 925 4.62 944 4.77 963 4.93 982 5.10 1002 5.29 1021 5.47<br />

7700 925 5.32 944 5.49 963 5.66 982 5.82 999 5.98 1016 6.14 1033 6.30 1050 6.47 1069 6.66 1086 6.86<br />

8400 1006 6.87 1024 7.06 1041 7.24 1058 7.42 1075 7.60 1091 7.78 1107 7.95 1122 8.13 1138 8.31 1154 8.50<br />

7.5 HP Oversize Motor & Sheaves<br />

5 HP Standard Motor & Sheaves<br />

Table PD-19 — Evaporator Fan Performance — 17½ Ton — TC*210C — Continued<br />

External Static Pressure (Inches of Water)<br />

1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00<br />

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

5 HP Standard Motor & Sheaves<br />

5600 923 3.50 946 3.68 968 3.85 989 4.03 1011 4.21 1033 4.39 1056 4.58 1078 4.77 1099 4.96 1122 5.18<br />

6300 976 4.46 997 4.63 1019 4.82 1040 5.00 1060 5.19 1079 5.39 1100 5.60 1118 5.79 1138 6.00 1157 6.20<br />

7000 1039 5.65 1057 5.82 1074 6.00 1092 6.19 1111 6.39 1130 6.59 1150 6.80 1168 7.01 1186 7.22 1205 7.46<br />

7700 1104 7.06 1122 7.26 1138 7.46 1154 7.66 1170 7.84 1186 8.05 1202 8.25 1220 8.47 — — — —<br />

8400 — — — — — — — — — — — — — — — — — — — —<br />

For Standard Evaporator Fan Speed (RPM), reference Table PD-31.<br />

For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.<br />

For Standard Motor & Low Static Drive Accessory Fan Speed (RPM), reference Table PD-34.<br />

Fan motor heat (MBH) = 3.15 x Fan BHP<br />

Data includes pressure drop due to wet coils and filters.<br />

No accessories or options are included in pressure drop data.<br />

Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.<br />

Notes:<br />

1. For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor & Sheave/<br />

Fan Speed” tables to determine operating range.<br />

7.5 HP Oversive Motor & Sheaves<br />

Factory supplied motors, in commercial equipment, are<br />

definite purpose motors, specifically designed and tested to<br />

operate reliably and continuously at all cataloged conditions.<br />

Using the full horsepower range of our fan motors as shown<br />

in our tabular data will not result in nuisance tripping or<br />

premature motor failure. Our product’s warranty will not be<br />

affected.<br />

*Indicates both downflow and horizontal units.<br />

RT-PRC002-EN<br />