General<br />
Data<br />
(17½, 20, 25 Ton)<br />
Standard Efficiency<br />
Table GD - 2 — General Data<br />
17½ Ton 20 Ton 25 Ton<br />
Downflow and Horizontal <strong>Units</strong> Downflow and Horizontal <strong>Units</strong> Downflow and Horizontal <strong>Units</strong><br />
TC*210C3, C4, CW, CK TC*240B3, B4, BW, BK TC*300B3, B4, BW, BK<br />
<strong>Cooling</strong> Performance 1<br />
Gross <strong>Cooling</strong> Capacity 210,000 242,000 290,000<br />
EER 2 9.8 9.7 9.7<br />
Nominal CFM / ARI Rated CFM 7,000/5,800 8,000/7,000 10,000/8,750<br />
ARI Net <strong>Cooling</strong> Capacity 196,000 232,000 272,000<br />
Integrated Part Load Value 3 10.0 10.0 9.8<br />
System Power (KW) 20.0 23.91 28.05<br />
Compressor<br />
No./Type 2/Scrolls 2/Scrolls 2/Scrolls<br />
Sound Rating (BELS) 4 9.4 9.4 9.4<br />
Outdoor Coil — Type Hi-Performance Hi-Performance Hi-Performance<br />
Tube Size (in.) O.D. .375 .375 .375<br />
Face Area (sq ft) 27.12 35.30 36.43<br />
Rows/FPI 3/16 3/16 2/16<br />
Indoor Coil — Type Hi-Performance Hi-Performance Hi-Performance<br />
Tube Size (in.) .375 .375 .375<br />
Face Area (sq ft) 17.50 26.00 26.00<br />
Rows/FPI 4/15 2/15 3/15<br />
Refrigerant Control Short Orifice Short Orifice Short Orifice<br />
Drain Connection No./Size (in.) 1/1.00 NPT 1/1.00 NPT 1/1.00 NPT<br />
Outdoor Fan — Type Propeller Propeller Propeller<br />
No. Used/Diameter (in.) 2/26 2/26 2/28<br />
Drive Type/No. Speeds Direct/1 Direct/1 Direct/1<br />
CFM 13,400 14,600 16,700<br />
No. Motors/HP 2/1.0 2/1.0 2/1.0<br />
Motor RPM 1,125 1,125 1,125<br />
Indoor Fan — Type FC Centrifugal FC Centrifugal FC Centrifugal<br />
No. Used 1 1 1<br />
Diameter x Width (in.) 15 x 15 18 x 18 18 x 18<br />
Drive Type/No. Speeds Belt / 1 Belt / 1 Belt / 1<br />
No. Motors 1 1 1<br />
Motor HP (Standard/Oversized) 5.0/7.5 5.0/7.5 7.5/NA<br />
Motor RPM (Standard/Oversized) 3,450/3,470 3,450/3,470 3,470/NA<br />
Motor Frame Size (Standard/Oversized) 145T/184T 145T/184T 184T/NA<br />
Filters — Type Furnished 7 Throwaway Throwaway Throwaway<br />
(No.) Size Recommended (in.)<br />
Downflow (2) 20 x 20 x 2, (4) 20 x 25 x 2 (4) 20 x 20 x 2, (4) 20 x 25 x 2 (4) 20 x 20 x 2, (4) 20 x 25 x 2<br />
Horizontal (2) 20 x 20 x 2, (4) 20 x 25 x 2 (8) 20 x 25 x 2 (8) 20 x 25 x 2<br />
Refrigerant Charge (Lbs of R-22) 5 21.0/14.3/Circuit 6 18.9/21.0/Circuit 17.0/Circuit<br />
Notes:<br />
1. <strong>Cooling</strong> Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net<br />
and includes the effect of fan motor heat. <strong>Units</strong> are suitable for operation to ±20% of nominal cfm. 17½ - 20 ton models are certified in accordance <strong>with</strong> the Unitary Large<br />
Equipment certification program, which is based on ARI Standard 340/360-93. 25 ton model ratings shown are tested in accordance <strong>with</strong> ARI Standard 340/360-93.<br />
2. EER is rated at ARI conditions and in accordance <strong>with</strong> ARI Standard 210/240 or 360.<br />
3. Integrated Part Load Value is based in accordance <strong>with</strong> ARI Standard 210/240 or 360. <strong>Units</strong> are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI<br />
rated cfm.<br />
4. Sound Rating shown is tested in accordance <strong>with</strong> ARI Standard 270 or 370.<br />
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.<br />
6. Refrigerant charge for horizontal models is 21.5/14.5 per circuit.<br />
7. Optional two inch pleated filters are also available.<br />
8. For 380V/60Hz units, the oversized motor is used as the standard motor. Refer to oversized motor data.<br />
*Indicates both downflow and horizontal units.<br />
14 RT-PRC002-EN