Performance<br />
Data<br />
(17½ Ton)<br />
High Efficiency<br />
Table PD-10 — Gross <strong>Cooling</strong> Capacities (MBH)17½ Ton Three Phase TC*211C3, C4, CW — Standard Refrigeration Option<br />
Ambient Temperature<br />
85 95 105 115<br />
Enter<br />
Dry<br />
Entering Wet Bulb<br />
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73<br />
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC<br />
75 200.0 169.0 224.0 130.0 233.0 86.2 184.0 162.0 215.0 125.0 231.0 83.3 169.0 154.0 199.0 118.0 226.0 79.3 147.0 147.0 180.0 113.0 214.0 74.2<br />
6300 80 202.0 202.0 225.0 161.0 236.0 118.0 190.0 190.0 216.0 158.0 234.0 117.0 177.0 177.0 200.0 151.0 227.0 112.0 164.0 164.0 181.0 142.0 214.0 107.0<br />
85 216.0 216.0 227.0 191.0 239.0 143.0 206.0 206.0 217.0 190.0 236.0 146.0 193.0 193.0 202.0 184.0 228.0 144.0 180.0 180.0 185.0 176.0 215.0 139.0<br />
90 227.0 227.0 230.0 221.0 242.0 169.0 220.0 220.0 220.0 220.0 239.0 175.0 209.0 209.0 209.0 209.0 229.0 174.0 196.0 196.0 195.0 195.0 217.0 171.0<br />
75 205.0 180.0 226.0 134.0 234.0 87.6 190.0 172.0 219.0 131.0 233.0 84.8 174.0 164.0 204.0 124.0 228.0 80.8 155.0 155.0 184.0 116.0 218.0 76.0<br />
7000 80 210.0 210.0 228.0 167.0 237.0 119.0 198.0 198.0 220.0 167.0 236.0 120.0 185.0 185.0 205.0 160.0 229.0 117.0 171.0 171.0 186.0 152.0 218.0 112.0<br />
85 223.0 223.0 230.0 199.0 241.0 145.0 215.0 215.0 222.0 202.0 238.0 150.0 202.0 202.0 209.0 197.0 231.0 150.0 188.0 188.0 191.0 189.0 219.0 147.0<br />
90 232.0 232.0 233.0 230.0 244.0 173.0 227.0 227.0 227.0 227.0 241.0 180.0 218.0 218.0 218.0 218.0 232.0 182.0 205.0 205.0 204.0 204.0 221.0 181.0<br />
75 210.0 190.0 228.0 138.0 235.0 88.9 195.0 183.0 222.0 137.0 234.0 86.0 179.0 175.0 208.0 130.0 229.0 82.4 161.0 161.0 188.0 122.0 220.0 77.7<br />
7700 80 217.0 217.0 231.0 173.0 239.0 120.0 206.0 206.0 223.0 174.0 237.0 121.0 192.0 192.0 209.0 169.0 231.0 121.0 178.0 178.0 190.0 161.0 221.0 116.0<br />
85 228.0 228.0 232.0 206.0 242.0 148.0 221.0 221.0 226.0 211.0 240.0 153.0 210.0 210.0 214.0 209.0 234.0 156.0 196.0 196.0 195.0 195.0 222.0 154.0<br />
90 235.0 235.0 235.0 235.0 245.0 176.0 232.0 232.0 232.0 232.0 243.0 185.0 224.0 224.0 224.0 224.0 235.0 189.0 213.0 213.0 212.0 212.0 224.0 191.0<br />
75 214.0 200.0 230.0 141.0 236.0 90.3 200.0 193.0 224.0 141.0 235.0 87.4 181.0 181.0 211.0 136.0 230.0 83.8 166.0 166.0 191.0 128.0 222.0 79.2<br />
8400 80 222.0 222.0 232.0 177.0 239.0 133.0 213.0 213.0 226.0 181.0 238.0 123.0 199.0 199.0 213.0 178.0 233.0 124.0 184.0 184.0 194.0 170.0 223.0 121.0<br />
85 231.0 231.0 234.0 211.0 243.0 149.0 226.0 226.0 229.0 220.0 241.0 155.0 216.0 216.0 216.0 216.0 235.0 161.0 203.0 203.0 202.0 202.0 224.0 162.0<br />
90 238.0 238.0 238.0 238.0 246.0 178.0 235.0 235.0 235.0 235.0 244.0 189.0 229.0 229.0 229.0 229.0 237.0 195.0 219.0 219.0 219.0 219.0 227.0 199.0<br />
Notes:<br />
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to<br />
appropriate airflow table notes.<br />
2. MBH = Total Gross <strong>Cooling</strong> Capacity<br />
3. SHC = Sensible <strong>Heat</strong> Capacity<br />
*Indicates both downflow and horizontal units.<br />
24 RT-PRC002-EN