Packaged Cooling with Electric Heat Rooftop Units Voyager ... - Trane
Packaged Cooling with Electric Heat Rooftop Units Voyager ... - Trane
Packaged Cooling with Electric Heat Rooftop Units Voyager ... - Trane
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
General<br />
Data<br />
(12½, 15 Ton)<br />
High Efficiency<br />
Table GD - 3 — General Data<br />
12½ Ton<br />
15 Ton<br />
Downflow and Horizontal<br />
Downflow and Horizontal<br />
TC*151C3,C4,CW<br />
TC*181C3,C4, CW<br />
<strong>Cooling</strong> Performance 1<br />
Gross <strong>Cooling</strong> Capacity 154,000 189,000<br />
EER 2 11.3 11.5 8<br />
Nominal CFM / ARI Rated CFM 5,000/4,400 6,000/5,300<br />
ARI Net <strong>Cooling</strong> Capacity 146,000 180,000<br />
Integrated Part Load Value 3 11.5 13.3<br />
System Power KW 12.92 15.65 3<br />
Compressor<br />
No./Type 2/Scrolls 2/Scrolls<br />
Sound Rating (BELS) 4 9.2 9.2<br />
Outdoor Coil — Type Hi-Performance Hi-Performance<br />
Tube Size (in.) O.D. 0.375 0.375<br />
Face Area (sq ft) 27.12 35.30<br />
Rows/FPI 3/16 3/16<br />
Indoor Coil — Type Hi-Performance Hi-Performance<br />
Tube Size (in.) 0.375 0.375<br />
Face Area (sq ft) 17.50 26.00<br />
Rows/FPI 3/15 3/15<br />
Refrigerant Control Short Orifice 9 Short Orifice 8<br />
Drain Connection No./Size (in.) 1/1.0 NPT 1/1.0 NPT<br />
Outdoor Fan — Type Propeller Propeller<br />
No. Used/Diameter (in.) 2/26 2/26<br />
Drive Type/No. Speeds Direct/1 Direct/1<br />
CFM 10,400 11,000<br />
No. Motors/HP 2/.50 2/.50<br />
Motor RPM 1100 1100<br />
Indoor Fan — Type FC Centrifugal FC Centrifugal<br />
No. Used 1 1<br />
Diameter x Width (in.) 15 x 15 18 x 18<br />
Drive Type/No. Speeds BELT/1 BELT/1<br />
No. Motors 1 1<br />
Motor HP (Standard/Oversized) 3.0/5.0 3.0/5.0<br />
Motor RPM (Standard/Oversized) 1740/3450 1740/3450<br />
Motor Frame Size (Standard/Oversized) 145T/145T 145T/145T<br />
Filters — Type/Furnished? Throwaway/Yes 8 Throwaway/Yes 8<br />
(No.) Size Recommended (in.) (2)20 x 20 x 2 (4) 20 x 20 x 2<br />
(4)20 x 25 x 2 (4) 20 x 25 x 2<br />
Optional Hot Gas Reheat Coil — Type Hi-Performance Hi-Performance<br />
Tube Size (in.) OD 0.375 0.375<br />
Face Area (sq. ft.) 17.5 26<br />
Rows/FPI 1/16 1/16<br />
Refrigerant Charge (Lbs of R-22) 5 /Circuit<br />
Standard 15.0/13.8 9 25.0/13.0 8<br />
Optional Hot Gas Reheat Coil 15.3/14.3 27.8/11.4<br />
Notes:<br />
1. <strong>Cooling</strong> Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net<br />
and includes the effect of fan motor heat. <strong>Units</strong> are suitable for operation to ±20% of nominal cfm. Certified in accordance <strong>with</strong> the Unitary Large Equipment certification<br />
program, which is based on ARI Standard 340/360-93.<br />
2. EER is rated at ARI conditions and in accordance <strong>with</strong> DOE test procedures.<br />
3. Integrated Part Load Value is based in accordance <strong>with</strong> ARI Standard 210/240 or 360. <strong>Units</strong> are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI<br />
rated cfm.<br />
4. Sound Rating shown is tested in accordance <strong>with</strong> ARI Standard 270 or 370.<br />
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.<br />
6. Face area for Indoor Coil on horizontal models is 12.36.<br />
7. Horizontal models have 4 - 20 x 25 x 2 filters.<br />
8. Optional two inch pleated filters are also available for 12½ ton models.<br />
9. TXV/Face-Split Option (Downflow Only) TCD151C3,4,W (Refrigerant Control): Expansion Valve; (Refrigerant Charge): 13.4/12.0.<br />
*Indicates both downflow and horizontal units.<br />
RT-PRC002-EN<br />