General<br />

Data<br />

(17½, 20, 25 Ton)<br />

High Efficiency<br />

Table GD - 4 — General Data<br />

17½ Ton 20 Ton 25 Ton<br />

Downflow and Horizontal Downflow and Horizontal Downflow and Horizontal<br />

TC*211C3,C4,CW TC*241C3,C4,CW TC*301C3,C4,CW<br />

<strong>Cooling</strong> Performance 1<br />

Gross <strong>Cooling</strong> Capacity 220,000 268,000 9 300,000 11<br />

EER 2 11.0 10.6 10.4 11<br />

Nominal CFM / ARI Rated CFM 7,000/6,200 8,000/7,000 10,000/8,750<br />

ARI Net <strong>Cooling</strong> Capacity 208,000 250,000 9 278,000<br />

Integrated Part Load Value 3 12.0 11.2 11.0 11<br />

System Power KW 18.91 23.58 9 26.73 11<br />

Compressor<br />

No./Type 2/Scrolls 2/Scrolls 2/Scrolls<br />

Sound Rating (BELS) 4 9.4 9.4 9.4<br />

Outdoor Coil — Type Hi-Performance Hi-Performance Hi-Performance<br />

Tube Size (in.) O.D. 0.375 0.375 0.375<br />

Face Area (sq ft) 35.30 35.30<br />

Rows/FPI 3/16 3/16 3/16<br />

Indoor Coil — Type Hi-Performance Hi-Performance Hi-Performance<br />

Tube Size (in.) 0.375 0.375 0.375<br />

Face Area (sq ft) 26.000 26.00 26.00<br />

Rows/FPI 4/15 4/15 4/15<br />

Refrigerant Control Short Orifice Short Orifice 9 Short Orifice 11<br />

Drain Connection No./Size (in.) 1 /1.0 NPT 1/1.0 NPT 1/1.0 NPT<br />

Outdoor Fan — Type Propeller Propeller Propeller<br />

No. Used/Diameter (in.) 2/26 2/26 2/26<br />

Drive Type/No. Speeds Direct/1 Direct/1 Direct/1<br />

CFM 12,800 13,700 13,700<br />

No. Motors/HP 2/1.00 2/1.00 2/1.00<br />

Motor RPM 1125 1125 1125<br />

Indoor Fan — Type FC Centrifugal FC Centrifugal FC Centrifugal<br />

No. Used 1 1 1<br />

Diameter x Width (in.) 18 x 18 18 x 18 18 x 18<br />

Drive Type/No. Speeds BELT/1 BELT/1 BELT/1<br />

No. Motors 1 1 1<br />

Motor HP (Standard/Oversized) 5.0/7.5 5.0/7.5 7.5/NA<br />

Motor RPM(Standard/Oversized) 3450/3470 3450/3470 3470/NA<br />

Motor Frame Size (Standard/Oversized) 145T/184T 145T/184T 184T/NA<br />

Filters — Type Furnished 7 Throwaway Throwaway Throwaway<br />

(No.) Size Recommended (in.) (4/4)20 x 20 x 2/20 x 25 x 2 6 (4/4)20 x 20 x 2/20 x 25 x 2 6 (4/4)20 x 20 x 2/20 x 25 x 2 6<br />

Optional Hot Gas Reheat Coil — Type — Hi-Performance —<br />

Tube Size (in.) OD — 0.375 —<br />

Face Area — 26 —<br />

Rows/FPI — 1/16 —<br />

Refrigerant Charge (Lbs of R-22) 5 / Circuit<br />

Standard 25.7/12.5 10 21.8/21.8 9 24.5/24.5 11<br />

Optional Hot Gas Reheat Coil — 21.3/21.0 —<br />

Notes:<br />

1. <strong>Cooling</strong> Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net<br />

and includes the effect of fan motor heat. 15 - 20 ton models are certified in accordance <strong>with</strong> the Unitary Large Equipment certification program, which is based on ARI<br />

Standard 340/360-93. 25 ton model ratings shown are tested in accordance <strong>with</strong> ARI Standard 340/360-93.<br />

2. EER is rated at ARI conditions and in accordance <strong>with</strong> DOE test procedures.<br />

3. Integrated Part Load Value is based in accordance <strong>with</strong> ARI Standard 210/240 or 360. <strong>Units</strong> are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI<br />

rated cfm.<br />

4. Sound Rating shown is tested in accordance <strong>with</strong> ARI Standard 270 or 370.<br />

5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.<br />

6. Horizontal models have 8 - 20 x 25 x 2 filters.<br />

7. Optional two inch pleated filters are also available.<br />

8. TXV/Face-Split Option (Downflow Only) TCD181C3,4,W (EER):11.4; (System Power kW): 15.79; (Refrigerant Control): Expansion Valve; (Refrigerant Charge): 26.0/12.0<br />

9. TXV/Face-Split Option (Downflow Only) TCD241C3,4,W (Gross <strong>Cooling</strong> Capacity):259,000; (ARI Net <strong>Cooling</strong> Capacity): 244,000; (System Power kW): 23.02;<br />

(Refrigerant Control): Expansion Valve; (Refrigerant Charge): 21.5/22.2<br />

10. TXV/Face-Split Option (Downflow Only) TCD211C3,4,W Refrigerant Charge): 27.0/10.0<br />

11. TXV/Face-Split Option (Downflow Only) TCD301C3,4,W (EER): 10; (Gross <strong>Cooling</strong> Capacity): 294,000; (ARI Net <strong>Cooling</strong> Capacity): 272,000; (IPLV): 10.6; System Power kW): 27.2;<br />

Refrigerant Control: Expansion Valve; (Refrigerant Charge): 21.0/23.0<br />

*Indicates both downflow and horizontal units.<br />