Insight™ Ducted Air Handler Product Data - Trane
Insight™ Ducted Air Handler Product Data - Trane Insight™ Ducted Air Handler Product Data - Trane
Insight Ducted Air Handler Product Data Heat Pump Split System Air Conditioning 30 to 50 MBh - 50 Hz Air Handler Models TWE030CA TWE040CA TWE050CA Condensing Models TWJ020-036CA TWA030-060CD TWE-PRC001-EN-10-15-99
- Page 2 and 3: Features and Benefits TWE Features
- Page 4 and 5: System Performance Cooling Capacity
- Page 6 and 7: General Data TWJ Model Power Conn.
- Page 8 and 9: Performance Data Cooling English Un
- Page 10 and 11: Performance Data Cooling English Un
- Page 12 and 13: Performance Data Cooling English Un
- Page 14 and 15: Performance Data Cooling English Un
- Page 16 and 17: Performance Data Heating English Un
- Page 18 and 19: Performance Data Heating English Un
- Page 20 and 21: Performance Data Heating English Un
- Page 22 and 23: Performance Data Heating English Un
- Page 24 and 25: Performance Data Blower Performance
- Page 26 and 27: Performance Data Air Pressure Drop
- Page 28 and 29: Electrical Data System Wiring Diagr
- Page 30 and 31: Dimensions TWJ020-036CA and TWA030-
- Page 32: Mechanical Specification Options Ge
Insight <br />
<strong>Ducted</strong> <strong>Air</strong> <strong>Handler</strong><br />
<strong>Product</strong> <strong>Data</strong><br />
Heat Pump Split System <strong>Air</strong> Conditioning<br />
30 to 50 MBh - 50 Hz<br />
<strong>Air</strong> <strong>Handler</strong> Models<br />
TWE030CA<br />
TWE040CA<br />
TWE050CA<br />
Condensing Models<br />
TWJ020-036CA<br />
TWA030-060CD<br />
TWE-PRC001-EN-10-15-99
Features and<br />
Benefits<br />
TWE<br />
Features<br />
• Ships horizontal<br />
• Six way convertibility-horizontal (left and<br />
right), upflow, downflow (front and rear<br />
access)<br />
• Electrical, refrigerant, condensate and<br />
blower access convertible to either side<br />
• Corrosion resistant galvanized steel<br />
with attractive finish<br />
• Internally enhanced finned coil tubes<br />
• Direct drive motor<br />
• Standard filters<br />
• Multi-speed blower<br />
• 220 volt primary and 24 volt secondary<br />
transformer<br />
• Insulated cabinet<br />
• External access to heater circuit<br />
breakers<br />
• Start kits are not required<br />
• Built-in indoor fan delay function for<br />
increased efficiency. No kit required.<br />
<strong>Air</strong> Handling Units<br />
New Features<br />
• Improved filter access and latch -<br />
Eliminate current T-bar and shipping<br />
bracket.<br />
• Provision for 1-1/8 inches thick field<br />
supplied electrostatic filter<br />
• Reversible Duct Flanges - Fits up to<br />
1-1/2 inches duct board<br />
• Improve controls access with control<br />
box mounted next to blower.<br />
• 40 VA transformer with 5 amp automotive<br />
style fuse on 3 tons and less<br />
• 5 Amp automotive style fuse replaces<br />
Bussman “red cap” fuse on 3.5 to 5 ton<br />
models<br />
• Blower mounting brackets improved -<br />
Front access to screw with power driver<br />
• Improved bottom carton cushioning<br />
• 1 inch thick foil faced insulation for all<br />
models<br />
TWJ<br />
TWA<br />
Condensing Units<br />
Features:<br />
• Vertical <strong>Air</strong> Discharge<br />
• High Efficiency TRANE Climatuff ®<br />
Compressor<br />
• Powder Paint finish<br />
• Brazed connections<br />
• Spine Fin Outdoor Coil<br />
• Switchover Valves<br />
Benefits:<br />
• Flexibility in application<br />
• Quality and reliability<br />
• Uniform covering for a smooth, attractive<br />
and corrosion-resistant finish<br />
©American Standard Inc. 1999<br />
TWE5-PRC001-EN-10-15-99
Contents<br />
Features and Benefits 2<br />
<strong>Air</strong> Handling Units 2<br />
Condensing Units 2<br />
System Performance 4<br />
Selection Procedure 4<br />
Model Number Nomenclature 4<br />
General <strong>Data</strong> 5<br />
TWE030CA40B 5<br />
TWE040CA40C 5<br />
TWE050CA50D 5<br />
TWJ020CA00A0 6<br />
TWJ024CA00A0 6<br />
TWJ030CA00A0 6<br />
TWJ036CA00A0 6<br />
TWA030CD00A0 7<br />
TWA040CD00A0 7<br />
TWA050CD00A0 7<br />
TWA060CD00A0 7<br />
Performance <strong>Data</strong> 8<br />
TWJ/TWE Cooling 8<br />
TWA/TWE Cooling 12<br />
TWJ/TWE Heating 16<br />
TWA/TWE Heating 20<br />
Evaporator Fan Performance 24<br />
<strong>Air</strong> Pressure Drop 26<br />
Supplementary Heaters 27<br />
Electrical <strong>Data</strong> 28<br />
Dimensions 29<br />
Convertibility 31<br />
Mechanical Specification Options 32<br />
TWE5-PRC001-EN-10-15-99 3
System<br />
Performance<br />
Cooling Capacity<br />
95° F (35° C)<br />
Outdoor Unit Indoor Unit CFM CMH MBh Kw<br />
<strong>Ducted</strong> <strong>Air</strong> <strong>Handler</strong>s<br />
TWJ020CA00A TWE030CA00A 700 1185 20 6<br />
TWJ024CA00A TWE030CA00A 900 1520 27 8<br />
TWJ030CA00A TWE030CA00A 1000 1690 31 9<br />
TWJ030CA00A TWE040CA00A 1100 1860 33 9.5<br />
TWJ036CA00A TWE030CA00A 1100 1860 38 11<br />
TWJ036CA00A TWE040CA00A 1325 2240 40.5 11.5<br />
TWJ036CA00A TWE050CA00A 1400 2360 41.6 12<br />
TWA030CD00A TWE030CA00A 1000 1690 32 9<br />
TWA030CD00A TWE040CA00A 1100 1860 34 9.6<br />
TWA040CD00A TWE040CA00A 1300 2200 42 12<br />
TWA040CD00A TWE050CA00A 1500 2535 43 12.5<br />
TWA050CD00A TWE050CA00A 1800 3040 51 14.5<br />
TWA060CD00A TWE050CA00A 1800 3040 63 18<br />
Selection<br />
Procedure<br />
Model Number Nomenclature<br />
1 2 3 4 5 6 7 8 9 10 11 12<br />
T W E 0 3 0 C A 4 0 A 0<br />
PRODUCT TYPE<br />
TW = Split System Component<br />
Heat Pump Compatible<br />
AIRFLOW CONFIGURATION<br />
E = Convertible<br />
REFRIGERANT CONNECTIONS<br />
0 = Brazed<br />
NOMINAL NET COOLING<br />
CAPACITY<br />
30 = 30 MBh<br />
40 = 40 MBh<br />
50 = 50 MBh<br />
MAJOR DESIGN MODIFICATION<br />
NOT USED<br />
PRODUCT<br />
SERVICE CHANGE<br />
MINOR DESIGN<br />
MODIFICATION<br />
REFRIGERANT FLOW CONTROL<br />
4 = Accutron Flow Control/Check Valve<br />
5 = Bleed TXV<br />
ELECTRICAL CHARACTERISTICS<br />
A = 220V/1/50<br />
4 TWE5-PRC001-EN-10-15-99
General<br />
<strong>Data</strong><br />
TWE<br />
TWE <strong>Product</strong> Specifications<br />
Model TWE030CA40B TWE040CA40C TWE050CA50D<br />
Power Conn.— Volts/Ph/Hz 220/1/50 220/1/50 220/1/50<br />
Indoor Coil - Type Plate Fin Plate Fin Plate Fin<br />
Rows 3 3 3<br />
Fins per inch (Fins per 25.4 mm) 14 14 14<br />
Face Area sq ft (sq m) 3.21 (.30) 5.04 (.47) 6.19 (.58)<br />
Tube Size in. (mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)<br />
Refrigerant Control FCCV FCCV FCCV<br />
Drain Conn. Size in. (mm) 3/4 NPT 3/4 NPT 3/4 NPT<br />
Duct Connections See Outline Drawing See Outline Drawing See Outline Drawing<br />
Indoor Fan - Type Centrifugal Centrifugal Centrifugal<br />
No. Used 1 1 1<br />
Diameter in. (mm) 10.0 (254.0) 10.0 (254.0) 11.0 (279.4)<br />
Width in. (mm) 8.0 (203.2) 10.0 (254.0) 10.0 (254.0)<br />
Type Drive - No. Speeds Direct - 3 Direct - 3 Direct - 3<br />
<strong>Air</strong>flow (High)<br />
CFM @ 0.0 in. w.g. See Fan Performance Table See Fan Performance Table See Fan Performance Table<br />
CMH @ 0.0 Pa See Fan Performance Table See Fan Performance Table See Fan Performance Table<br />
No. Motors - HP 1 - 1/3 1 - 1/3 1 - 3/4<br />
Motor RPM 1000 900 900<br />
Volts/Ph/Hz 220/1/50 220/1/50 220/1/50<br />
F.L. Amps 2.6 2.1 4.5<br />
L.R. Amps 3.3 4.2 10.1<br />
Filters<br />
Vertical Applications<br />
Filter Furnished Yes Yes Yes<br />
Type Furnished Throwaway Throwaway High Velocity<br />
No.-Size-Thickness 1 - 20 x 20 - 1 1 - 20 x 20 - 1 1 - 2 2 x 20 - 1<br />
Horizontal Applications<br />
Filter Furnished No No No<br />
Type Recommended See Note Below See Note Below See Note Below<br />
No.-Size-Thickness See Note Below See Note Below See Note Below<br />
Refrigerant Line Size<br />
Line Size ID Gas in. (mm) 7/8 (22.23) 1-1/8 (28.56) 1-1/8 (28.56)<br />
Line Size ID Liquid in. (mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)<br />
Dimensions (H x W x D)<br />
Crated - in. 44.5 x 24.0 x 23.5 53.25 x 26.0 x 23.5 59.5 x 26.0 x 23.5<br />
- (mm) (1130 x 610 x 597) (1353 x 660 x 597) (1511 x 660 x 597)<br />
Uncrated - in. 43.0 x 21.5 x 21.0 52.0 x 23.5 x 21.0 58.0 x 23.5 x 21.0<br />
- (mm) (1092 x 546 x 533) (1321 x 597x 533) (1473 x 597 x 533)<br />
Weight Ibs. (kg)<br />
Shipping 125 (56.7) 165 (74.8) 198 (898)<br />
Net 115 (52.2) 150 (68.0) 183 (83.0)<br />
Minimum filter size for horizontal applications based on airflow selection and calculated as follows:<br />
Low Velocity Filter: Face Area (sq ft) = CFM/300<br />
High Velocity Filter: Face Area (sq ft) = CFM/500<br />
TWE5-PRC001-EN-10-15-99 5
General<br />
<strong>Data</strong><br />
TWJ<br />
Model<br />
Power Conn. - Volts/Ph/Hz<br />
Fuse Size - max. amps<br />
Compressor - Type<br />
No. Used - No. Speeds<br />
Volts/Ph/Hz<br />
F.L. Amps - L.R. Amps<br />
Outdoor Fan - Type<br />
No. Used<br />
Diameter in. (mm)<br />
Type Drive - No. Speeds<br />
CFM @ 0.0 in. w.g. 3<br />
(M) 3/HR. @ 0.0 mm w.g. 3<br />
No. Motors - HP<br />
Motor Speed (RPM)<br />
Volts/Ph/Hz<br />
F.L. Amps<br />
Outdoor Coil - Type<br />
No. Rows<br />
Fins/in. (mm)<br />
Face Area sq ft (sq m)<br />
Tube Size in. (mm)<br />
Refrigerant<br />
R-22 (O.D. Unit) 4 - lbs. (kg)<br />
Factory Supplied<br />
Line Size - OD Gas 5 in. (mm)<br />
Line Size - OD Liq. 5 in. (mm)<br />
FCCV<br />
Restrictor Orifice Size in. (mm)<br />
Dimensions (H x W x D)<br />
Crated - in.<br />
- (mm)<br />
Uncrated<br />
Weight lbs. (kg)<br />
Shipping<br />
Net<br />
NOTES:<br />
TWJ020CA00A0<br />
200/230/1/60<br />
PER LOCAL CODES<br />
CLIMATUFF ®<br />
1 - 1<br />
200/230/1/50<br />
10 - 60<br />
PROPELLER<br />
1<br />
18 (457)<br />
DIRECT - 1<br />
1503<br />
709<br />
1 - 1/8<br />
690<br />
200/230/1/60/50<br />
0.90<br />
SPINE FIN<br />
1<br />
24 (.945)<br />
12.22 (1.14)<br />
3/8 (9.52)<br />
5 LBS., 4 OZ (2.38)<br />
YES<br />
3/4 (19.1)<br />
5/16 (7.94)<br />
0.051 (1.30)<br />
25 X 26-1/2 X 30<br />
(635 X 673 X 762)<br />
SEE OUTLINE DRAWINGS<br />
170 (77.1)<br />
162 (73.5)<br />
TWJ <strong>Product</strong> Specifications 12<br />
TWJ024CA00A0<br />
200/230/1/60<br />
PER LOCAL CODES<br />
CLIMATUFF ®<br />
1 - 1<br />
200/230/1/50<br />
17.9 - 69<br />
PROPELLER<br />
1<br />
18 (457)<br />
DIRECT - 1<br />
1987<br />
938<br />
1 - 1/5<br />
1075<br />
200/230/1/50<br />
1.60<br />
SPINE FIN<br />
1<br />
24 (.945)<br />
16.84 (1.56)<br />
3/8 (9.52)<br />
4 LBS, 13 OZ. (2.18)<br />
YES<br />
3/4 (19.1)<br />
5/16 (7.94)<br />
0.061 (1.55)<br />
33-1/4 X 30 X 26-1/2<br />
(845 X 762 X 673)<br />
SEE OUTLINE DRAWINGS<br />
187 (84.8)<br />
178 (80.7)<br />
TWJ030CA00A0<br />
200/230/1/60<br />
PER LOCAL CODES<br />
CLIMATUFF ®<br />
1 - 1<br />
200/230/1/50<br />
19 - 94<br />
PROPELLER<br />
1<br />
18 (457)<br />
DIRECT - 1<br />
1975<br />
932<br />
1 - 1/5<br />
900<br />
200/230/1/60/50<br />
1.60<br />
SPINE FIN<br />
1<br />
24 (.945)<br />
16.84 (1.56)<br />
3/8 (9.52)<br />
6 LBS., 12 OZ. (3.06)<br />
YES<br />
7/8 (22.2)<br />
3/8 (9.52)<br />
0.065 (1.65)<br />
33-1/4 X 26-1/2 X 30<br />
(845 X 673 X 762)<br />
SEE OUTLINE DRAWINGS<br />
214 (97.1)<br />
205 (93.0)<br />
1 RATING CONDITIONS (COOLING): 80F (27C) D.B. 67F (20C) W.B. ENTERING AIR TO INDOOR COIL OF APPLICABLE TYPE.<br />
95F (35C) D.B. ENTERING AIR TO OUTDOOR COIL.<br />
INDOOR COIL AND UNIT CONNECTED BY 25 FT. (7.62 METERS) TUBING.<br />
2 RATING CONDITIONS (HEATING): 70F (21C) D.B. ENTERING AIR TO INDOOR COIL; 47F (8C) D.B.<br />
43F (6C) W.B. ENTERING AIR TO OUTDOOR COIL.<br />
NO SUPPLEMENTARY HEAT INCLUDED.<br />
3 STANDARD AIR - DRY COIL - OUTDOOR<br />
4 THIS VALUE APPROXIMATE. FOR MORE PRECISE VALUE SEE UNIT NAMEPLATE AND SERVICE INSTRUCTIONS.<br />
5 MAX. OF 80 FT. (24.38 METERS) TOTAL MEASURED LENGTH INCLUDING 60 FT. (18.29 METERS) MAX. LIFT BETWEEN O.D. AND I.D. SECTIONS.<br />
TWJ036CA00A0<br />
200/230/1/60<br />
PER LOCAL CODES<br />
CLIMATUFF ®<br />
1 - 1<br />
200/230/1/60/50<br />
21.9 - 95<br />
PROPELLER<br />
1<br />
22 (559)<br />
DIRECT - 1<br />
2748<br />
1297<br />
1 - 1/4<br />
900<br />
200/230/1/50<br />
1.40<br />
SPINE FIN<br />
1<br />
24 (.945)<br />
23.11 (2.15)<br />
3/8 (9.52)<br />
8 LBS., 2 OZ. (3.69)<br />
YES<br />
7/8 (22.2)<br />
3/8 (9.52)<br />
0.073 (1.85)<br />
37-1/2 X 34-3/4 X 30-1/2<br />
(953 X 883 X 775)<br />
SEE OUTLINE DRAWINGS<br />
252 (114)<br />
238 (108)<br />
6 TWE5-PRC001-EN-10-15-99
General<br />
<strong>Data</strong><br />
TWA<br />
Model<br />
Power Conn. - Volts/Ph/Hz<br />
Fuse Size - max. amps<br />
Compressor - Type<br />
No. Used - No. Speeds<br />
Volts/Ph/Hz<br />
F.L. Amps - L.R. Amps<br />
Outdoor Fan - Type<br />
No. Used<br />
Diameter in. (mm)<br />
Type Drive - No. Speeds<br />
CFM @ 0.0 in. w.g. 3<br />
(M) 3/HR. @ 0.0 mm w.g. 3<br />
No. Motors - HP<br />
Motor Speed (RPM)<br />
Volts/Ph/Hz<br />
F.L. Amps<br />
Outdoor Coil - Type<br />
No. Rows<br />
Fins/in. (mm)<br />
Face Area sq ft (sq m)<br />
Tube Size in. (mm)<br />
Refrigerant<br />
R-22 (O.D. Unit) 4 - lbs. (kg)<br />
Factory Supplied<br />
Line Size - OD Gas 5 in. (mm)<br />
Line Size - OD Liq. 5 in. (mm)<br />
FCCV<br />
Restrictor Orifice Size in. (mm)<br />
Dimensions (H x W x D)<br />
Crated - in.<br />
- (mm)<br />
Uncrated<br />
Weight lbs. (kg)<br />
Shipping<br />
Net<br />
NOTES:<br />
TWA030CD00A0<br />
380/415/3/60<br />
PER LOCAL CODES<br />
CLIMATUFF ®<br />
1 - 1<br />
380/415/3/50<br />
5 - 51<br />
PROPELLER<br />
1<br />
18 (457)<br />
DIRECT - 1<br />
1976<br />
933<br />
1 - 1/4<br />
1075/900<br />
460/1/60/50<br />
0.80<br />
SPINE FIN<br />
1<br />
24 (.945)<br />
16.84 (1.56)<br />
3/8 (9.52)<br />
6 LBS.,12 OZ. (3.06)<br />
YES<br />
7/8 (22.2)<br />
3/8 (9.52)<br />
0.065 (1.65)<br />
33-1/4 X 30 X 26-1/2<br />
(845 X 762 X 673)<br />
SEE OUTLINE DRAWINGS<br />
219 (99.3)<br />
210 (95.3)<br />
TWA <strong>Product</strong> Specifications 12<br />
TWA040CD00A0<br />
380/415/3/60<br />
PER LOCAL CODES<br />
CLIMATUFF ®<br />
1 - 1<br />
380/415/3/50<br />
7 - 51<br />
PROPELLER<br />
1<br />
22 (559)<br />
DIRECT - 1<br />
2738<br />
1292<br />
1 - 1/3<br />
825/690<br />
460/1/60/50<br />
1.0<br />
SPINE FIN<br />
1<br />
24 (.945)<br />
20.32 (1.89)<br />
3/8 (9.52)<br />
8 LBS.,13 OZ. (4.00)<br />
YES<br />
1-1/8 (3.18)<br />
3/8 (9.52)<br />
0.075 (1.91)<br />
33-1/4 X 34-3/4 X 30-1/2<br />
(845 X 883 X 775)<br />
SEE OUTLINE DRAWINGS<br />
251 (114)<br />
239 (108)<br />
TWA050CD00A0<br />
380/415/3/60<br />
PER LOCAL CODES<br />
CLIMATUFF ®<br />
1 - 1<br />
380/415/3/50<br />
9 - 71<br />
PROPELLER<br />
1<br />
26 (660)<br />
DIRECT - 1<br />
3141<br />
1482<br />
1 - 1/3<br />
825/690<br />
460/1/60/50<br />
1.0<br />
SPINE FIN<br />
1<br />
24 (.945)<br />
28.91 (2.69)<br />
3/8 (9.52)<br />
10 LBS.,9 OZ. (4.79)<br />
YES<br />
1-1/8 (3.18)<br />
3/8 (9.52)<br />
0.086 (2.18)<br />
37-1/2 X 40-3/4 X 36-1/2<br />
(953 X 1035 X 927)<br />
SEE OUTLINE DRAWINGS<br />
308 (140)<br />
293 (133)<br />
1 RATING CONDITIONS (COOLING): 80F (27C) D.B. 67F (20C) W.B. ENTERING AIR TO INDOOR COIL OF APPLICABLE TYPE.<br />
95F (35C) D.B. ENTERING AIR TO OUTDOOR COIL.<br />
INDOOR COIL AND UNIT CONNECTED BY 25 FT. (7.62 METERS) TUBING.<br />
2 RATING CONDITIONS (HEATING): 70F (21C) D.B. ENTERING AIR TO INDOOR COIL; 47F (8C) D.B.<br />
43F (6C) W.B. ENTERING AIR TO OUTDOOR COIL.<br />
NO SUPPLEMENTARY HEAT INCLUDED.<br />
3 STANDARD AIR - DRY COIL - OUTDOOR<br />
4 THIS VALUE APPROXIMATE. FOR MORE PRECISE VALUE SEE UNIT NAMEPLATE AND SERVICE INSTRUCTIONS.<br />
5 MAX. OF 80 FT. (24.38 METERS) TOTAL MEASURED LENGTH INCLUDING 60 FT. (18.29 METERS) MAX. LIFT BETWEEN O.D. AND I.D. SECTIONS.<br />
TWA060CD00A0<br />
380/415/3/60<br />
PER LOCAL CODES<br />
CLIMATUFF ®<br />
1 - 1<br />
380/415/3/50<br />
10.6 - 64<br />
PROPELLER<br />
1<br />
26 (660)<br />
DIRECT - 1<br />
3931<br />
1855<br />
1 - 1/3<br />
825<br />
460/1/60/50<br />
1.7<br />
SPINE FIN<br />
2<br />
24 (.945)<br />
35.39 (3.29)<br />
3/8 (9.52)<br />
16 LBS.,12 OZ. (7.60)<br />
YES<br />
1-1/8 (3.18)<br />
3/8 (9.52)<br />
0.086 (2.18)<br />
45-1/2 X 41 X 37<br />
(1156 X 1041 X 940)<br />
SEE OUTLINE DRAWINGS<br />
395 (179)<br />
376 (171)<br />
TWE5-PRC001-EN-10-15-99 7
Performance<br />
<strong>Data</strong> Cooling<br />
English Units<br />
TWJ020CA WITH TWE030CA4 AT 700 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)<br />
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.<br />
D.B. W.B. CAP. 72 74 76 78 80 KW<br />
59 18.2 15.5 16.7 18.0 18.6* 19.1* 1.34<br />
85 63 19.7 13.0 14.3 15.5 16.8 18.1 1.39<br />
67 21.2 10.3 11.6 12.8 14.1 15.4 1.44<br />
71 22.7 7.5 8.8 10.1 11.3 12.6 1.49<br />
59 17.9 15.3 16.6 17.8 18.4* 18.8* 1.40<br />
90 63 19.3 12.8 14.1 15.4 16.7 17.9 1.45<br />
67 20.8 10.1 11.4 12.7 13.9 15.2 1.50<br />
71 22.3 7.4 8.6 9.9 11.2 12.4 1.55<br />
59 17.5 15.2 16.4 17.6* 18.1* 18.5* 1.46<br />
95 63 18.9 12.7 14.0 15.2 16.5 17.8 1.51<br />
67 20.4 10.0 11.3 12.5 13.8 15.1 1.56<br />
71 21.9 7.2 8.5 9.8 11.0 12.3 1.62<br />
59 17.0 15.0 16.2 17.2* 17.7* 18.1* 1.53<br />
100 63 18.4 12.5 13.8 15.0 16.3 17.6 1.58<br />
67 19.8 9.8 11.0 12.3 13.6 14.9 1.63<br />
71 21.3 7.0 8.3 9.5 10.8 12.1 1.68<br />
59 16.5 14.7 16.0 16.8* 17.3* 17.7* 1.59<br />
105 63 17.9 12.3 13.6 14.8 16.1 17.4 1.64<br />
67 19.2 9.6 10.8 12.1 13.4 14.6 1.70<br />
71 20.7 6.8 8.1 9.3 10.6 11.9 1.75<br />
59 15.6 14.3 15.6* 16.0* 16.4* 16.9* 1.72<br />
115 63 16.8 11.9 13.1 14.4 15.7 16.9* 1.78<br />
67 18.1 9.2 10.4 11.7 13.0 14.2 1.83<br />
71 19.4 6.4 7.7 8.9 10.2 11.5 1.89<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(MULTIPLY OR ADD AS INDICATED)<br />
AIRFLOW 625 800<br />
TOTAL CAP. X0.99 X1.01<br />
SENS. CAP. X0.95 X1.06<br />
COMPR. KW X0.99 X1.01<br />
VALUES AT 95/80/67 RATING CONDITIONS<br />
GROSS CAPACITY = 20400 BTUH<br />
AIRFLOW = 700 CFM<br />
COMPRESSOR POWER = 1562 WATTS<br />
I.D. FAN POWER = 310 WATTS<br />
O.D. FAN POWER = 130 WATTS<br />
S.E.E.R. = 10.30 BTUH/WATT<br />
E.E.R. = 9.50 BTUH/WATT<br />
NOTE:RATED WITH 25 FEET OF 3/4 SUCT.<br />
AND 5/16 LIQUID LINE<br />
* DRY COIL CONDITION (TOTAL CAPACITY =<br />
SENSIBLE CAPACITY)<br />
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.<br />
ARE VALID ONLY FOR WET COIL<br />
ALL TEMPERATURES IN DEGREES F.<br />
TWJ024CA WITH TWE030CA4 AT 900 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)<br />
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.<br />
D.B. W.B. CAP. 72 74 76 78 80 KW<br />
59 24.2 19.7 21.3 22.9 24.3* 24.9* 1.92<br />
85 63 26.0 16.7 18.3 19.8 21.4 23.0 1.98<br />
67 28.0 13.3 14.9 16.5 18.0 19.6 2.05<br />
71 30.0 9.9 11.5 13.0 14.6 16.2 2.12<br />
59 23.8 19.6 21.1 22.7 24.0* 24.6* 2.01<br />
90 63 25.6 16.5 18.1 19.7 21.2 22.8 2.08<br />
67 27.5 13.2 14.7 16.3 17.9 19.4 2.14<br />
71 29.5 9.7 11.3 12.8 14.4 16.0 2.21<br />
59 23.4 19.4 21.0 22.5 23.7* 24.3* 2.10<br />
95 63 25.2 16.4 17.9 19.5 21.0 22.6 2.17<br />
67 27.1 13.0 14.5 16.1 17.7 19.2 2.24<br />
71 29.0 9.5 11.1 12.7 14.2 15.8 2.31<br />
59 22.8 19.2 20.7 22.3 23.2* 23.8* 2.21<br />
100 63 24.6 16.1 17.7 19.2 20.8 22.4 2.27<br />
67 26.4 12.7 14.3 15.9 17.4 19.0 2.34<br />
71 28.3 9.3 10.9 12.4 14.0 15.6 2.41<br />
59 22.2 18.9 20.5 22.0 22.8* 23.3* 2.31<br />
105 63 24.0 15.9 17.4 19.0 20.6 22.1 2.37<br />
67 25.7 12.5 14.1 15.6 17.2 18.8 2.44<br />
71 27.6 9.0 10.6 12.2 13.7 15.3 2.51<br />
59 21.1 18.4 20.0 21.3* 21.8* 22.4* 2.52<br />
115 63 22.7 15.4 16.9 18.5 20.1 21.6 2.58<br />
67 24.4 12.0 13.6 15.1 16.7 18.3 2.65<br />
71 26.2 8.6 10.1 11.7 13.3 14.8 2.71<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(MULTIPLY OR ADD AS INDICATED)<br />
AIRFLOW 800 1025<br />
TOTAL CAP. X0.99 X1.01<br />
SENS. CAP. X0.95 X1.06<br />
COMPR. KW X0.99 X1.01<br />
VALUES AT 95/80/67 RATING CONDITIONS<br />
GROSS CAPACITY = 27100 BTUH<br />
AIRFLOW = 900 CFM<br />
COMPRESSOR POWER = 2239 WATTS<br />
I.D. FAN POWER = 430 WATTS<br />
O.D. FAN POWER = 180 WATTS<br />
E.E.R. = 8.90 BTUH/WATT<br />
NOTE:RATED WITH 25 FEET OF 3/4 SUCT.<br />
AND 5/16 LIQUID LINE<br />
* DRY COIL CONDITION (TOTAL CAPACITY =<br />
SENSIBLE CAPACITY)<br />
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.<br />
ARE VALID ONLY FOR WET COIL<br />
ALL TEMPERATURES IN DEGREES F.<br />
TWJ030CA WITH TWE030CA4 AT 1000 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)<br />
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.<br />
D.B. W.B. CAP. 72 74 76 78 80 KW<br />
59 29.0 22.8 24.5 26.2 28.0 29.3* 2.57<br />
85 63 31.2 19.4 21.2 22.9 24.6 26.3 2.66<br />
67 33.5 15.7 17.4 19.2 20.9 22.6 2.75<br />
71 35.8 11.9 13.6 15.3 17.1 18.8 2.85<br />
59 28.5 22.6 24.3 26.0 27.7 28.9* 2.69<br />
90 63 30.6 19.2 20.9 22.7 24.4 26.1 2.78<br />
67 32.9 15.5 17.2 18.9 20.7 22.4 2.88<br />
71 35.2 11.7 13.4 15.1 16.9 18.6 2.97<br />
59 28.0 22.3 24.1 25.8 27.5 28.5* 2.82<br />
95 63 30.1 19.0 20.7 22.4 24.2 25.9 2.91<br />
67 32.3 15.3 17.0 18.7 20.4 22.2 3.00<br />
71 34.6 11.5 13.2 14.9 16.6 18.4 3.10<br />
59 27.3 22.1 23.8 25.5 27.2 28.0* 2.95<br />
100 63 29.4 18.7 20.4 22.1 23.9 25.6 3.04<br />
67 31.5 15.0 16.7 18.4 20.1 21.9 3.13<br />
71 33.8 11.2 12.9 14.6 16.3 18.1 3.23<br />
59 26.6 21.8 23.5 25.2 26.8* 27.4* 3.08<br />
105 63 28.7 18.4 20.1 21.9 23.6 25.3 3.17<br />
67 30.8 14.7 16.4 18.1 19.9 21.6 3.26<br />
71 32.9 10.9 12.6 14.3 16.1 17.8 3.36<br />
59 25.3 21.2 22.9 24.6 25.7* 26.3* 3.35<br />
115 63 27.2 17.8 19.6 21.3 23.0 24.7 3.43<br />
67 29.2 14.1 15.8 17.6 19.3 21.0 3.52<br />
71 31.3 10.3 12.0 13.8 15.5 17.2 3.62<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(MULTIPLY OR ADD AS INDICATED)<br />
AIRFLOW 875 1125<br />
TOTAL CAP. X0.98 X1.01<br />
SENS. CAP. X0.95 X1.05<br />
COMPR. KW X0.99 X1.01<br />
VALUES AT 95/80/67 RATING CONDITIONS<br />
GROSS CAPACITY = 32400 BTUH<br />
AIRFLOW = 1000 CFM<br />
COMPRESSOR POWER = 3002 WATTS<br />
I.D. FAN POWER = 440 WATTS<br />
O.D. FAN POWER = 195 WATTS<br />
E.E.R. = 8.30 BTUH/WATT<br />
NOTE:RATED WITH 25 FEET OF 7/8 SUCT.<br />
AND 3/8 LIQUID LINE<br />
* DRY COIL CONDITION (TOTAL CAPACITY =<br />
SENSIBLE CAPACITY)<br />
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.<br />
ARE VALID ONLY FOR WET COIL<br />
ALL TEMPERATURES IN DEGREES F.<br />
8 TWE5-PRC001-EN-10-15-99
Performance<br />
<strong>Data</strong> Cooling<br />
Metric Units<br />
TWJ020CA WITH TWE030CA4 AT 1189 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)<br />
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.<br />
D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW<br />
15.0 5.3 4.5 4.9 5.3 5.4* 5.6* 1.3<br />
29.4 17.2 5.8 3.8 4.2 4.5 4.9 5.3 1.4<br />
19.4 6.2 3.0 3.4 3.8 4.1 4.5 1.4<br />
21.7 6.7 2.2 2.6 3.0 3.3 3.7 1.5<br />
15.0 5.2 4.5 4.9 5.2 5.4* 5.5* 1.4<br />
32.2 17.2 5.7 3.8 4.1 4.5 4.9 5.2 1.5<br />
19.4 6.1 3.0 3.3 3.7 4.1 4.5 1.5<br />
21.7 6.5 2.2 2.5 2.9 3.3 3.6 1.5<br />
15.0 5.1 4.5 4.8 5.2* 5.3* 5.4* 1.5<br />
35.0 17.2 5.5 3.7 4.1 4.5 4.8 5.2 1.5<br />
19.4 6.0 2.9 3.3 3.7 4.0 4.4 1.6<br />
21.7 6.4 2.1 2.5 2.9 3.2 3.6 1.6<br />
15.0 5.0 4.4 4.7 5.0* 5.2* 5.3* 1.5<br />
37.8 17.2 5.4 3.7 4.0 4.4 4.8 5.2 1.6<br />
19.4 5.8 2.9 3.2 3.6 4.0 4.4 1.6<br />
21.7 6.2 2.1 2.4 2.8 3.2 3.5 1.7<br />
15.0 4.8 4.3 4.7 4.9* 5.1* 5.2* 1.6<br />
40.6 17.2 5.2 3.6 4.0 4.3 4.7 5.1 1.6<br />
19.4 5.6 2.8 3.2 3.5 3.9 4.3 1.7<br />
21.7 6.1 2.0 2.4 2.7 3.1 3.5 1.8<br />
15.0 4.6 4.2 4.6* 4.7* 4.8* 5.0* 1.7<br />
46.1 17.2 4.9 3.5 3.8 4.2 4.6 5.0* 1.8<br />
19.4 5.3 2.7 3.0 3.4 3.8 4.2 1.8<br />
21.7 5.7 1.9 2.3 2.6 3.0 3.4 1.9<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(MULTIPLY OR ADD AS INDICATED)<br />
AIRFLOW 1061 1358<br />
TOTAL CAP. X0.99 X1.01<br />
SENS. CAP. X0.95 X1.06<br />
COMPR. KW X0.99 X1.01<br />
VALUES AT ARI RATING CONDITIONS<br />
GROSS CAPACITY = 5.98 KW<br />
AIRFLOW = 1189 CMH<br />
COMPRESSOR POWER = 1562 WATTS<br />
I.D. FAN POWER = 310 WATTS<br />
O.D. FAN POWER = 130 WATTS<br />
S.E.E.R. = 10.30 BTUH/WATT<br />
E.E.R. = 9.50 BTUH/WATT<br />
NOTE:RATED WITH 7.62 METERS OF 19 MM SUCT.<br />
AND 8 MM LIQUID LINES<br />
* DRY COIL CONDITION (TOTAL CAPACITY =<br />
SENSIBLE CAPACITY)<br />
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.<br />
ARE VALID ONLY FOR WET COIL<br />
ALL TEMPERATURES IN DEGREES C.<br />
TWJ024CA WITH TWE030CA4 AT 1528 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)<br />
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.<br />
D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW<br />
15.0 7.1 5.8 6.2 6.7 7.1* 7.3* 1.9<br />
29.4 17.2 7.6 4.9 5.4 5.8 6.3 6.7 2.0<br />
19.4 8.2 3.9 4.4 4.8 5.3 5.7 2.0<br />
21.7 8.8 2.9 3.4 3.8 4.3 4.7 2.1<br />
15.0 7.0 5.7 6.2 6.7 7.0* 7.2* 2.0<br />
32.2 17.2 7.5 4.8 5.3 5.8 6.2 6.7 2.1<br />
19.4 8.1 3.9 4.3 4.8 5.2 5.7 2.1<br />
21.7 8.6 2.8 3.3 3.8 4.2 4.7 2.2<br />
15.0 6.9 5.7 6.2 6.6 6.9* 7.1* 2.1<br />
35.0 17.2 7.4 4.8 5.2 5.7 6.2 6.6 2.2<br />
19.4 7.9 3.8 4.2 4.7 5.2 5.6 2.2<br />
21.7 8.5 2.8 3.3 3.7 4.2 4.6 2.3<br />
15.0 6.7 5.6 6.1 6.5 6.8* 7.0* 2.2<br />
37.8 17.2 7.2 4.7 5.2 5.6 6.1 6.6 2.3<br />
19.4 7.7 3.7 4.2 4.7 5.1 5.6 2.3<br />
21.7 8.3 2.7 3.2 3.6 4.1 4.6 2.4<br />
15.0 6.5 5.5 6.0 6.4 6.7* 6.8* 2.3<br />
40.6 17.2 7.0 4.7 5.1 5.6 6.0 6.5 2.4<br />
19.4 7.5 3.7 4.1 4.6 5.0 5.5 2.4<br />
21.7 8.1 2.6 3.1 3.6 4.0 4.5 2.5<br />
15.0 6.2 5.4 5.9 6.2* 6.4* 6.6* 2.5<br />
46.1 17.2 6.7 4.5 5.0 5.4 5.9 6.3 2.6<br />
19.4 7.1 3.5 4.0 4.4 4.9 5.4 2.7<br />
21.7 7.7 2.5 3.0 3.4 3.9 4.3 2.7<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(MULTIPLY OR ADD AS INDICATED)<br />
AIRFLOW 1358 1741<br />
TOTAL CAP. X0.99 X1.01<br />
SENS. CAP. X0.95 X1.06<br />
COMPR. KW X0.99 X1.01<br />
VALUES AT ARI RATING CONDITIONS<br />
GROSS CAPACITY = 7.94 KW<br />
AIRFLOW = 1528 CMH<br />
COMPRESSOR POWER = 2239 WATTS<br />
I.D. FAN POWER = 430 WATTS<br />
O.D. FAN POWER = 180 WATTS<br />
E.E.R. = 8.90 BTUH/WATT<br />
NOTE:RATED WITH 7.62 METERS OF 19 MM SUCT.<br />
AND 8 MM LIQUID LINES<br />
* DRY COIL CONDITION (TOTAL CAPACITY =<br />
SENSIBLE CAPACITY)<br />
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.<br />
ARE VALID ONLY FOR WET COIL<br />
ALL TEMPERATURES IN DEGREES C.<br />
TWJ030CA WITH TWE030CA4 AT 1698 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)<br />
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.<br />
D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW<br />
15.0 8.5 6.7 7.2 7.7 8.2 8.6* 2.6<br />
29.4 17.2 9.1 5.7 6.2 6.7 7.2 7.7 2.7<br />
19.4 9.8 4.6 5.1 5.6 6.1 6.6 2.8<br />
21.7 10.5 3.5 4.0 4.5 5.0 5.5 2.8<br />
15.0 8.4 6.6 7.1 7.6 8.1 8.5* 2.7<br />
32.2 17.2 9.0 5.6 6.1 6.7 7.1 7.6 2.8<br />
19.4 9.6 4.5 5.0 5.5 6.1 6.6 2.9<br />
21.7 10.3 3.4 3.9 4.4 5.0 5.4 3.0<br />
15.0 8.2 6.5 7.1 7.6 8.1 8.4* 2.8<br />
35.0 17.2 8.8 5.6 6.1 6.6 7.1 7.6 2.9<br />
19.4 9.5 4.5 5.0 5.5 6.0 6.5 3.0<br />
21.7 10.1 3.4 3.9 4.4 4.9 5.4 3.1<br />
15.0 8.0 6.5 7.0 7.5 8.0 8.2* 3.0<br />
37.8 17.2 8.6 5.5 6.0 6.5 7.0 7.5 3.0<br />
19.4 9.2 4.4 4.9 5.4 5.9 6.4 3.1<br />
21.7 9.9 3.3 3.8 4.3 4.8 5.3 3.2<br />
15.0 7.8 6.4 6.9 7.4 7.9* 8.0* 3.1<br />
40.6 17.2 8.4 5.4 5.9 6.4 6.9 7.4 3.2<br />
19.4 9.0 4.3 4.8 5.3 5.8 6.3 3.3<br />
21.7 9.6 3.2 3.7 4.2 4.7 5.2 3.4<br />
15.0 7.4 6.2 6.7 7.2 7.5* 7.7* 3.3<br />
46.1 17.2 8.0 5.2 5.7 6.2 6.7 7.2 3.4<br />
19.4 8.6 4.1 4.6 5.2 5.7 6.2 3.5<br />
21.7 9.2 3.0 3.5 4.0 4.5 5.0 3.6<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(MULTIPLY OR ADD AS INDICATED)<br />
AIRFLOW 1486 1910<br />
TOTAL CAP. X0.98 X1.01<br />
SENS. CAP. X0.95 X1.05<br />
COMPR. KW X0.99 X1.01<br />
VALUES AT ARI RATING CONDITIONS<br />
GROSS CAPACITY = 9.49 KW<br />
AIRFLOW = 1698 CMH<br />
COMPRESSOR POWER = 3002 WATTS<br />
I.D. FAN POWER = 440 WATTS<br />
O.D. FAN POWER = 195 WATTS<br />
E.E.R. = 8.30 BTUH/WATT<br />
NOTE:RATED WITH 7.62 METERS OF 22 MM SUCT.<br />
AND 9.5 MM LIQUID LINES<br />
* DRY COIL CONDITION (TOTAL CAPACITY =<br />
SENSIBLE CAPACITY)<br />
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.<br />
ARE VALID ONLY FOR WET COIL<br />
ALL TEMPERATURES IN DEGREES C.<br />
TWE5-PRC001-EN-10-15-99 9
Performance<br />
<strong>Data</strong> Cooling<br />
English Units<br />
TWJ030CA WITH TWE040CA4-B AT 1100 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)<br />
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.<br />
D.B. W.B. CAP. 72 74 76 78 80 KW<br />
59 30.7 25.1 27.1 29.1 31.0* 31.6* 2.65<br />
85 63 33.0 21.2 23.2 25.2 27.2 29.2 2.75<br />
67 35.3 16.9 18.9 20.9 22.9 24.9 2.84<br />
71 37.7 12.5 14.5 16.5 18.5 20.4 2.94<br />
59 30.1 24.9 26.9 28.9 30.5* 31.2* 2.78<br />
90 63 32.3 21.0 22.9 24.9 26.9 28.9 2.87<br />
67 34.6 16.6 18.6 20.6 22.6 24.6 2.97<br />
71 37.0 12.2 14.2 16.2 18.2 20.2 3.07<br />
59 29.5 24.6 26.6 28.6 30.0* 30.7* 2.91<br />
95 63 31.7 20.7 22.7 24.7 26.7 28.7 3.00<br />
67 33.9 16.4 18.4 20.4 22.3 24.3 3.10<br />
71 36.2 12.0 14.0 15.9 17.9 19.9 3.20<br />
59 28.8 24.3 26.3 28.3 29.3* 30.0* 3.04<br />
100 63 30.9 20.4 22.4 24.3 26.3 28.3 3.13<br />
67 33.0 16.0 18.0 20.0 22.0 24.0 3.23<br />
71 35.3 11.6 13.6 15.6 17.6 19.6 3.33<br />
59 28.0 24.0 26.0 27.9 28.7* 29.4* 3.17<br />
105 63 30.0 20.0 22.0 24.0 26.0 28.0 3.27<br />
67 32.1 15.7 17.7 19.7 21.7 23.7 3.36<br />
71 34.3 11.3 13.3 15.3 17.3 19.3 3.46<br />
59 26.5 23.3 25.3 26.8* 27.4* 28.1* 3.45<br />
115 63 28.4 19.4 21.4 23.4 25.4 27.3 3.54<br />
67 30.4 15.1 17.1 19.0 21.0 23.0 3.63<br />
71 32.4 10.7 12.7 14.6 16.6 18.6 3.73<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(MULTIPLY OR ADD AS INDICATED)<br />
AIRFLOW 975 1275<br />
TOTAL CAP. X0.98 X1.02<br />
SENS. CAP. X0.95 X1.07<br />
COMPR. KW X0.99 X1.01<br />
VALUES AT 95/80/67 RATING CONDITIONS<br />
GROSS CAPACITY = 34100 BTUH<br />
AIRFLOW = 1125 CFM<br />
COMPRESSOR POWER = 3104 WATTS<br />
I.D. FAN POWER = 300 WATTS<br />
O.D. FAN POWER = 195 WATTS<br />
E.E.R. = 9.05 BTUH/WATT<br />
NOTE:RATED WITH 25 FEET OF 7/8 SUCT.<br />
AND 3/8 LIQUID LINE<br />
* DRY COIL CONDITION (TOTAL CAPACITY =<br />
SENSIBLE CAPACITY)<br />
TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE<br />
VALID ONLY FOR WET COIL<br />
ALL TEMPERATURES IN DEGREES F.<br />
TWJ036CA WITH TWE030CA4 AT 1100 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)<br />
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.<br />
D.B. W.B. CAP. 72 74 76 78 80 KW<br />
59 33.9 25.9 27.8 29.7 31.6 33.4 2.52<br />
85 63 36.7 22.4 24.3 26.1 28.0 29.9 2.60<br />
67 39.5 18.4 20.3 22.1 24.0 25.9 2.68<br />
71 42.5 14.3 16.2 18.0 19.9 21.8 2.77<br />
59 33.4 25.7 27.6 29.4 31.3 33.2 2.65<br />
90 63 36.1 22.1 24.0 25.9 27.8 29.6 2.73<br />
67 38.9 18.1 20.0 21.9 23.8 25.6 2.82<br />
71 41.8 14.0 15.9 17.8 19.7 21.5 2.91<br />
59 32.8 25.4 27.3 29.2 31.1 32.9* 2.78<br />
95 63 35.5 21.9 23.8 25.6 27.5 29.4 2.87<br />
67 38.3 17.9 19.8 21.6 23.5 25.4 2.95<br />
71 41.2 13.8 15.7 17.5 19.4 21.3 3.04<br />
59 32.1 25.1 27.0 28.9 30.7 32.4* 2.92<br />
100 63 34.7 21.5 23.4 25.3 27.2 29.0 3.00<br />
67 37.4 17.6 19.4 21.3 23.2 25.1 3.09<br />
71 40.2 13.5 15.3 17.2 19.1 21.0 3.18<br />
59 31.3 24.8 26.7 28.5 30.4 31.8* 3.06<br />
105 63 33.9 21.2 23.1 25.0 26.8 28.7 3.14<br />
67 36.5 17.2 19.1 21.0 22.8 24.7 3.23<br />
71 39.3 13.1 15.0 16.9 18.7 20.6 3.31<br />
59 29.8 24.1 26.0 27.9 29.7 30.6* 3.35<br />
115 63 32.2 20.5 22.4 24.3 26.2 28.0 3.42<br />
67 34.8 16.5 18.4 20.3 22.2 24.0 3.50<br />
71 37.4 12.5 14.3 16.2 18.1 19.9 3.58<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(MULTIPLY OR ADD AS INDICATED)<br />
AIRFLOW 975 1275<br />
TOTAL CAP. X0.98 X1.02<br />
SENS. CAP. X0.95 X1.06<br />
COMPR. KW X0.99 X1.01<br />
VALUES AT 95/80/67 RATING CONDITIONS<br />
GROSS CAPACITY = 38500 BTUH<br />
AIRFLOW = 1125 CFM<br />
COMPRESSOR POWER = 2957 WATTS<br />
I.D. FAN POWER = 540 WATTS<br />
O.D. FAN POWER = 235 WATTS<br />
E.E.R. = 9.65 BTUH/WATT<br />
NOTE:RATED WITH 25 FEET OF 7/8 SUCT.<br />
AND 3/8 LIQUID LINE<br />
* DRY COIL CONDITION (TOTAL CAPACITY =<br />
SENSIBLE CAPACITY)<br />
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.<br />
ARE VALID ONLY FOR WET COIL<br />
ALL TEMPERATURES IN DEGREES F.<br />
TWJ036CA WITH TWE040CA4-B AT 1400 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)<br />
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.<br />
D.B. W.B. CAP. 72 74 76 78 80 KW<br />
59 37.2 30.6 33.0 35.5 37.6* 38.5* 2.63<br />
85 63 40.1 25.8 28.3 30.7 33.1 35.6 2.71<br />
67 43.1 20.6 23.0 25.4 27.9 30.3 2.80<br />
71 46.2 15.2 17.6 20.1 22.5 25.0 2.89<br />
59 36.5 30.3 32.7 35.2 37.0* 37.9* 2.76<br />
90 63 39.3 25.5 28.0 30.4 32.8 35.3 2.85<br />
67 42.3 20.3 22.7 25.1 27.6 30.0 2.94<br />
71 45.3 14.9 17.3 19.8 22.2 24.7 3.03<br />
59 35.8 30.0 32.4 34.9 36.5* 37.3* 2.90<br />
95 63 38.6 25.2 27.7 30.1 32.5 35.0 2.99<br />
67 41.5 20.0 22.4 24.8 27.3 29.7 3.07<br />
71 44.4 14.6 17.0 19.5 21.9 24.4 3.17<br />
59 34.9 29.6 32.0 34.5 35.7* 36.5* 3.04<br />
100 63 37.6 24.8 27.3 29.7 32.1 34.6 3.13<br />
67 40.4 19.6 22.0 24.4 26.9 29.3 3.22<br />
71 43.3 14.2 16.6 19.1 21.5 24.0 3.31<br />
59 34.0 29.2 31.6 34.1* 34.9* 35.8* 3.19<br />
105 63 36.6 24.4 26.9 29.3 31.7 34.2 3.27<br />
67 39.3 19.2 21.6 24.0 26.5 28.9 3.36<br />
71 42.1 13.8 16.2 18.7 21.1 23.6 3.45<br />
59 32.1 28.4 30.8 32.6* 33.4* 34.2* 3.48<br />
115 63 34.6 23.6 26.1 28.5 30.9 33.4 3.56<br />
67 37.1 18.4 20.8 23.2 25.7 28.1 3.64<br />
71 39.8 13.0 15.4 17.9 20.3 22.8 3.73<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(MULTIPLY OR ADD AS INDICATED)<br />
AIRFLOW 1175 1525<br />
TOTAL CAP. X0.97 X1.01<br />
SENS. CAP. X0.92 X1.04<br />
COMPR. KW X0.98 X1.01<br />
VALUES AT 95/80/67 RATING CONDITIONS<br />
GROSS CAPACITY = 41300 BTUH<br />
AIRFLOW = 1350 CFM<br />
COMPRESSOR POWER = 3066 WATTS<br />
I.D. FAN POWER = 360 WATTS<br />
O.D. FAN POWER = 235 WATTS<br />
E.E.R. = 10.80 BTUH/WATT<br />
NOTE:RATED WITH 25 FEET OF 7/8 SUCT.<br />
AND 3/8 LIQUID LINE<br />
* DRY COIL CONDITION (TOTAL CAPACITY =<br />
SENSIBLE CAPACITY)<br />
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.<br />
ARE VALID ONLY FOR WET COIL<br />
ALL TEMPERATURES IN DEGREES F.<br />
10 TWE5-PRC001-EN-10-15-99
Performance<br />
<strong>Data</strong> Cooling<br />
Metric Units<br />
TWJ030CA WITH TWE040CA4-B AT 1868 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)<br />
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.<br />
D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW<br />
15.0 9.0 7.4 7.9 8.5 9.1* 9.3* 2.7<br />
29.4 17.2 9.7 6.2 6.8 7.4 8.0 8.6 2.8<br />
19.4 10.3 5.0 5.5 6.1 6.7 7.3 2.8<br />
21.7 11.0 3.7 4.2 4.8 5.4 6.0 2.9<br />
15.0 8.8 7.3 7.9 8.5 8.9* 9.1* 2.8<br />
32.2 17.2 9.5 6.2 6.7 7.3 7.9 8.5 2.9<br />
19.4 10.1 4.9 5.4 6.0 6.6 7.2 3.0<br />
21.7 10.8 3.6 4.2 4.7 5.3 5.9 3.1<br />
15.0 8.6 7.2 7.8 8.4 8.8* 9.0* 2.9<br />
35.0 17.2 9.3 6.1 6.7 7.2 7.8 8.4 3.0<br />
19.4 9.9 4.8 5.4 6.0 6.5 7.1 3.1<br />
21.7 10.6 3.5 4.1 4.7 5.2 5.8 3.2<br />
15.0 8.4 7.1 7.7 8.3 8.6* 8.8* 3.0<br />
37.8 17.2 9.1 6.0 6.6 7.1 7.7 8.3 3.1<br />
19.4 9.7 4.7 5.3 5.9 6.4 7.0 3.2<br />
21.7 10.3 3.4 4.0 4.6 5.2 5.7 3.3<br />
15.0 8.2 7.0 7.6 8.2 8.4* 8.6* 3.2<br />
40.6 17.2 8.8 5.9 6.4 7.0 7.6 8.2 3.3<br />
19.4 9.4 4.6 5.2 5.8 6.4 6.9 3.4<br />
21.7 10.0 3.3 3.9 4.5 5.1 5.7 3.5<br />
15.0 7.8 6.8 7.4 7.9* 8.0* 8.2* 3.5<br />
46.1 17.2 8.3 5.7 6.3 6.9 7.4 8.0 3.5<br />
19.4 8.9 4.4 5.0 5.6 6.2 6.7 3.6<br />
21.7 9.5 3.1 3.7 4.3 4.9 5.4 3.7<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(MULTIPLY OR ADD AS INDICATED)<br />
AIRFLOW 1656 2165<br />
TOTAL CAP. X0.98 X1.02<br />
SENS. CAP. X0.95 X1.07<br />
COMPR. KW X0.99 X1.01<br />
VALUES AT ARI RATING CONDITIONS<br />
GROSS CAPACITY = 9.99 KW<br />
AIRFLOW = 1910 CMH<br />
COMPRESSOR POWER = 3104 WATTS<br />
I.D. FAN POWER = 300 WATTS<br />
O.D. FAN POWER = 195 WATTS<br />
E.E.R. = 9.05 BTUH/WATT<br />
NOTE:RATED WITH 7.62 METERS OF 22 MM SUCT.<br />
AND 9.5 MM LIQUID LINES<br />
* DRY COIL CONDITION (TOTAL CAPACITY =<br />
SENSIBLE CAPACITY)<br />
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.<br />
ARE VALID ONLY FOR WET COIL<br />
ALL TEMPERATURES IN DEGREES C.<br />
TWJ036CA WITH TWE030CA4 AT 1868 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)<br />
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.<br />
D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW<br />
15.0 9.9 7.6 8.1 8.7 9.3 9.8 2.5<br />
29.4 17.2 10.8 6.6 7.1 7.6 8.2 8.8 2.6<br />
19.4 11.6 5.4 5.9 6.5 7.0 7.6 2.7<br />
21.7 12.5 4.2 4.7 5.3 5.8 6.4 2.8<br />
15.0 9.8 7.5 8.1 8.6 9.2 9.7 2.7<br />
32.2 17.2 10.6 6.5 7.0 7.6 8.1 8.7 2.7<br />
19.4 11.4 5.3 5.9 6.4 7.0 7.5 2.8<br />
21.7 12.2 4.1 4.7 5.2 5.8 6.3 2.9<br />
15.0 9.6 7.4 8.0 8.6 9.1 9.6* 2.8<br />
35.0 17.2 10.4 6.4 7.0 7.5 8.1 8.6 2.9<br />
19.4 11.2 5.2 5.8 6.3 6.9 7.4 3.0<br />
21.7 12.1 4.0 4.6 5.1 5.7 6.2 3.0<br />
15.0 9.4 7.4 7.9 8.5 9.0 9.5* 2.9<br />
37.8 17.2 10.2 6.3 6.9 7.4 8.0 8.5 3.0<br />
19.4 11.0 5.2 5.7 6.2 6.8 7.4 3.1<br />
21.7 11.8 4.0 4.5 5.0 5.6 6.2 3.2<br />
15.0 9.2 7.3 7.8 8.4 8.9 9.3* 3.1<br />
40.6 17.2 9.9 6.2 6.8 7.3 7.9 8.4 3.1<br />
19.4 10.7 5.0 5.6 6.2 6.7 7.2 3.2<br />
21.7 11.5 3.8 4.4 5.0 5.5 6.0 3.3<br />
15.0 8.7 7.1 7.6 8.2 8.7 9.0* 3.3<br />
46.1 17.2 9.4 6.0 6.6 7.1 7.7 8.2 3.4<br />
19.4 10.2 4.8 5.4 5.9 6.5 7.0 3.5<br />
21.7 11.0 3.7 4.2 4.7 5.3 5.8 3.6<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(MULTIPLY OR ADD AS INDICATED)<br />
AIRFLOW 1656 2165<br />
TOTAL CAP. X0.98 X1.02<br />
SENS. CAP. X0.95 X1.06<br />
COMPR. KW X0.99 X1.01<br />
VALUES AT ARI RATING CONDITIONS<br />
GROSS CAPACITY = 11.28 KW<br />
AIRFLOW = 1910 CMH<br />
COMPRESSOR POWER = 2957 WATTS<br />
I.D. FAN POWER = 540 WATTS<br />
O.D. FAN POWER = 235 WATTS<br />
E.E.R. = 9.65 BTUH/WATT<br />
NOTE:RATED WITH 7.62 METERS OF 22 MM SUCT.<br />
AND 9.5 MM LIQUID LINES<br />
* DRY COIL CONDITION (TOTAL CAPACITY =<br />
SENSIBLE CAPACITY)<br />
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.<br />
ARE VALID ONLY FOR WET COIL<br />
ALL TEMPERATURES IN DEGREES C.<br />
TWJ036CA WITH TWE040CA4-B AT 2378 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)<br />
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.<br />
D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW<br />
15.0 10.9 9.0 9.7 10.4 11.0* 11.3* 2.6<br />
29.4 17.2 11.7 7.6 8.3 9.0 9.7 10.4 2.7<br />
19.4 12.6 6.0 6.7 7.4 8.2 8.9 2.8<br />
21.7 13.5 4.5 5.2 5.9 6.6 7.3 2.9<br />
15.0 10.7 8.9 9.6 10.3 10.8* 11.1* 2.8<br />
32.2 17.2 11.5 7.5 8.2 8.9 9.6 10.3 2.8<br />
19.4 12.4 5.9 6.7 7.4 8.1 8.8 2.9<br />
21.7 13.3 4.4 5.1 5.8 6.5 7.2 3.0<br />
15.0 10.5 8.8 9.5 10.2 10.7* 10.9* 2.9<br />
35.0 17.2 11.3 7.4 8.1 8.8 9.5 10.3 3.0<br />
19.4 12.2 5.9 6.6 7.3 8.0 8.7 3.1<br />
21.7 13.0 4.3 5.0 5.7 6.4 7.1 3.2<br />
15.0 10.2 8.7 9.4 10.1 10.5* 10.7* 3.0<br />
37.8 17.2 11.0 7.3 8.0 8.7 9.4 10.1 3.1<br />
19.4 11.8 5.7 6.4 7.1 7.9 8.6 3.2<br />
21.7 12.7 4.2 4.9 5.6 6.3 7.0 3.3<br />
15.0 10.0 8.6 9.3 10.0* 10.2* 10.5* 3.2<br />
40.6 17.2 10.7 7.1 7.9 8.6 9.3 10.0 3.3<br />
19.4 11.5 5.6 6.3 7.0 7.8 8.5 3.4<br />
21.7 12.3 4.0 4.7 5.5 6.2 6.9 3.5<br />
15.0 9.4 8.3 9.0 9.6* 9.8* 10.0* 3.5<br />
46.1 17.2 10.1 6.9 7.6 8.4 9.1 9.8 3.6<br />
19.4 10.9 5.4 6.1 6.8 7.5 8.2 3.6<br />
21.7 11.7 3.8 4.5 5.2 5.9 6.7 3.7<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(MULTIPLY OR ADD AS INDICATED)<br />
AIRFLOW 1995 2590<br />
TOTAL CAP. X0.97 X1.01<br />
SENS. CAP. X0.92 X1.04<br />
COMPR. KW X0.98 X1.01<br />
VALUES AT ARI RATING CONDITIONS<br />
GROSS CAPACITY = 12.10 KW<br />
AIRFLOW = 2293 CMH<br />
COMPRESSOR POWER = 3066 WATTS<br />
I.D. FAN POWER = 360 WATTS<br />
O.D. FAN POWER = 235 WATTS<br />
E.E.R. = 10.80 BTUH/WATT<br />
NOTE:RATED WITH 7.62 METERS OF 22 MM SUCT.<br />
AND 9.5 MM LIQUID LINES<br />
* DRY COIL CONDITION (TOTAL CAPACITY =<br />
SENSIBLE CAPACITY)<br />
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.<br />
ARE VALID ONLY FOR WET COIL<br />
ALL TEMPERATURES IN DEGREES C.<br />
TWE5-PRC001-EN-10-15-99 11
Performance<br />
<strong>Data</strong> Cooling<br />
English Units<br />
TWA030CD WITH TWE030CA4 AT 1000 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)<br />
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.<br />
D.B. W.B. CAP. 72 74 76 78 80 KW<br />
59 28.8 22.6 24.4 26.1 27.8 29.2* 2.13<br />
85 63 31.0 19.3 21.0 22.8 24.5 26.2 2.21<br />
67 33.3 15.6 17.3 19.1 20.8 22.5 2.29<br />
71 35.7 11.8 13.6 15.3 17.0 18.7 2.37<br />
59 28.3 22.4 24.1 25.8 27.6 28.7* 2.24<br />
90 63 30.4 19.1 20.8 22.5 24.2 26.0 2.32<br />
67 32.7 15.4 17.1 18.8 20.5 22.3 2.40<br />
71 35.1 11.6 13.3 15.0 16.8 18.5 2.48<br />
59 27.7 22.2 23.9 25.6 27.3 28.3* 2.35<br />
95 63 29.9 18.9 20.6 22.3 24.0 25.7 2.42<br />
67 32.1 15.2 16.9 18.6 20.3 22.0 2.51<br />
71 34.4 11.4 13.1 14.8 16.5 18.2 2.59<br />
59 27.0 21.9 23.6 25.3 27.1* 27.7* 2.46<br />
100 63 29.1 18.5 20.3 22.0 23.7 25.4 2.54<br />
67 31.3 14.8 16.6 18.3 20.0 21.7 2.62<br />
71 33.5 11.1 12.8 14.5 16.2 17.9 2.70<br />
59 26.3 21.6 23.3 25.0 26.5* 27.2* 2.57<br />
105 63 28.3 18.2 20.0 21.7 23.4 25.1 2.65<br />
67 30.4 14.5 16.2 18.0 19.7 21.4 2.73<br />
71 32.6 10.7 12.5 14.2 15.9 17.6 2.81<br />
59 24.9 21.0 22.7 24.4 25.4* 26.0* 2.80<br />
115 63 26.8 17.6 19.3 21.1 22.8 24.5 2.87<br />
67 28.8 13.9 15.6 17.3 19.1 20.8 2.95<br />
71 30.8 10.1 11.8 13.6 15.3 17.0 3.02<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(MULTIPLY OR ADD AS INDICATED)<br />
AIRFLOW 875 1125<br />
TOTAL CAP. X0.98 X1.01<br />
SENS. CAP. X0.95 X1.05<br />
COMPR. KW X0.99 X1.01<br />
VALUES AT 95/80/67 RATING CONDITIONS<br />
GROSS CAPACITY = 32200 BTUH<br />
AIRFLOW = 1000 CFM<br />
COMPRESSOR POWER = 2505 WATTS<br />
I.D. FAN POWER = 440 WATTS<br />
O.D. FAN POWER = 214 WATTS<br />
E.E.R. = 9.55 BTUH/WATT<br />
NOTE:RATED WITH 25 FEET OF 7/8 SUCT.<br />
AND 3/8 LIQUID LINE<br />
* DRY COIL CONDITION (TOTAL CAPACITY =<br />
SENSIBLE CAPACITY)<br />
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.<br />
ARE VALID ONLY FOR WET COIL<br />
ALL TEMPERATURES IN DEGREES F.<br />
TWA030CD WITH TWE040CA4-B AT 1100 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)<br />
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.<br />
D.B. W.B. CAP. 72 74 76 78 80 KW<br />
59 30.8 25.2 27.1 29.1 31.0* 31.7* 2.21<br />
85 63 33.0 21.2 23.2 25.2 27.2 29.2 2.29<br />
67 35.4 16.9 18.9 20.9 22.9 24.9 2.37<br />
71 37.9 12.5 14.5 16.5 18.5 20.5 2.45<br />
59 30.1 24.9 26.9 28.9 30.5* 31.2* 2.32<br />
90 63 32.3 21.0 23.0 24.9 26.9 28.9 2.40<br />
67 34.7 16.7 18.6 20.6 22.6 24.6 2.48<br />
71 37.0 12.3 14.2 16.2 18.2 20.2 2.56<br />
59 29.5 24.6 26.6 28.6 29.9* 30.6* 2.43<br />
95 63 31.6 20.7 22.7 24.7 26.7 28.6 2.51<br />
67 33.9 16.4 18.4 20.4 22.3 24.3 2.59<br />
71 36.2 12.0 14.0 16.0 17.9 19.9 2.67<br />
59 28.6 24.2 26.2 28.2 29.3* 29.9* 2.54<br />
100 63 30.8 20.3 22.3 24.3 26.3 28.3 2.62<br />
67 32.9 16.0 18.0 20.0 22.0 24.0 2.70<br />
71 35.2 11.6 13.6 15.6 17.6 19.6 2.78<br />
59 27.8 23.9 25.9 27.9* 28.6* 29.2* 2.66<br />
105 63 29.9 20.0 22.0 23.9 25.9 27.9 2.73<br />
67 32.0 15.7 17.6 19.6 21.6 23.6 2.81<br />
71 34.2 11.3 13.2 15.2 17.2 19.2 2.90<br />
59 26.2 23.2 25.2 26.5* 27.2* 27.8* 2.89<br />
115 63 28.1 19.3 21.2 23.2 25.2 27.2 2.96<br />
67 30.1 14.9 16.9 18.9 20.9 22.9 3.04<br />
71 32.1 10.6 12.5 14.5 16.5 18.5 3.11<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(MULTIPLY OR ADD AS INDICATED)<br />
AIRFLOW 975 1275<br />
TOTAL CAP. X0.98 X1.02<br />
SENS. CAP. X0.95 X1.07<br />
COMPR. KW X0.99 X1.01<br />
VALUES AT 95/80/67 RATING CONDITIONS<br />
GROSS CAPACITY = 34100 BTUH<br />
AIRFLOW = 1125 CFM<br />
COMPRESSOR POWER = 2594 WATTS<br />
I.D. FAN POWER = 300 WATTS<br />
O.D. FAN POWER = 214 WATTS<br />
E.E.R. = 10.45 BTUH/WATT<br />
NOTE:RATED WITH 25 FEET OF 7/8 SUCT.<br />
AND 3/8 LIQUID LINE<br />
* DRY COIL CONDITION (TOTAL CAPACITY =<br />
SENSIBLE CAPACITY)<br />
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.<br />
ARE VALID ONLY FOR WET COIL<br />
ALL TEMPERATURES IN DEGREES F.<br />
TWA040CD WITH TWE040CA4-B AT 1500 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)<br />
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.<br />
D.B. W.B. CAP. 72 74 76 78 80 KW<br />
59 39.3 32.2 34.8 37.4 39.6* 40.5* 2.79<br />
85 63 42.2 27.1 29.7 32.3 34.9 37.4 2.90<br />
67 45.2 21.5 24.1 26.7 29.3 31.8 3.01<br />
71 48.4 15.8 18.4 21.0 23.6 26.1 3.13<br />
59 38.5 31.9 34.4 37.0 39.0* 39.9* 2.93<br />
90 63 41.4 26.8 29.4 32.0 34.5 37.1 3.04<br />
67 44.3 21.2 23.8 26.4 28.9 31.5 3.16<br />
71 47.4 15.5 18.1 20.7 23.2 25.8 3.29<br />
59 37.7 31.5 34.1 36.7 38.4* 39.2* 3.07<br />
95 63 40.5 26.5 29.1 31.6 34.2 36.8 3.18<br />
67 43.4 20.9 23.5 26.0 28.6 31.2 3.31<br />
71 46.4 15.2 17.7 20.3 22.9 25.5 3.44<br />
59 36.7 31.1 33.7 36.3 37.5* 38.4* 3.21<br />
100 63 39.4 26.0 28.6 31.2 33.8 36.4 3.33<br />
67 42.3 20.5 23.0 25.6 28.2 30.8 3.46<br />
71 45.2 14.7 17.3 19.9 22.5 25.1 3.59<br />
59 35.7 30.7 33.3 35.9* 36.7* 37.6* 3.36<br />
105 63 38.4 25.6 28.2 30.8 33.4 35.9 3.48<br />
67 41.1 20.0 22.6 25.2 27.8 30.3 3.61<br />
71 44.0 14.3 16.9 19.5 22.1 24.6 3.75<br />
59 33.7 29.9 32.4 34.2* 35.0* 35.9* 3.65<br />
115 63 36.2 24.8 27.4 29.9 32.5 35.1 3.78<br />
67 38.8 19.2 21.8 24.3 26.9 29.5 3.92<br />
71 41.5 13.5 16.1 18.6 21.2 23.8 4.06<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(MULTIPLY OR ADD AS INDICATED)<br />
AIRFLOW 1325 1700<br />
TOTAL CAP. X0.98 X1.01<br />
SENS. CAP. X0.95 X1.06<br />
COMPR. KW X0.99 X1.01<br />
VALUES AT 95/80/67 RATING CONDITIONS<br />
GROSS CAPACITY = 43500 BTUH<br />
AIRFLOW = 1500 CFM<br />
COMPRESSOR POWER = 3309 WATTS<br />
I.D. FAN POWER = 420 WATTS<br />
O.D. FAN POWER = 244 WATTS<br />
E.E.R. = 10.45 BTUH/WATT<br />
NOTE:RATED WITH 25 FEET OF 1-1/8 SUCT.<br />
AND 3/8 LIQUID LINE<br />
* DRY COIL CONDITION (TOTAL CAPACITY =<br />
SENSIBLE CAPACITY)<br />
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.<br />
ARE VALID ONLY FOR WET COIL<br />
ALL TEMPERATURES IN DEGREES F.<br />
12 TWE5-PRC001-EN-10-15-99
Performance<br />
<strong>Data</strong> Cooling<br />
Metric Units<br />
TWA030CD WITH TWE030CA4 AT 1698 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)<br />
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.<br />
D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW<br />
15.0 8.4 6.6 7.1 7.6 8.1 8.6* 2.1<br />
29.4 17.2 9.1 5.7 6.2 6.7 7.2 7.7 2.2<br />
19.4 9.8 4.6 5.1 5.6 6.1 6.6 2.3<br />
21.7 10.5 3.5 4.0 4.5 5.0 5.5 2.4<br />
15.0 8.3 6.6 7.1 7.6 8.1 8.4* 2.2<br />
32.2 17.2 8.9 5.6 6.1 6.6 7.1 7.6 2.3<br />
19.4 9.6 4.5 5.0 5.5 6.0 6.5 2.4<br />
21.7 10.3 3.4 3.9 4.4 4.9 5.4 2.5<br />
15.0 8.1 6.5 7.0 7.5 8.0 8.3* 2.3<br />
35.0 17.2 8.8 5.5 6.0 6.5 7.0 7.5 2.4<br />
19.4 9.4 4.5 5.0 5.4 5.9 6.4 2.5<br />
21.7 10.1 3.3 3.8 4.3 4.8 5.3 2.6<br />
15.0 7.9 6.4 6.9 7.4 7.9* 8.1* 2.5<br />
37.8 17.2 8.5 5.4 5.9 6.4 6.9 7.4 2.5<br />
19.4 9.2 4.3 4.9 5.4 5.9 6.4 2.6<br />
21.7 9.8 3.3 3.8 4.2 4.7 5.2 2.7<br />
15.0 7.7 6.3 6.8 7.3 7.8* 8.0* 2.6<br />
40.6 17.2 8.3 5.3 5.9 6.4 6.9 7.4 2.7<br />
19.4 8.9 4.2 4.7 5.3 5.8 6.3 2.7<br />
21.7 9.6 3.1 3.7 4.2 4.7 5.2 2.8<br />
15.0 7.3 6.2 6.7 7.1 7.4* 7.6* 2.8<br />
46.1 17.2 7.9 5.2 5.7 6.2 6.7 7.2 2.9<br />
19.4 8.4 4.1 4.6 5.1 5.6 6.1 3.0<br />
21.7 9.0 3.0 3.5 4.0 4.5 5.0 3.0<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(MULTIPLY OR ADD AS INDICATED)<br />
AIRFLOW 1486 1910<br />
TOTAL CAP. X0.98 X1.01<br />
SENS. CAP. X0.95 X1.05<br />
COMPR. KW X0.99 X1.01<br />
VALUES AT ARI RATING CONDITIONS<br />
GROSS CAPACITY = 9.43 KW<br />
AIRFLOW = 1698 CMH<br />
COMPRESSOR POWER = 2505 WATTS<br />
I.D. FAN POWER = 440 WATTS<br />
O.D. FAN POWER = 214 WATTS<br />
E.E.R. = 9.55 BTUH/WATT<br />
NOTE:RATED WITH 7.62 METERS OF 22 MM SUCT.<br />
AND 9.5 MM LIQUID LINES<br />
* DRY COIL CONDITION (TOTAL CAPACITY =<br />
SENSIBLE CAPACITY)<br />
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.<br />
ARE VALID ONLY FOR WET COIL<br />
ALL TEMPERATURES IN DEGREES C.<br />
TWA030CD WITH TWE040CA4-B AT 1868 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)<br />
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.<br />
D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW<br />
15.0 9.0 7.4 7.9 8.5 9.1* 9.3* 2.2<br />
29.4 17.2 9.7 6.2 6.8 7.4 8.0 8.6 2.3<br />
19.4 10.4 5.0 5.5 6.1 6.7 7.3 2.4<br />
21.7 11.1 3.7 4.2 4.8 5.4 6.0 2.5<br />
15.0 8.8 7.3 7.9 8.5 8.9* 9.1* 2.3<br />
32.2 17.2 9.5 6.2 6.7 7.3 7.9 8.5 2.4<br />
19.4 10.2 4.9 5.4 6.0 6.6 7.2 2.5<br />
21.7 10.8 3.6 4.2 4.7 5.3 5.9 2.6<br />
15.0 8.6 7.2 7.8 8.4 8.8* 9.0* 2.4<br />
35.0 17.2 9.3 6.1 6.7 7.2 7.8 8.4 2.5<br />
19.4 9.9 4.8 5.4 6.0 6.5 7.1 2.6<br />
21.7 10.6 3.5 4.1 4.7 5.2 5.8 2.7<br />
15.0 8.4 7.1 7.7 8.3 8.6* 8.8* 2.5<br />
37.8 17.2 9.0 5.9 6.5 7.1 7.7 8.3 2.6<br />
19.4 9.6 4.7 5.3 5.9 6.4 7.0 2.7<br />
21.7 10.3 3.4 4.0 4.6 5.2 5.7 2.8<br />
15.0 8.1 7.0 7.6 8.2* 8.4* 8.6* 2.7<br />
40.6 17.2 8.8 5.9 6.4 7.0 7.6 8.2 2.7<br />
19.4 9.4 4.6 5.2 5.7 6.3 6.9 2.8<br />
21.7 10.0 3.3 3.9 4.5 5.0 5.6 2.9<br />
15.0 7.7 6.8 7.4 7.8* 8.0* 8.1* 2.9<br />
46.1 17.2 8.2 5.7 6.2 6.8 7.4 8.0 3.0<br />
19.4 8.8 4.4 5.0 5.5 6.1 6.7 3.0<br />
21.7 9.4 3.1 3.7 4.2 4.8 5.4 3.1<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(MULTIPLY OR ADD AS INDICATED)<br />
AIRFLOW 1656 2165<br />
TOTAL CAP. X0.98 X1.02<br />
SENS. CAP. X0.95 X1.07<br />
COMPR. KW X0.99 X1.01<br />
VALUES AT ARI RATING CONDITIONS<br />
GROSS CAPACITY = 9.99 KW<br />
AIRFLOW = 1910 CMH<br />
COMPRESSOR POWER = 2594 WATTS<br />
I.D. FAN POWER = 300 WATTS<br />
O.D. FAN POWER = 214 WATTS<br />
E.E.R. = 10.45 BTUH/WATT<br />
NOTE:RATED WITH 7.62 METERS OF 22 MM SUCT.<br />
AND 9.5 MM LIQUID LINES<br />
* DRY COIL CONDITION (TOTAL CAPACITY =<br />
SENSIBLE CAPACITY)<br />
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.<br />
ARE VALID ONLY FOR WET COIL<br />
ALL TEMPERATURES IN DEGREES C.<br />
TWA040CD WITH TWE040CA4-B AT 2547 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)<br />
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.<br />
D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW<br />
15.0 11.5 9.4 10.2 11.0 11.6* 11.9* 2.8<br />
29.4 17.2 12.4 7.9 8.7 9.5 10.2 11.0 2.9<br />
19.4 13.2 6.3 7.1 7.8 8.6 9.3 3.0<br />
21.7 14.2 4.6 5.4 6.2 6.9 7.6 3.1<br />
15.0 11.3 9.3 10.1 10.8 11.4* 11.7* 2.9<br />
32.2 17.2 12.1 7.9 8.6 9.4 10.1 10.9 3.0<br />
19.4 13.0 6.2 7.0 7.7 8.5 9.2 3.2<br />
21.7 13.9 4.5 5.3 6.1 6.8 7.6 3.3<br />
15.0 11.0 9.2 10.0 10.8 11.3* 11.5* 3.1<br />
35.0 17.2 11.9 7.8 8.5 9.3 10.0 10.8 3.2<br />
19.4 12.7 6.1 6.9 7.6 8.4 9.1 3.3<br />
21.7 13.6 4.5 5.2 5.9 6.7 7.5 3.4<br />
15.0 10.8 9.1 9.9 10.6 11.0* 11.3* 3.2<br />
37.8 17.2 11.5 7.6 8.4 9.1 9.9 10.7 3.3<br />
19.4 12.4 6.0 6.7 7.5 8.3 9.0 3.5<br />
21.7 13.2 4.3 5.1 5.8 6.6 7.4 3.6<br />
15.0 10.5 9.0 9.8 10.5* 10.8* 11.0* 3.4<br />
40.6 17.2 11.3 7.5 8.3 9.0 9.8 10.5 3.5<br />
19.4 12.0 5.9 6.6 7.4 8.1 8.9 3.6<br />
21.7 12.9 4.2 5.0 5.7 6.5 7.2 3.8<br />
15.0 9.9 8.8 9.5 10.0* 10.3* 10.5* 3.7<br />
46.1 17.2 10.6 7.3 8.0 8.8 9.5 10.3 3.8<br />
19.4 11.4 5.6 6.4 7.1 7.9 8.6 3.9<br />
21.7 12.2 4.0 4.7 5.4 6.2 7.0 4.1<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(MULTIPLY OR ADD AS INDICATED)<br />
AIRFLOW 2250 2887<br />
TOTAL CAP. X0.98 X1.01<br />
SENS. CAP. X0.95 X1.06<br />
COMPR. KW X0.99 X1.01<br />
VALUES AT ARI RATING CONDITIONS<br />
GROSS CAPACITY = 12.75 KW<br />
AIRFLOW = 2547 CMH<br />
COMPRESSOR POWER = 3309 WATTS<br />
I.D. FAN POWER = 420 WATTS<br />
O.D. FAN POWER = 244 WATTS<br />
E.E.R. = 10.45 BTUH/WATT<br />
NOTE:RATED WITH 7.62 METERS OF 28.6 MM SUCT.<br />
AND 9.5 MM LIQUID LINES<br />
* DRY COIL CONDITION (TOTAL CAPACITY =<br />
SENSIBLE CAPACITY)<br />
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.<br />
ARE VALID ONLY FOR WET COIL<br />
ALL TEMPERATURES IN DEGREES C.<br />
TWE5-PRC001-EN-10-15-99 13
Performance<br />
<strong>Data</strong> Cooling<br />
English Units<br />
TWA040CD WITH TWE050CA5-C AT 1500 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)<br />
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.<br />
D.B. W.B. CAP. 72 74 76 78 80 KW<br />
59 40.1 33.2 35.9 38.6 40.6* 41.5* 2.78<br />
85 63 43.1 28.0 30.7 33.3 36.0 38.7 2.89<br />
67 46.1 22.2 24.9 27.5 30.2 32.9 3.01<br />
71 49.3 16.3 18.9 21.6 24.3 27.0 3.13<br />
59 39.1 32.8 35.5 38.2 39.8* 40.7* 2.91<br />
90 63 42.0 27.5 30.2 32.9 35.6 38.2 3.02<br />
67 44.9 21.7 24.4 27.1 29.8 32.4 3.14<br />
71 48.0 15.8 18.5 21.2 23.8 26.5 3.27<br />
59 38.1 32.4 35.0 37.7 38.9* 39.8* 3.04<br />
95 63 40.9 27.1 29.8 32.4 35.1 37.8 3.15<br />
67 43.7 21.3 24.0 26.6 29.3 32.0 3.28<br />
71 46.7 15.4 18.0 20.7 23.4 26.1 3.41<br />
59 37.0 31.9 34.6 37.2* 38.0* 38.9* 3.16<br />
100 63 39.7 26.6 29.3 32.0 34.6 37.3 3.29<br />
67 42.5 20.8 23.5 26.2 28.8 31.5 3.41<br />
71 45.3 14.9 17.6 20.2 22.9 25.6 3.55<br />
59 35.9 31.4 34.1 36.3* 37.1* 37.9* 3.30<br />
105 63 38.5 26.1 28.8 31.5 34.2 36.8 3.42<br />
67 41.2 20.3 23.0 25.7 28.4 31.0 3.55<br />
71 44.0 14.4 17.1 19.8 22.4 25.1 3.69<br />
59 33.6 30.5 33.2 34.4* 35.2* 36.0* 3.56<br />
115 63 36.1 25.2 27.9 30.6 33.2 35.9 3.69<br />
67 38.6 19.4 22.1 24.7 27.4 30.1 3.82<br />
71 41.2 13.5 16.2 18.8 21.5 24.2 3.96<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(MULTIPLY OR ADD AS INDICATED)<br />
AIRFLOW 1325 1700<br />
TOTAL CAP. X0.99 X1.01<br />
SENS. CAP. X0.95 X1.06<br />
COMPR. KW X0.99 X1.01<br />
VALUES AT 95/80/67 RATING CONDITIONS<br />
GROSS CAPACITY = 43800 BTUH<br />
AIRFLOW = 1500 CFM<br />
COMPRESSOR POWER = 3279 WATTS<br />
I.D. FAN POWER = 510 WATTS<br />
O.D. FAN POWER = 244 WATTS<br />
E.E.R. = 10.30 BTUH/WATT<br />
NOTE:RATED WITH 25 FEET OF 1-1/8 SUCT.<br />
AND 3/8 LIQUID LINE<br />
* DRY COIL CONDITION (TOTAL CAPACITY =<br />
SENSIBLE CAPACITY)<br />
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.<br />
ARE VALID ONLY FOR WET COIL<br />
ALL TEMPERATURES IN DEGREES F.<br />
TWA050CD WITH TWE050CA5-C AT 1800 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)<br />
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.<br />
D.B. W.B. CAP. 72 74 76 78 80 KW<br />
59 48.8 39.6 42.7 45.8 49.0* 50.1* 3.60<br />
85 63 52.3 33.4 36.5 39.6 42.7 45.9 3.72<br />
67 55.9 26.6 29.7 32.8 35.9 39.0 3.84<br />
71 59.6 19.6 22.7 25.8 29.0 32.1 3.96<br />
59 47.6 39.1 42.2 45.3 48.0* 49.1* 3.77<br />
90 63 51.0 32.9 36.0 39.1 42.2 45.3 3.88<br />
67 54.5 26.0 29.2 32.3 35.4 38.5 4.00<br />
71 58.1 19.1 22.2 25.3 28.4 31.5 4.13<br />
59 46.4 38.5 41.6 44.8 47.0* 48.1* 3.93<br />
95 63 49.7 32.3 35.5 38.6 41.7 44.8 4.05<br />
67 53.1 25.5 28.6 31.7 34.9 38.0 4.17<br />
71 56.6 18.6 21.7 24.8 27.9 31.0 4.30<br />
59 45.1 38.0 41.1 44.2 45.9* 46.9* 4.10<br />
100 63 48.2 31.8 34.9 38.0 41.1 44.2 4.21<br />
67 51.5 24.9 28.1 31.2 34.3 37.4 4.33<br />
71 54.9 18.0 21.1 24.2 27.3 30.4 4.46<br />
59 43.7 37.4 40.5 43.6 44.8* 45.8* 4.27<br />
105 63 46.8 31.2 34.3 37.4 40.5 43.7 4.38<br />
67 50.0 24.4 27.5 30.6 33.7 36.8 4.50<br />
71 53.2 17.4 20.5 23.6 26.8 29.9 4.62<br />
59 41.1 36.3 39.4 41.6* 42.5* 43.5* 4.61<br />
115 63 43.9 30.1 33.2 36.3 39.4 42.5 4.71<br />
67 46.9 23.2 26.3 29.5 32.6 35.7 4.83<br />
71 49.9 16.3 19.4 22.5 25.6 28.7 4.94<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(MULTIPLY OR ADD AS INDICATED)<br />
AIRFLOW 1575 2025<br />
TOTAL CAP. X0.99 X1.01<br />
SENS. CAP. X0.95 X1.05<br />
COMPR. KW X0.99 X1.01<br />
VALUES AT 95/80/67 RATING CONDITIONS<br />
GROSS CAPACITY = 53100 BTUH<br />
AIRFLOW = 1800 CFM<br />
COMPRESSOR POWER = 4171 WATTS<br />
I.D. FAN POWER = 750 WATTS<br />
O.D. FAN POWER = 255 WATTS<br />
E.E.R. = 9.65 BTUH/WATT<br />
NOTE:RATED WITH 25 FEET OF 1-1/8 SUCT.<br />
AND 3/8 LIQUID LINE<br />
* DRY COIL CONDITION (TOTAL CAPACITY =<br />
SENSIBLE CAPACITY)<br />
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.<br />
ARE VALID ONLY FOR WET COIL<br />
ALL TEMPERATURES IN DEGREES F.<br />
TWA060CD WITH TWE050CA5-C AT 1800 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)<br />
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.<br />
D.B. W.B. CAP. 72 74 76 78 80 KW<br />
59 57.2 43.7 46.8 50.0 53.1 56.3 4.61<br />
85 63 61.6 37.6 40.7 43.9 47.0 50.2 4.77<br />
67 66.1 30.8 34.0 37.1 40.2 43.4 4.93<br />
71 70.8 23.8 27.0 30.1 33.3 36.4 5.10<br />
59 55.9 43.1 46.3 49.4 52.6 55.7 4.80<br />
90 63 60.1 37.0 40.2 43.3 46.5 49.6 4.96<br />
67 64.6 30.2 33.4 36.5 39.7 42.8 5.13<br />
71 69.1 23.2 26.4 29.5 32.7 35.8 5.30<br />
59 54.6 42.5 45.7 48.8 52.0 55.0* 5.00<br />
95 63 58.7 36.4 39.6 42.7 45.9 49.0 5.16<br />
67 63.1 29.6 32.8 35.9 39.1 42.2 5.33<br />
71 67.5 22.7 25.8 29.0 32.1 35.3 5.50<br />
59 53.2 41.9 45.1 48.2 51.4 53.8* 5.23<br />
100 63 57.2 35.8 38.9 42.1 45.2 48.4 5.38<br />
67 61.4 29.0 32.1 35.3 38.4 41.6 5.55<br />
71 65.8 22.0 25.2 28.3 31.5 34.6 5.71<br />
59 51.8 41.3 44.4 47.6 50.7 52.7* 5.45<br />
105 63 55.7 35.2 38.3 41.5 44.6 47.8 5.61<br />
67 59.8 28.4 31.5 34.7 37.8 40.9 5.77<br />
71 64.0 21.4 24.5 27.7 30.8 34.0 5.93<br />
59 48.9 40.1 43.2 46.3 49.3* 50.4* 5.91<br />
115 63 52.6 33.9 37.1 40.2 43.4 46.5 6.06<br />
67 56.5 27.1 30.2 33.4 36.5 39.7 6.20<br />
71 60.5 20.1 23.3 26.4 29.6 32.7 6.36<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(MULTIPLY OR ADD AS INDICATED)<br />
AIRFLOW 1575 2025<br />
TOTAL CAP. X0.98 X1.01<br />
SENS. CAP. X0.95 X1.05<br />
COMPR. KW X0.99 X1.01<br />
VALUES AT 95/80/67 RATING CONDITIONS<br />
GROSS CAPACITY = 63100 BTUH<br />
AIRFLOW = 1800 CFM<br />
COMPRESSOR POWER = 5326 WATTS<br />
I.D. FAN POWER = 750 WATTS<br />
O.D. FAN POWER = 395 WATTS<br />
E.E.R. = 9.20 BTUH/WATT<br />
NOTE:RATED WITH 25 FEET OF 1-1/8 SUCT.<br />
AND 3/8 LIQUID LINE<br />
* DRY COIL CONDITION (TOTAL CAPACITY =<br />
SENSIBLE CAPACITY)<br />
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.<br />
ARE VALID ONLY FOR WET COIL<br />
ALL TEMPERATURES IN DEGREES F.<br />
14 TWE5-PRC001-EN-10-15-99
Performance<br />
<strong>Data</strong> Cooling<br />
Metric Units<br />
TWA040CD WITH TWE050CA5-C AT 2547 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)<br />
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.<br />
D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW<br />
15.0 11.7 9.7 10.5 11.3 11.9* 12.2* 2.8<br />
29.4 17.2 12.6 8.2 9.0 9.8 10.5 11.3 2.9<br />
19.4 13.5 6.5 7.3 8.1 8.8 9.6 3.0<br />
21.7 14.4 4.8 5.5 6.3 7.1 7.9 3.1<br />
15.0 11.5 9.6 10.4 11.2 11.7* 11.9* 2.9<br />
32.2 17.2 12.3 8.1 8.8 9.6 10.4 11.2 3.0<br />
19.4 13.2 6.4 7.1 7.9 8.7 9.5 3.1<br />
21.7 14.1 4.6 5.4 6.2 7.0 7.8 3.3<br />
15.0 11.2 9.5 10.3 11.0 11.4* 11.7* 3.0<br />
35.0 17.2 12.0 7.9 8.7 9.5 10.3 11.1 3.2<br />
19.4 12.8 6.2 7.0 7.8 8.6 9.4 3.3<br />
21.7 13.7 4.5 5.3 6.1 6.9 7.6 3.4<br />
15.0 10.8 9.3 10.1 10.9* 11.1* 11.4* 3.2<br />
37.8 17.2 11.6 7.8 8.6 9.4 10.1 10.9 3.3<br />
19.4 12.5 6.1 6.9 7.7 8.4 9.2 3.4<br />
21.7 13.3 4.4 5.2 5.9 6.7 7.5 3.5<br />
15.0 10.5 9.2 10.0 10.6* 10.9* 11.1* 3.3<br />
40.6 17.2 11.3 7.6 8.4 9.2 10.0 10.8 3.4<br />
19.4 12.1 5.9 6.7 7.5 8.3 9.1 3.5<br />
21.7 12.9 4.2 5.0 5.8 6.6 7.4 3.7<br />
15.0 9.8 8.9 9.7 10.1* 10.3* 10.5* 3.6<br />
46.1 17.2 10.6 7.4 8.2 9.0 9.7 10.5 3.7<br />
19.4 11.3 5.7 6.5 7.2 8.0 8.8 3.8<br />
21.7 12.1 4.0 4.7 5.5 6.3 7.1 4.0<br />
TWA050CD WITH TWE050CA5-C AT 3057 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)<br />
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.<br />
D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW<br />
15.0 14.3 11.6 12.5 13.4 14.4* 14.7* 3.6<br />
29.4 17.2 15.3 9.8 10.7 11.6 12.5 13.4 3.7<br />
19.4 16.4 7.8 8.7 9.6 10.5 11.4 3.8<br />
21.7 17.5 5.7 6.7 7.6 8.5 9.4 4.0<br />
15.0 13.9 11.5 12.4 13.3 14.1* 14.4* 3.8<br />
32.2 17.2 14.9 9.6 10.5 11.5 12.4 13.3 3.9<br />
19.4 16.0 7.6 8.6 9.5 10.4 11.3 4.0<br />
21.7 17.0 5.6 6.5 7.4 8.3 9.2 4.1<br />
15.0 13.6 11.3 12.2 13.1 13.8* 14.1* 3.9<br />
35.0 17.2 14.6 9.5 10.4 11.3 12.2 13.1 4.1<br />
19.4 15.6 7.5 8.4 9.3 10.2 11.1 4.2<br />
21.7 16.6 5.4 6.4 7.3 8.2 9.1 4.3<br />
15.0 13.2 11.1 12.0 13.0 13.4* 13.7* 4.1<br />
37.8 17.2 14.1 9.3 10.2 11.1 12.0 13.0 4.2<br />
19.4 15.1 7.3 8.2 9.1 10.0 11.0 4.3<br />
21.7 16.1 5.3 6.2 7.1 8.0 8.9 4.5<br />
15.0 12.8 11.0 11.9 12.8 13.1* 13.4* 4.3<br />
40.6 17.2 13.7 9.1 10.0 11.0 11.9 12.8 4.4<br />
19.4 14.6 7.1 8.1 9.0 9.9 10.8 4.5<br />
21.7 15.6 5.1 6.0 6.9 7.9 8.8 4.6<br />
15.0 12.0 10.6 11.5 12.2* 12.5* 12.7* 4.6<br />
46.1 17.2 12.9 8.8 9.7 10.6 11.5 12.5 4.7<br />
19.4 13.7 6.8 7.7 8.6 9.6 10.5 4.8<br />
21.7 14.6 4.8 5.7 6.6 7.5 8.4 4.9<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(MULTIPLY OR ADD AS INDICATED)<br />
AIRFLOW 2250 2887<br />
TOTAL CAP. X0.99 X1.01<br />
SENS. CAP. X0.95 X1.06<br />
COMPR. KW X0.99 X1.01<br />
VALUES AT ARI RATING CONDITIONS<br />
GROSS CAPACITY = 12.83 KW<br />
AIRFLOW = 2547 CMH<br />
COMPRESSOR POWER = 3279 WATTS<br />
I.D. FAN POWER = 510 WATTS<br />
O.D. FAN POWER = 244 WATTS<br />
E.E.R. = 10.30 BTUH/WATT<br />
NOTE:RATED WITH 7.62 METERS OF 28.6 MM SUCT.<br />
AND 9.5 MM LIQUID LINES<br />
* DRY COIL CONDITION (TOTAL CAPACITY =<br />
SENSIBLE CAPACITY)<br />
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.<br />
ARE VALID ONLY FOR WET COIL<br />
ALL TEMPERATURES IN DEGREES C.<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(MULTIPLY OR ADD AS INDICATED)<br />
AIRFLOW 2675 3439<br />
TOTAL CAP. X0.99 X1.01<br />
SENS. CAP. X0.95 X1.05<br />
COMPR. KW X0.99 X1.01<br />
VALUES AT ARI RATING CONDITIONS<br />
GROSS CAPACITY = 15.56 KW<br />
AIRFLOW = 3057 CMH<br />
COMPRESSOR POWER = 4171 WATTS<br />
I.D. FAN POWER = 750 WATTS<br />
O.D. FAN POWER = 255 WATTS<br />
E.E.R. = 9.65 BTUH/WATT<br />
NOTE:RATED WITH 7.62 METERS OF 28.6 MM SUCT.<br />
AND 9.5 MM LIQUID LINES<br />
* DRY COIL CONDITION (TOTAL CAPACITY =<br />
SENSIBLE CAPACITY)<br />
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.<br />
ARE VALID ONLY FOR WET COIL<br />
ALL TEMPERATURES IN DEGREES C.<br />
TWA060CD WITH TWE050CA5-C AT 3057 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)<br />
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.<br />
D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW<br />
15.0 16.8 12.8 13.7 14.6 15.6 16.5 4.6<br />
29.4 17.2 18.0 11.0 11.9 12.9 13.8 14.7 4.8<br />
19.4 19.4 9.0 10.0 10.9 11.8 12.7 4.9<br />
21.7 20.7 7.0 7.9 8.8 9.8 10.7 5.1<br />
15.0 16.4 12.6 13.6 14.5 15.4 16.3 4.8<br />
32.2 17.2 17.6 10.8 11.8 12.7 13.6 14.5 5.0<br />
19.4 18.9 8.8 9.8 10.7 11.6 12.5 5.1<br />
21.7 20.2 6.8 7.7 8.6 9.6 10.5 5.3<br />
15.0 16.0 12.5 13.4 14.3 15.2 16.1* 5.0<br />
35.0 17.2 17.2 10.7 11.6 12.5 13.4 14.4 5.2<br />
19.4 18.5 8.7 9.6 10.5 11.5 12.4 5.3<br />
21.7 19.8 6.7 7.6 8.5 9.4 10.3 5.5<br />
15.0 15.6 12.3 13.2 14.1 15.1 15.8* 5.2<br />
37.8 17.2 16.8 10.5 11.4 12.3 13.2 14.2 5.4<br />
19.4 18.0 8.5 9.4 10.3 11.3 12.2 5.6<br />
21.7 19.3 6.4 7.4 8.3 9.2 10.1 5.7<br />
15.0 15.2 12.1 13.0 13.9 14.9 15.4* 5.4<br />
40.6 17.2 16.3 10.3 11.2 12.2 13.1 14.0 5.6<br />
19.4 17.5 8.3 9.2 10.2 11.1 12.0 5.8<br />
21.7 18.8 6.3 7.2 8.1 9.0 10.0 5.9<br />
15.0 14.3 11.7 12.7 13.6 14.4* 14.8* 5.9<br />
46.1 17.2 15.4 9.9 10.9 11.8 12.7 13.6 6.1<br />
19.4 16.6 7.9 8.8 9.8 10.7 11.6 6.2<br />
21.7 17.7 5.9 6.8 7.7 8.7 9.6 6.4<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(MULTIPLY OR ADD AS INDICATED)<br />
AIRFLOW 2675 3439<br />
TOTAL CAP. X0.98 X1.01<br />
SENS. CAP. X0.95 X1.05<br />
COMPR. KW X0.99 X1.01<br />
VALUES AT ARI RATING CONDITIONS<br />
GROSS CAPACITY = 18.49 KW<br />
AIRFLOW = 3057 CMH<br />
COMPRESSOR POWER = 5326 WATTS<br />
I.D. FAN POWER = 750 WATTS<br />
O.D. FAN POWER = 395 WATTS<br />
E.E.R. = 9.20 BTUH/WATT<br />
NOTE:RATED WITH 7.62 METERS OF 28.6 MM SUCT.<br />
AND 9.5 MM LIQUID LINES<br />
* DRY COIL CONDITION (TOTAL CAPACITY =<br />
SENSIBLE CAPACITY)<br />
TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE<br />
VALID ONLY FOR WET COIL<br />
ALL TEMPERATURES IN DEGREES C.<br />
TWE5-PRC001-EN-10-15-99 15
Performance<br />
<strong>Data</strong> Heating<br />
English Units<br />
TWJ020CA WITH TWE030CA4 AT 700 CFM<br />
O.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT<br />
TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.<br />
F. 60 70 75 80 60 70 75 80<br />
-18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00<br />
-13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00<br />
-8 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00<br />
-3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00<br />
2 6.79 6.60 6.50 6.41 1.47 1.54 1.58 1.61<br />
7 8.13 7.90 7.78 7.67 1.50 1.57 1.61 1.64<br />
12 9.48 9.20 9.06 8.92 1.52 1.60 1.63 1.67<br />
17 10.8 10.5 10.3 10.2 1.55 1.63 1.66 1.70<br />
22 11.2 10.9 10.7 10.5 1.56 1.64 1.68 1.71<br />
27 11.6 11.2 11.0 10.9 1.57 1.65 1.69 1.73<br />
32 11.9 11.6 11.4 11.2 1.58 1.66 1.70 1.74<br />
37 12.3 11.9 11.8 11.6 1.60 1.68 1.71 1.75<br />
42 12.7 12.3 12.1 11.9 1.61 1.69 1.73 1.77<br />
47 18.9 18.3 18.0 17.7 1.71 1.79 1.84 1.88<br />
52 20.2 19.6 19.3 19.0 1.73 1.82 1.87 1.91<br />
57 21.6 20.9 20.6 20.2 1.76 1.85 1.90 1.94<br />
62 22.9 22.2 21.8 21.5 1.79 1.88 1.92 1.97<br />
67 24.3 23.5 23.1 22.7 1.81 1.91 1.95 2.00<br />
72 25.6 24.8 24.4 24.0 1.84 1.93 1.98 2.03<br />
TWJ024CA WITH TWE030CA4 AT 900 CFM<br />
O.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT<br />
TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.<br />
F. 60 70 75 80 60 70 75 80<br />
-18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00<br />
-13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00<br />
-8 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00<br />
-3 8.10 7.93 7.85 7.77 1.86 1.94 1.98 2.03<br />
2 9.91 9.70 9.60 9.49 1.92 2.01 2.06 2.10<br />
7 11.7 11.5 11.3 11.2 1.99 2.08 2.13 2.17<br />
12 13.5 13.2 13.1 12.9 2.06 2.15 2.20 2.25<br />
17 15.3 15.0 14.8 14.7 2.12 2.22 2.27 2.32<br />
22 16.2 15.9 15.7 15.5 2.18 2.28 2.33 2.38<br />
27 17.1 16.7 16.5 16.3 2.23 2.34 2.39 2.44<br />
32 18.0 17.6 17.4 17.2 2.29 2.40 2.45 2.51<br />
37 18.9 18.4 18.2 18.0 2.34 2.45 2.51 2.57<br />
42 19.8 19.3 19.1 18.9 2.39 2.51 2.57 2.63<br />
47 26.2 25.6 25.3 25.0 2.52 2.65 2.71 2.77<br />
52 28.0 27.4 27.0 26.7 2.59 2.72 2.78 2.85<br />
57 29.8 29.1 28.8 28.4 2.66 2.79 2.86 2.92<br />
62 31.6 30.9 30.5 30.2 2.72 2.86 2.93 3.00<br />
67 33.5 32.7 32.3 31.9 2.79 2.93 3.00 3.07<br />
72 35.3 34.4 34.0 33.6 2.86 3.00 3.07 3.14<br />
TWJ030CA WITH TWE030CA4 AT 1000 CFM<br />
O.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT<br />
TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.<br />
F. 60 70 75 80 60 70 75 80<br />
-18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00<br />
-13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00<br />
-8 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00<br />
-3 9.79 9.60 9.51 9.41 2.27 2.38 2.44 2.49<br />
2 11.8 11.6 11.5 11.4 2.36 2.47 2.53 2.59<br />
7 13.9 13.6 13.5 13.3 2.44 2.56 2.62 2.69<br />
12 15.9 15.6 15.4 15.3 2.53 2.65 2.72 2.78<br />
17 18.0 17.6 17.4 17.2 2.61 2.74 2.81 2.88<br />
22 18.9 18.5 18.3 18.2 2.69 2.83 2.89 2.96<br />
27 19.9 19.5 19.3 19.1 2.77 2.91 2.98 3.05<br />
32 20.9 20.4 20.2 20.0 2.85 2.99 3.06 3.14<br />
37 21.8 21.4 21.2 20.9 2.92 3.07 3.15 3.22<br />
42 22.8 22.3 22.1 21.8 3.00 3.16 3.23 3.31<br />
47 30.2 29.6 29.3 29.0 3.12 3.28 3.37 3.45<br />
52 32.3 31.6 31.3 30.9 3.21 3.37 3.46 3.54<br />
57 34.3 33.6 33.2 32.9 3.29 3.46 3.55 3.64<br />
62 36.4 35.6 35.2 34.8 3.38 3.55 3.64 3.73<br />
67 38.4 37.6 37.2 36.8 3.46 3.64 3.74 3.83<br />
72 40.5 39.6 39.2 38.7 3.55 3.73 3.83 3.92<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(VALUE AT 700 CFM TIMES CORR. FACTOR<br />
= VALUE AT NEW AIRFLOW)<br />
AIRFLOW 625 800<br />
HEATING CAP. X0.99 X1.02<br />
COMPR. KW X1.01 X0.98<br />
VALUES AT ARI RATING CONDITIONS OF:<br />
70&47/43 (HIGH TEMP. POINT)<br />
70&17/15 (LOW TEMP. POINT)<br />
AIRFLOW = 700 CFM<br />
HEATING CAP. (HIGH TEMP.) = 18300 BTUH<br />
HEATING CAP. (LOW TEMP.) = 10500 BTUH<br />
COMPR. POWER (HIGH TEMP.) = 1354 WATTS<br />
COMPR. POWER (LOW TEMP.) = 1185 WATTS<br />
COEFF. OF PERF. (HIGH TEMP.) = 3.00<br />
COEFF. OF PERF. (LOW TEMP.) = 1.88<br />
OUTDOOR FAN POWER = 130 WATTS<br />
INDOOR FAN POWER = 310 WATTS<br />
NOTE: RATED WITH 25 FEET OF 3/4<br />
SUCTION AND 5/16 LIQUID LINE<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(VALUE AT 900 CFM TIMES CORR. FACTOR<br />
= VALUE AT NEW AIRFLOW)<br />
AIRFLOW 800 1025<br />
HEATING CAP. X0.99 X1.02<br />
COMPR. KW X1.02 X0.98<br />
VALUES AT ARI RATING CONDITIONS OF:<br />
70&47/43 (HIGH TEMP. POINT)<br />
70&17/15 (LOW TEMP. POINT)<br />
AIRFLOW = 900 CFM<br />
HEATING CAP. (HIGH TEMP.) = 25600 BTUH<br />
HEATING CAP. (LOW TEMP.) = 15000 BTUH<br />
COMPR. POWER (HIGH TEMP.) = 2038 WATTS<br />
COMPR. POWER (LOW TEMP.) = 1614 WATTS<br />
COEFF. OF PERF. (HIGH TEMP.) = 2.84<br />
COEFF. OF PERF. (LOW TEMP.) = 1.96<br />
OUTDOOR FAN POWER = 180 WATTS<br />
INDOOR FAN POWER = 430 WATTS<br />
NOTE: RATED WITH 25 FEET OF 3/4<br />
SUCTION AND 5/16 LIQUID LINE<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(VALUE AT 1000 CFM TIMES CORR. FACTOR<br />
= VALUE AT NEW AIRFLOW)<br />
AIRFLOW 875 1125<br />
HEATING CAP. X0.99 X1.01<br />
COMPR. KW X1.02 X0.98<br />
VALUES AT ARI RATING CONDITIONS OF:<br />
70&47/43 (HIGH TEMP. POINT)<br />
70&17/15 (LOW TEMP. POINT)<br />
AIRFLOW = 1000 CFM<br />
HEATING CAP. (HIGH TEMP.) = 29600 BTUH<br />
HEATING CAP. (LOW TEMP.) = 17600 BTUH<br />
COMPR. POWER (HIGH TEMP.) = 2649 WATTS<br />
COMPR. POWER (LOW TEMP.) = 2109 WATTS<br />
COEFF. OF PERF. (HIGH TEMP.) = 2.64<br />
COEFF. OF PERF. (LOW TEMP.) = 1.86<br />
OUTDOOR FAN POWER = 195 WATTS<br />
INDOOR FAN POWER = 440 WATTS<br />
NOTE: RATED WITH 25 FEET OF 7/8<br />
SUCTION AND 3/8 LIQUID LINE<br />
16 TWE5-PRC001-EN-10-15-99
Performance<br />
<strong>Data</strong> Heating<br />
Metric Units<br />
TWJ020CA WITH TWE030CA4 AT 1189 CMH<br />
O.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT<br />
TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.<br />
C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7<br />
-27.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0<br />
-25.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0<br />
-22.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0<br />
-19.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0<br />
-16.7 2.0 1.9 1.9 1.9 1.5 1.5 1.6 1.6<br />
-13.9 2.4 2.3 2.3 2.2 1.5 1.6 1.6 1.6<br />
-11.1 2.8 2.7 2.7 2.6 1.5 1.6 1.6 1.7<br />
-8.3 3.2 3.1 3.0 3.0 1.5 1.6 1.7 1.7<br />
-5.6 3.3 3.2 3.1 3.1 1.6 1.6 1.7 1.7<br />
-2.8 3.4 3.3 3.2 3.2 1.6 1.6 1.7 1.7<br />
0.0 3.5 3.4 3.3 3.3 1.6 1.7 1.7 1.7<br />
2.8 3.6 3.5 3.5 3.4 1.6 1.7 1.7 1.8<br />
5.6 3.7 3.6 3.5 3.5 1.6 1.7 1.7 1.8<br />
8.3 5.5 5.4 5.3 5.2 1.7 1.8 1.8 1.9<br />
11.1 5.9 5.7 5.7 5.6 1.7 1.8 1.9 1.9<br />
13.9 6.3 6.1 6.0 5.9 1.8 1.9 1.9 1.9<br />
16.7 6.7 6.5 6.4 6.3 1.8 1.9 1.9 2.0<br />
19.4 7.1 6.9 6.8 6.7 1.8 1.9 2.0 2.0<br />
22.2 7.5 7.3 7.1 7.0 1.8 1.9 2.0 2.0<br />
TWJ024CA WITH TWE030CA4 AT 1528 CMH<br />
O.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT<br />
TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.<br />
C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7<br />
-27.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0<br />
-25.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0<br />
-22.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0<br />
-19.4 2.4 2.3 2.3 2.3 1.9 1.9 2.0 2.0<br />
-16.7 2.9 2.8 2.8 2.8 1.9 2.0 2.1 2.1<br />
-13.9 3.4 3.4 3.3 3.3 2.0 2.1 2.1 2.2<br />
-11.1 4.0 3.9 3.8 3.8 2.1 2.2 2.2 2.3<br />
-8.3 4.5 4.4 4.3 4.3 2.1 2.2 2.3 2.3<br />
-5.6 4.7 4.7 4.6 4.5 2.2 2.3 2.3 2.4<br />
-2.8 5.0 4.9 4.8 4.8 2.2 2.3 2.4 2.4<br />
0.0 5.3 5.2 5.1 5.0 2.3 2.4 2.5 2.5<br />
2.8 5.5 5.4 5.3 5.3 2.3 2.5 2.5 2.6<br />
5.6 5.8 5.7 5.6 5.5 2.4 2.5 2.6 2.6<br />
8.3 7.7 7.5 7.4 7.3 2.5 2.7 2.7 2.8<br />
11.1 8.2 8.0 7.9 7.8 2.6 2.7 2.8 2.8<br />
13.9 8.7 8.5 8.4 8.3 2.7 2.8 2.9 2.9<br />
16.7 9.3 9.1 8.9 8.8 2.7 2.9 2.9 3.0<br />
19.4 9.8 9.6 9.5 9.3 2.8 2.9 3.0 3.1<br />
22.2 10.3 10.1 10.0 9.8 2.9 3.0 3.1 3.1<br />
TWJ030CA WITH TWE030CA4 AT 1698 CMH<br />
O.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT<br />
TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.<br />
C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7<br />
-27.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0<br />
-25.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0<br />
-22.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0<br />
-19.4 2.9 2.8 2.8 2.8 2.3 2.4 2.4 2.5<br />
-16.7 3.5 3.4 3.4 3.3 2.4 2.5 2.5 2.6<br />
-13.9 4.1 4.0 4.0 3.9 2.4 2.6 2.6 2.7<br />
-11.1 4.7 4.6 4.5 4.5 2.5 2.7 2.7 2.8<br />
-8.3 5.3 5.2 5.1 5.0 2.6 2.7 2.8 2.9<br />
-5.6 5.5 5.4 5.4 5.3 2.7 2.8 2.9 3.0<br />
-2.8 5.8 5.7 5.7 5.6 2.8 2.9 3.0 3.0<br />
0.0 6.1 6.0 5.9 5.9 2.8 3.0 3.1 3.1<br />
2.8 6.4 6.3 6.2 6.1 2.9 3.1 3.2 3.2<br />
5.6 6.7 6.5 6.5 6.4 3.0 3.2 3.2 3.3<br />
8.3 8.8 8.7 8.6 8.5 3.1 3.3 3.4 3.5<br />
11.1 9.5 9.3 9.2 9.1 3.2 3.4 3.5 3.5<br />
13.9 10.0 9.8 9.7 9.6 3.3 3.5 3.5 3.6<br />
16.7 10.7 10.4 10.3 10.2 3.4 3.5 3.6 3.7<br />
19.4 11.3 11.0 10.9 10.8 3.5 3.6 3.7 3.8<br />
22.2 11.9 11.6 11.5 11.3 3.5 3.7 3.8 3.9<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(VALUE AT 1189 CMH TIMES CORR. FACTOR<br />
= VALUE AT NEW AIRFLOW)<br />
AIRFLOW 1061 1358<br />
HEATING CAP. X0.99 X1.02<br />
COMPR. KW X1.01 X0.98<br />
VALUES AT ARI RATING CONDITIONS OF:<br />
21.1& 8.3/6.1(HIGH TEMP. POINT)<br />
21.1&-8.3/-9.4(LOW TEMP. POINT)<br />
AIRFLOW = 1189 CMH<br />
HEATING CAP. (HIGH TEMP.) = 5.36 KW<br />
HEATING CAP. (LOW TEMP.) = 3.08 KW<br />
COMPR. POWER (HIGH TEMP.) = 1354 WATTS<br />
COMPR. POWER (LOW TEMP.) = 1185 WATTS<br />
COEFF. OF PERF. (HIGH TEMP.) = 3.00<br />
COEFF. OF PERF. (LOW TEMP.) = 1.88<br />
OUTDOOR FAN POWER = 130 WATTS<br />
INDOOR FAN POWER = 310 WATTS<br />
NOTE: RATED WITH 7.62 METERS OF 19 MM<br />
SUCTION AND 8 MM LIQUID LINE<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(VALUE AT 1528 CMH TIMES CORR. FACTOR<br />
= VALUE AT NEW AIRFLOW)<br />
AIRFLOW 1358 1741<br />
HEATING CAP. X0.99 X1.02<br />
COMPR. KW X1.02 X0.98<br />
VALUES AT ARI RATING CONDITIONS OF:<br />
21.1& 8.3/6.1(HIGH TEMP. POINT)<br />
21.1&-8.3/-9.4(LOW TEMP. POINT)<br />
AIRFLOW = 1528 CMH<br />
HEATING CAP. (HIGH TEMP.) = 7.50 KW<br />
HEATING CAP. (LOW TEMP.) = 4.39 KW<br />
COMPR. POWER (HIGH TEMP.) = 2038 WATTS<br />
COMPR. POWER (LOW TEMP.) = 1614 WATTS<br />
COEFF. OF PERF. (HIGH TEMP.) = 2.84<br />
COEFF. OF PERF. (LOW TEMP.) = 1.96<br />
OUTDOOR FAN POWER = 180 WATTS<br />
INDOOR FAN POWER = 430 WATTS<br />
NOTE: RATED WITH 7.62 METERS OF 19 MM<br />
SUCTION AND 8 MM LIQUID LINE<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(VALUE AT 1698 CMH TIMES CORR. FACTOR<br />
= VALUE AT NEW AIRFLOW)<br />
AIRFLOW 1486 1910<br />
HEATING CAP. X0.99 X1.01<br />
COMPR. KW X1.02 X0.98<br />
VALUES AT ARI RATING CONDITIONS OF:<br />
21.1& 8.3/6.1(HIGH TEMP. POINT)<br />
21.1&-8.3/-9.4(LOW TEMP. POINT)<br />
AIRFLOW = 1698 CMH<br />
HEATING CAP. (HIGH TEMP.) = 8.67 KW<br />
HEATING CAP. (LOW TEMP.) = 5.16 KW<br />
COMPR. POWER (HIGH TEMP.) = 2649 WATTS<br />
COMPR. POWER (LOW TEMP.) = 2109 WATTS<br />
COEFF. OF PERF. (HIGH TEMP.) = 2.64<br />
COEFF. OF PERF. (LOW TEMP.) = 1.86<br />
OUTDOOR FAN POWER = 195 WATTS<br />
INDOOR FAN POWER = 440 WATTS<br />
NOTE: RATED WITH 7.62 METERS OF 22 MM<br />
SUCTION AND 9.5 MM LIQUID LINE<br />
TWE5-PRC001-EN-10-15-99 17
Performance<br />
<strong>Data</strong> Heating<br />
English Units<br />
TWJ030CA WITH TWE040CA4-B AT 1100 CFM<br />
O.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT<br />
TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.<br />
F. 60 70 75 80 60 70 75 80<br />
-18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00<br />
-13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00<br />
-8 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00<br />
-3 9.46 9.27 9.17 9.08 2.12 2.24 2.30 2.36<br />
2 11.6 11.3 11.2 11.1 2.19 2.31 2.37 2.44<br />
7 13.6 13.4 13.2 13.1 2.26 2.39 2.45 2.52<br />
12 15.7 15.4 15.2 15.1 2.33 2.47 2.53 2.60<br />
17 17.8 17.5 17.3 17.1 2.40 2.54 2.61 2.68<br />
22 18.9 18.5 18.3 18.1 2.47 2.61 2.68 2.76<br />
27 19.9 19.5 19.3 19.1 2.54 2.69 2.76 2.83<br />
32 21.0 20.5 20.3 20.1 2.61 2.76 2.83 2.91<br />
37 22.0 21.6 21.3 21.1 2.67 2.83 2.91 2.99<br />
42 23.1 22.6 22.3 22.1 2.74 2.90 2.98 3.06<br />
47 30.4 29.7 29.4 29.1 2.83 3.00 3.08 3.17<br />
52 32.5 31.8 31.4 31.1 2.91 3.08 3.16 3.25<br />
57 34.6 33.8 33.5 33.1 2.98 3.15 3.24 3.33<br />
62 36.7 35.9 35.5 35.1 3.05 3.23 3.32 3.41<br />
67 38.8 37.9 37.5 37.1 3.12 3.31 3.40 3.49<br />
72 40.9 40.0 39.5 39.1 3.19 3.38 3.48 3.57<br />
TWJ036CA WITH TWE030CA4 AT 1100 CFM<br />
O.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT<br />
TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.<br />
F. 60 70 75 80 60 70 75 80<br />
-18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00<br />
-13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00<br />
-8 8.32 8.18 8.11 8.04 2.00 2.09 2.13 2.18<br />
-3 10.8 10.6 10.5 10.4 2.13 2.22 2.27 2.32<br />
2 13.3 13.0 12.9 12.8 2.25 2.36 2.41 2.46<br />
7 15.8 15.5 15.3 15.2 2.38 2.49 2.54 2.60<br />
12 18.3 17.9 17.7 17.5 2.50 2.62 2.68 2.74<br />
17 20.7 20.3 20.1 19.9 2.63 2.75 2.82 2.88<br />
22 21.9 21.5 21.3 21.1 2.71 2.85 2.91 2.98<br />
27 23.1 22.7 22.4 22.2 2.80 2.94 3.01 3.08<br />
32 24.3 23.8 23.6 23.3 2.89 3.03 3.10 3.18<br />
37 25.5 25.0 24.7 24.5 2.98 3.13 3.20 3.27<br />
42 26.7 26.2 25.9 25.6 3.06 3.22 3.30 3.37<br />
47 35.6 34.9 34.5 34.2 3.38 3.55 3.64 3.72<br />
52 38.1 37.3 36.9 36.6 3.50 3.68 3.77 3.87<br />
57 40.6 39.8 39.3 38.9 3.63 3.82 3.91 4.01<br />
62 43.1 42.2 41.8 41.3 3.75 3.95 4.05 4.15<br />
67 45.6 44.6 44.2 43.7 3.88 4.08 4.19 4.29<br />
72 48.0 47.1 46.6 46.1 4.00 4.22 4.32 4.43<br />
TWJ036CA WITH TWE040CA4-B AT 1400 CFM<br />
O.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT<br />
TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.<br />
F. 60 70 75 80 60 70 75 80<br />
-18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00<br />
-13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00<br />
-8 7.73 7.59 7.52 7.45 1.84 1.93 1.98 2.03<br />
-3 10.3 10.1 10.0 9.94 1.94 2.05 2.10 2.15<br />
2 12.9 12.7 12.5 12.4 2.05 2.16 2.22 2.27<br />
7 15.5 15.2 15.1 14.9 2.16 2.27 2.33 2.39<br />
12 18.1 17.7 17.6 17.4 2.26 2.39 2.45 2.52<br />
17 20.7 20.3 20.1 19.9 2.37 2.50 2.57 2.64<br />
22 22.0 21.6 21.3 21.1 2.44 2.58 2.65 2.72<br />
27 23.3 22.8 22.6 22.4 2.52 2.66 2.73 2.81<br />
32 24.6 24.1 23.9 23.6 2.59 2.74 2.82 2.89<br />
37 25.9 25.4 25.1 24.9 2.67 2.82 2.90 2.97<br />
42 27.2 26.7 26.4 26.1 2.74 2.90 2.98 3.06<br />
47 36.3 35.5 35.1 34.8 3.00 3.18 3.27 3.36<br />
52 38.9 38.1 37.7 37.2 3.11 3.29 3.39 3.48<br />
57 41.5 40.6 40.2 39.7 3.22 3.41 3.50 3.60<br />
62 44.1 43.1 42.7 42.2 3.32 3.52 3.62 3.72<br />
67 46.6 45.7 45.2 44.7 3.43 3.63 3.74 3.84<br />
72 49.2 48.2 47.7 47.2 3.54 3.75 3.85 3.96<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(VALUE AT 1100 CFM TIMES CORR. FACTOR<br />
= VALUE AT NEW AIRFLOW)<br />
AIRFLOW 975 1275<br />
HEATING CAP. X0.99 X1.01<br />
COMPR. KW X1.02 X0.98<br />
VALUES AT ARI RATING CONDITIONS OF:<br />
70&47/43 (HIGH TEMP. POINT)<br />
70&17/15 (LOW TEMP. POINT)<br />
AIRFLOW = 1125 CFM<br />
HEATING CAP. (HIGH TEMP.) = 29800 BTUH<br />
HEATING CAP. (LOW TEMP.) = 17500 BTUH<br />
COMPR. POWER (HIGH TEMP.) = 2504 WATTS<br />
COMPR. POWER (LOW TEMP.) = 2047 WATTS<br />
COEFF. OF PERF. (HIGH TEMP.) = 2.92<br />
COEFF. OF PERF. (LOW TEMP.) = 2.00<br />
OUTDOOR FAN POWER = 195 WATTS<br />
INDOOR FAN POWER = 300 WATTS<br />
NOTE: RATED WITH 25 FEET OF 7/8<br />
SUCTION AND 3/8 LIQUID LINE<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(VALUE AT 1100 CFM TIMES CORR. FACTOR<br />
= VALUE AT NEW AIRFLOW)<br />
AIRFLOW 975 1275<br />
HEATING CAP. X0.99 X1.02<br />
COMPR. KW X1.02 X0.97<br />
VALUES AT ARI RATING CONDITIONS OF:<br />
70&47/43 (HIGH TEMP. POINT)<br />
70&17/15 (LOW TEMP. POINT)<br />
AIRFLOW = 1125 CFM<br />
HEATING CAP. (HIGH TEMP.) = 35000 BTUH<br />
HEATING CAP. (LOW TEMP.) = 20400 BTUH<br />
COMPR. POWER (HIGH TEMP.) = 2776 WATTS<br />
COMPR. POWER (LOW TEMP.) = 1982 WATTS<br />
COEFF. OF PERF. (HIGH TEMP.) = 2.88<br />
COEFF. OF PERF. (LOW TEMP.) = 2.16<br />
OUTDOOR FAN POWER = 235 WATTS<br />
INDOOR FAN POWER = 540 WATTS<br />
NOTE: RATED WITH 25 FEET OF 7/8<br />
SUCTION AND 3/8 LIQUID LINE<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(VALUE AT 1400 CFM TIMES CORR. FACTOR<br />
= VALUE AT NEW AIRFLOW)<br />
AIRFLOW 1175 1525<br />
HEATING CAP. X0.98 X1.01<br />
COMPR. KW X1.03 X0.99<br />
VALUES AT ARI RATING CONDITIONS OF:<br />
70&47/43 (HIGH TEMP. POINT)<br />
70&17/15 (LOW TEMP. POINT)<br />
AIRFLOW = 1350 CFM<br />
HEATING CAP. (HIGH TEMP.) = 35400 BTUH<br />
HEATING CAP. (LOW TEMP.) = 20200 BTUH<br />
COMPR. POWER (HIGH TEMP.) = 2590 WATTS<br />
COMPR. POWER (LOW TEMP.) = 1906 WATTS<br />
COEFF. OF PERF. (HIGH TEMP.) = 3.24<br />
COEFF. OF PERF. (LOW TEMP.) = 2.36<br />
OUTDOOR FAN POWER = 235 WATTS<br />
INDOOR FAN POWER = 360 WATTS<br />
NOTE: RATED WITH 25 FEET OF 7/8<br />
SUCTION AND 3/8 LIQUID LINE<br />
18 TWE5-PRC001-EN-10-15-99
Performance<br />
<strong>Data</strong> Heating<br />
Metric Units<br />
TWJ030CA WITH TWE040CA4-B AT 1868 CMH<br />
O.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT<br />
TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.<br />
C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7<br />
-27.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0<br />
-25.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0<br />
-22.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0<br />
-19.4 2.8 2.7 2.7 2.7 2.1 2.2 2.3 2.4<br />
-16.7 3.4 3.3 3.3 3.3 2.2 2.3 2.4 2.4<br />
-13.9 4.0 3.9 3.9 3.8 2.3 2.4 2.5 2.5<br />
-11.1 4.6 4.5 4.5 4.4 2.3 2.5 2.5 2.6<br />
-8.3 5.2 5.1 5.1 5.0 2.4 2.5 2.6 2.7<br />
-5.6 5.5 5.4 5.4 5.3 2.5 2.6 2.7 2.8<br />
-2.8 5.8 5.7 5.7 5.6 2.5 2.7 2.8 2.8<br />
0.0 6.2 6.0 5.9 5.9 2.6 2.8 2.8 2.9<br />
2.8 6.4 6.3 6.2 6.2 2.7 2.8 2.9 3.0<br />
5.6 6.8 6.6 6.5 6.5 2.7 2.9 3.0 3.1<br />
8.3 8.9 8.7 8.6 8.5 2.8 3.0 3.1 3.2<br />
11.1 9.5 9.3 9.2 9.1 2.9 3.1 3.2 3.3<br />
13.9 10.1 9.9 9.8 9.7 3.0 3.2 3.2 3.3<br />
16.7 10.8 10.5 10.4 10.3 3.0 3.2 3.3 3.4<br />
19.4 11.4 11.1 11.0 10.9 3.1 3.3 3.4 3.5<br />
22.2 12.0 11.7 11.6 11.5 3.2 3.4 3.5 3.6<br />
TWJ036CA WITH TWE030CA4 AT 1868 CMH<br />
O.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT<br />
TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.<br />
C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7<br />
-27.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0<br />
-25.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0<br />
-22.2 2.4 2.4 2.4 2.4 2.0 2.1 2.1 2.2<br />
-19.4 3.2 3.1 3.1 3.0 2.1 2.2 2.3 2.3<br />
-16.7 3.9 3.8 3.8 3.8 2.3 2.4 2.4 2.5<br />
-13.9 4.6 4.5 4.5 4.5 2.4 2.5 2.5 2.6<br />
-11.1 5.4 5.2 5.2 5.1 2.5 2.6 2.7 2.7<br />
-8.3 6.1 5.9 5.9 5.8 2.6 2.8 2.8 2.9<br />
-5.6 6.4 6.3 6.2 6.2 2.7 2.8 2.9 3.0<br />
-2.8 6.8 6.7 6.6 6.5 2.8 2.9 3.0 3.1<br />
0.0 7.1 7.0 6.9 6.8 2.9 3.0 3.1 3.2<br />
2.8 7.5 7.3 7.2 7.2 3.0 3.1 3.2 3.3<br />
5.6 7.8 7.7 7.6 7.5 3.1 3.2 3.3 3.4<br />
8.3 10.4 10.2 10.1 10.0 3.4 3.5 3.6 3.7<br />
11.1 11.2 10.9 10.8 10.7 3.5 3.7 3.8 3.9<br />
13.9 11.9 11.7 11.5 11.4 3.6 3.8 3.9 4.0<br />
16.7 12.6 12.4 12.2 12.1 3.8 4.0 4.1 4.2<br />
19.4 13.4 13.1 13.0 12.8 3.9 4.1 4.2 4.3<br />
22.2 14.1 13.8 13.7 13.5 4.0 4.2 4.3 4.4<br />
TWJ036CA WITH TWE040CA4-B AT 2378 CMH<br />
O.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT<br />
TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.<br />
C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7<br />
-27.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0<br />
-25.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0<br />
-22.2 2.3 2.2 2.2 2.2 1.8 1.9 2.0 2.0<br />
-19.4 3.0 3.0 2.9 2.9 1.9 2.0 2.1 2.2<br />
-16.7 3.8 3.7 3.7 3.6 2.0 2.2 2.2 2.3<br />
-13.9 4.5 4.5 4.4 4.4 2.2 2.3 2.3 2.4<br />
-11.1 5.3 5.2 5.2 5.1 2.3 2.4 2.5 2.5<br />
-8.3 6.1 5.9 5.9 5.8 2.4 2.5 2.6 2.6<br />
-5.6 6.4 6.3 6.2 6.2 2.4 2.6 2.7 2.7<br />
-2.8 6.8 6.7 6.6 6.6 2.5 2.7 2.7 2.8<br />
0.0 7.2 7.1 7.0 6.9 2.6 2.7 2.8 2.9<br />
2.8 7.6 7.4 7.4 7.3 2.7 2.8 2.9 3.0<br />
5.6 8.0 7.8 7.7 7.6 2.7 2.9 3.0 3.1<br />
8.3 10.6 10.4 10.3 10.2 3.0 3.2 3.3 3.4<br />
11.1 11.4 11.2 11.0 10.9 3.1 3.3 3.4 3.5<br />
13.9 12.2 11.9 11.8 11.6 3.2 3.4 3.5 3.6<br />
16.7 12.9 12.6 12.5 12.4 3.3 3.5 3.6 3.7<br />
19.4 13.7 13.4 13.2 13.1 3.4 3.6 3.7 3.8<br />
22.2 14.4 14.1 14.0 13.8 3.5 3.8 3.8 4.0<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(VALUE AT 1868 CMH TIMES CORR. FACTOR<br />
= VALUE AT NEW AIRFLOW)<br />
AIRFLOW 1656 2165<br />
HEATING CAP. X0.99 X1.01<br />
COMPR. KW X1.02 X0.98<br />
VALUES AT ARI RATING CONDITIONS OF:<br />
21.1& 8.3/6.1(HIGH TEMP. POINT)<br />
21.1&-8.3/-9.4(LOW TEMP. POINT)<br />
AIRFLOW = 1910 CMH<br />
HEATING CAP. (HIGH TEMP.) = 8.73 KW<br />
HEATING CAP. (LOW TEMP.) = 5.13 KW<br />
COMPR. POWER (HIGH TEMP.) = 2504 WATTS<br />
COMPR. POWER (LOW TEMP.) = 2047 WATTS<br />
COEFF. OF PERF. (HIGH TEMP.) = 2.92<br />
COEFF. OF PERF. (LOW TEMP.) = 2.00<br />
OUTDOOR FAN POWER = 195 WATTS<br />
INDOOR FAN POWER = 300 WATTS<br />
NOTE: RATED WITH 7.62 METERS OF 22 MM<br />
SUCTION AND 9.5 MM LIQUID LINE<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(VALUE AT 1868 CMH TIMES CORR. FACTOR<br />
= VALUE AT NEW AIRFLOW)<br />
AIRFLOW 1656 2165<br />
HEATING CAP. X0.99 X1.02<br />
COMPR. KW X1.02 X0.97<br />
VALUES AT ARI RATING CONDITIONS OF:<br />
21.1& 8.3/6.1(HIGH TEMP. POINT)<br />
21.1&-8.3/-9.4(LOW TEMP. POINT)<br />
AIRFLOW = 1910 CMH<br />
HEATING CAP. (HIGH TEMP.) = 10.25 KW<br />
HEATING CAP. (LOW TEMP.) = 5.98 KW<br />
COMPR. POWER (HIGH TEMP.) = 2776 WATTS<br />
COMPR. POWER (LOW TEMP.) = 1982 WATTS<br />
COEFF. OF PERF. (HIGH TEMP.) = 2.88<br />
COEFF. OF PERF. (LOW TEMP.) = 2.16<br />
OUTDOOR FAN POWER = 235 WATTS<br />
INDOOR FAN POWER = 540 WATTS<br />
NOTE: RATED WITH 7.62 METERS OF 22 MM<br />
SUCTION AND 9.5 MM LIQUID LINE<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(VALUE AT 2378 CMH TIMES CORR. FACTOR<br />
= VALUE AT NEW AIRFLOW)<br />
AIRFLOW 1995 2590<br />
HEATING CAP. X0.98 X1.01<br />
COMPR. KW X1.03 X0.99<br />
VALUES AT ARI RATING CONDITIONS OF:<br />
21.1& 8.3/6.1(HIGH TEMP. POINT)<br />
21.1&-8.3/-9.4(LOW TEMP. POINT)<br />
AIRFLOW = 2293 CMH<br />
HEATING CAP. (HIGH TEMP.) = 10.37 KW<br />
HEATING CAP. (LOW TEMP.) = 5.92 KW<br />
COMPR. POWER (HIGH TEMP.) = 2590 WATTS<br />
COMPR. POWER (LOW TEMP.) = 1906 WATTS<br />
COEFF. OF PERF. (HIGH TEMP.) = 3.24<br />
COEFF. OF PERF. (LOW TEMP.) = 2.36<br />
OUTDOOR FAN POWER = 235 WATTS<br />
INDOOR FAN POWER = 360 WATTS<br />
NOTE: RATED WITH 7.62 METERS OF 22 MM<br />
SUCTION AND 9.5 MM LIQUID LINE<br />
TWE5-PRC001-EN-10-15-99 19
Performance<br />
<strong>Data</strong> Heating<br />
English Units<br />
TWA030CD WITH TWE030CA4 AT 1000 CFM<br />
O.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT<br />
TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.<br />
F. 60 70 75 80 60 70 75 80<br />
-18 7.48 7.28 7.18 7.08 1.69 1.76 1.79 1.83<br />
-13 8.81 8.57 8.45 8.33 1.78 1.85 1.89 1.92<br />
-8 10.1 9.86 9.72 9.59 1.86 1.94 1.98 2.02<br />
-3 11.4 11.1 11.0 10.8 1.95 2.03 2.08 2.12<br />
2 12.8 12.4 12.3 12.1 2.03 2.13 2.17 2.22<br />
7 14.1 13.7 13.5 13.4 2.12 2.22 2.27 2.31<br />
12 15.4 15.0 14.8 14.6 2.20 2.31 2.36 2.41<br />
17 16.7 16.3 16.1 15.9 2.29 2.40 2.45 2.51<br />
22 17.7 17.3 17.0 16.8 2.36 2.47 2.53 2.58<br />
27 18.7 18.2 18.0 17.7 2.42 2.54 2.60 2.66<br />
32 19.7 19.2 19.0 18.7 2.49 2.61 2.67 2.73<br />
37 20.7 20.2 19.9 19.6 2.55 2.68 2.74 2.80<br />
42 21.7 21.2 20.9 20.6 2.62 2.75 2.81 2.88<br />
47 28.8 28.0 27.6 27.2 2.73 2.87 2.93 3.00<br />
52 30.8 30.0 29.5 29.1 2.80 2.94 3.01 3.08<br />
57 32.8 31.9 31.5 31.0 2.88 3.02 3.09 3.17<br />
62 34.8 33.9 33.4 32.9 2.95 3.10 3.17 3.25<br />
67 36.8 35.8 35.3 34.8 3.02 3.18 3.25 3.33<br />
72 38.8 37.8 37.2 36.7 3.10 3.26 3.33 3.41<br />
TWA030CD WITH TWE040CA4-B AT 1100 CFM<br />
O.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT<br />
TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.<br />
F. 60 70 75 80 60 70 75 80<br />
-18 7.58 7.37 7.26 7.16 1.49 1.56 1.59 1.63<br />
-13 8.87 8.62 8.50 8.38 1.58 1.65 1.69 1.73<br />
-8 10.2 9.88 9.74 9.60 1.66 1.75 1.79 1.83<br />
-3 11.4 11.1 11.0 10.8 1.75 1.84 1.88 1.93<br />
2 12.7 12.4 12.2 12.0 1.84 1.93 1.98 2.03<br />
7 14.0 13.6 13.5 13.3 1.92 2.02 2.08 2.13<br />
12 15.3 14.9 14.7 14.5 2.01 2.12 2.17 2.23<br />
17 16.6 16.2 15.9 15.7 2.10 2.21 2.27 2.33<br />
22 17.7 17.2 16.9 16.7 2.15 2.27 2.33 2.39<br />
27 18.7 18.2 18.0 17.7 2.21 2.33 2.39 2.45<br />
32 19.8 19.2 19.0 18.7 2.27 2.39 2.46 2.52<br />
37 20.8 20.3 20.0 19.7 2.32 2.45 2.52 2.58<br />
42 21.9 21.3 21.0 20.7 2.38 2.51 2.58 2.65<br />
47 29.1 28.3 27.9 27.5 2.47 2.61 2.68 2.75<br />
52 31.2 30.4 29.9 29.5 2.53 2.68 2.75 2.82<br />
57 33.3 32.4 31.9 31.5 2.60 2.74 2.82 2.89<br />
62 35.4 34.4 33.9 33.4 2.66 2.81 2.89 2.96<br />
67 37.5 36.5 35.9 35.4 2.72 2.88 2.96 3.03<br />
72 39.6 38.5 37.9 37.4 2.78 2.94 3.02 3.10<br />
TWA040CD WITH TWE040CA4-B AT 1500 CFM<br />
O.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT<br />
TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.<br />
F. 60 70 75 80 60 70 75 80<br />
-18 9.52 9.31 9.20 9.10 1.88 1.97 2.02 2.06<br />
-13 11.1 10.9 10.8 10.6 1.96 2.06 2.11 2.16<br />
-8 12.8 12.5 12.3 12.2 2.04 2.14 2.20 2.25<br />
-3 14.4 14.1 13.9 13.7 2.12 2.23 2.29 2.35<br />
2 16.0 15.6 15.5 15.3 2.20 2.32 2.38 2.44<br />
7 17.6 17.2 17.0 16.9 2.28 2.41 2.47 2.54<br />
12 19.2 18.8 18.6 18.4 2.36 2.49 2.56 2.63<br />
17 20.8 20.4 20.2 20.0 2.44 2.58 2.65 2.72<br />
22 22.2 21.7 21.5 21.3 2.52 2.67 2.75 2.82<br />
27 23.6 23.1 22.8 22.6 2.61 2.76 2.84 2.92<br />
32 24.9 24.4 24.1 23.9 2.69 2.86 2.94 3.02<br />
37 26.3 25.7 25.4 25.2 2.78 2.95 3.03 3.11<br />
42 27.7 27.1 26.8 26.5 2.87 3.04 3.12 3.21<br />
47 36.6 35.8 35.4 35.0 3.09 3.28 3.37 3.46<br />
52 39.2 38.4 37.9 37.5 3.20 3.39 3.49 3.59<br />
57 41.9 40.9 40.5 40.0 3.30 3.51 3.61 3.71<br />
62 44.5 43.5 43.0 42.5 3.41 3.62 3.73 3.83<br />
67 47.1 46.1 45.5 45.0 3.52 3.74 3.85 3.96<br />
72 49.7 48.6 48.1 47.5 3.63 3.85 3.97 4.08<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(VALUE AT 1000 CFM TIMES CORR. FACTOR<br />
= VALUE AT NEW AIRFLOW)<br />
AIRFLOW 875 1125<br />
HEATING CAP. X0.98 X1.01<br />
COMPR. KW X1.02 X0.98<br />
VALUES AT ARI RATING CONDITIONS OF:<br />
70&47/43 (HIGH TEMP. POINT)<br />
70&17/15 (LOW TEMP. POINT)<br />
AIRFLOW = 1000 CFM<br />
HEATING CAP. (HIGH TEMP.) = 28000 BTUH<br />
HEATING CAP. (LOW TEMP.) = 16300 BTUH<br />
COMPR. POWER (HIGH TEMP.) = 2212 WATTS<br />
COMPR. POWER (LOW TEMP.) = 1745 WATTS<br />
COEFF. OF PERF. (HIGH TEMP.) = 2.86<br />
COEFF. OF PERF. (LOW TEMP.) = 1.98<br />
OUTDOOR FAN POWER = 214 WATTS<br />
INDOOR FAN POWER = 440 WATTS<br />
NOTE: RATED WITH 25 FEET OF 7/8<br />
SUCTION AND 3/8 LIQUID LINE<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(VALUE AT 1100 CFM TIMES CORR. FACTOR<br />
= VALUE AT NEW AIRFLOW)<br />
AIRFLOW 975 1275<br />
HEATING CAP. X0.99 X1.01<br />
COMPR. KW X1.02 X0.98<br />
VALUES AT ARI RATING CONDITIONS OF:<br />
70&47/43 (HIGH TEMP. POINT)<br />
70&17/15 (LOW TEMP. POINT)<br />
AIRFLOW = 1125 CFM<br />
HEATING CAP. (HIGH TEMP.) = 28400 BTUH<br />
HEATING CAP. (LOW TEMP.) = 16200 BTUH<br />
COMPR. POWER (HIGH TEMP.) = 2097 WATTS<br />
COMPR. POWER (LOW TEMP.) = 1698 WATTS<br />
COEFF. OF PERF. (HIGH TEMP.) = 3.16<br />
COEFF. OF PERF. (LOW TEMP.) = 2.14<br />
OUTDOOR FAN POWER = 214 WATTS<br />
INDOOR FAN POWER = 300 WATTS<br />
NOTE: RATED WITH 25 FEET OF 7/8<br />
SUCTION AND 3/8 LIQUID LINE<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(VALUE AT 1500 CFM TIMES CORR. FACTOR<br />
= VALUE AT NEW AIRFLOW)<br />
AIRFLOW 1325 1700<br />
HEATING CAP. X0.99 X1.01<br />
COMPR. KW X1.02 X0.98<br />
VALUES AT ARI RATING CONDITIONS OF:<br />
70&47/43 (HIGH TEMP. POINT)<br />
70&17/15 (LOW TEMP. POINT)<br />
AIRFLOW = 1500 CFM<br />
HEATING CAP. (HIGH TEMP.) = 35800 BTUH<br />
HEATING CAP. (LOW TEMP.) = 20400 BTUH<br />
COMPR. POWER (HIGH TEMP.) = 2612 WATTS<br />
COMPR. POWER (LOW TEMP.) = 1918 WATTS<br />
COEFF. OF PERF. (HIGH TEMP.) = 3.18<br />
COEFF. OF PERF. (LOW TEMP.) = 2.32<br />
OUTDOOR FAN POWER = 244 WATTS<br />
INDOOR FAN POWER = 420 WATTS<br />
NOTE: RATED WITH 25 FEET OF 1-1/8<br />
SUCTION AND 3/8 LIQUID LINE<br />
20 TWE5-PRC001-EN-10-15-99
Performance<br />
<strong>Data</strong> Heating<br />
Metric Units<br />
TWA030CD WITH TWE030CA4 AT 1698 CMH<br />
O.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT<br />
TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.<br />
C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7<br />
-27.8 2.2 2.1 2.1 2.1 1.7 1.8 1.8 1.8<br />
-25.0 2.6 2.5 2.5 2.4 1.8 1.9 1.9 1.9<br />
-22.2 3.0 2.9 2.8 2.8 1.9 1.9 2.0 2.0<br />
-19.4 3.3 3.3 3.2 3.2 2.0 2.0 2.1 2.1<br />
-16.7 3.8 3.6 3.6 3.5 2.0 2.1 2.2 2.2<br />
-13.9 4.1 4.0 4.0 3.9 2.1 2.2 2.3 2.3<br />
-11.1 4.5 4.4 4.3 4.3 2.2 2.3 2.4 2.4<br />
-8.3 4.9 4.8 4.7 4.7 2.3 2.4 2.5 2.5<br />
-5.6 5.2 5.1 5.0 4.9 2.4 2.5 2.5 2.6<br />
-2.8 5.5 5.3 5.3 5.2 2.4 2.5 2.6 2.7<br />
0.0 5.8 5.6 5.6 5.5 2.5 2.6 2.7 2.7<br />
2.8 6.1 5.9 5.8 5.7 2.5 2.7 2.7 2.8<br />
5.6 6.4 6.2 6.1 6.0 2.6 2.8 2.8 2.9<br />
8.3 8.4 8.2 8.1 8.0 2.7 2.9 2.9 3.0<br />
11.1 9.0 8.8 8.6 8.5 2.8 2.9 3.0 3.1<br />
13.9 9.6 9.3 9.2 9.1 2.9 3.0 3.1 3.2<br />
16.7 10.2 9.9 9.8 9.6 3.0 3.1 3.2 3.3<br />
19.4 10.8 10.5 10.3 10.2 3.0 3.2 3.3 3.3<br />
22.2 11.4 11.1 10.9 10.8 3.1 3.3 3.3 3.4<br />
TWA030CD WITH TWE040CA4-B AT 1868 CMH<br />
O.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT<br />
TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.<br />
C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7<br />
-27.8 2.2 2.2 2.1 2.1 1.5 1.6 1.6 1.6<br />
-25.0 2.6 2.5 2.5 2.5 1.6 1.6 1.7 1.7<br />
-22.2 3.0 2.9 2.9 2.8 1.7 1.8 1.8 1.8<br />
-19.4 3.3 3.3 3.2 3.2 1.8 1.8 1.9 1.9<br />
-16.7 3.7 3.6 3.6 3.5 1.8 1.9 2.0 2.0<br />
-13.9 4.1 4.0 4.0 3.9 1.9 2.0 2.1 2.1<br />
-11.1 4.5 4.4 4.3 4.2 2.0 2.1 2.2 2.2<br />
-8.3 4.9 4.7 4.7 4.6 2.1 2.2 2.3 2.3<br />
-5.6 5.2 5.0 5.0 4.9 2.2 2.3 2.3 2.4<br />
-2.8 5.5 5.3 5.3 5.2 2.2 2.3 2.4 2.5<br />
0.0 5.8 5.6 5.6 5.5 2.3 2.4 2.5 2.5<br />
2.8 6.1 5.9 5.9 5.8 2.3 2.5 2.5 2.6<br />
5.6 6.4 6.2 6.2 6.1 2.4 2.5 2.6 2.7<br />
8.3 8.5 8.3 8.2 8.1 2.5 2.6 2.7 2.8<br />
11.1 9.1 8.9 8.8 8.6 2.5 2.7 2.8 2.8<br />
13.9 9.8 9.5 9.3 9.2 2.6 2.7 2.8 2.9<br />
16.7 10.4 10.1 9.9 9.8 2.7 2.8 2.9 3.0<br />
19.4 11.0 10.7 10.5 10.4 2.7 2.9 3.0 3.0<br />
22.2 11.6 11.3 11.1 11.0 2.8 2.9 3.0 3.1<br />
TWA040CD WITH TWE040CA4-B AT 2547 CMH<br />
O.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT<br />
TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.<br />
C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7<br />
-27.8 2.8 2.7 2.7 2.7 1.9 2.0 2.0 2.1<br />
-25.0 3.3 3.2 3.2 3.1 2.0 2.1 2.1 2.2<br />
-22.2 3.8 3.7 3.6 3.6 2.0 2.1 2.2 2.3<br />
-19.4 4.2 4.1 4.1 4.0 2.1 2.2 2.3 2.3<br />
-16.7 4.7 4.6 4.5 4.5 2.2 2.3 2.4 2.4<br />
-13.9 5.2 5.0 5.0 5.0 2.3 2.4 2.5 2.5<br />
-11.1 5.6 5.5 5.4 5.4 2.4 2.5 2.6 2.6<br />
-8.3 6.1 6.0 5.9 5.9 2.4 2.6 2.7 2.7<br />
-5.6 6.5 6.4 6.3 6.2 2.5 2.7 2.8 2.8<br />
-2.8 6.9 6.8 6.7 6.6 2.6 2.8 2.8 2.9<br />
0.0 7.3 7.1 7.1 7.0 2.7 2.9 2.9 3.0<br />
2.8 7.7 7.5 7.4 7.4 2.8 3.0 3.0 3.1<br />
5.6 8.1 7.9 7.9 7.8 2.9 3.0 3.1 3.2<br />
8.3 10.7 10.5 10.4 10.3 3.1 3.3 3.4 3.5<br />
11.1 11.5 11.3 11.1 11.0 3.2 3.4 3.5 3.6<br />
13.9 12.3 12.0 11.9 11.7 3.3 3.5 3.6 3.7<br />
16.7 13.0 12.7 12.6 12.5 3.4 3.6 3.7 3.8<br />
19.4 13.8 13.5 13.3 13.2 3.5 3.7 3.8 4.0<br />
22.2 14.6 14.2 14.1 13.9 3.6 3.8 4.0 4.1<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(VALUE AT 1698 CMH TIMES CORR. FACTOR<br />
= VALUE AT NEW AIRFLOW)<br />
AIRFLOW 1486 1910<br />
HEATING CAP. X0.98 X1.01<br />
COMPR. KW X1.02 X0.98<br />
VALUES AT ARI RATING CONDITIONS OF:<br />
21.1& 8.3/6.1(HIGH TEMP. POINT)<br />
21.1&-8.3/-9.4(LOW TEMP. POINT)<br />
AIRFLOW = 1698 CMH<br />
HEATING CAP. (HIGH TEMP.) = 8.20 KW<br />
HEATING CAP. (LOW TEMP.) = 4.78 KW<br />
COMPR. POWER (HIGH TEMP.) = 2212 WATTS<br />
COMPR. POWER (LOW TEMP.) = 1745 WATTS<br />
COEFF. OF PERF. (HIGH TEMP.) = 2.86<br />
COEFF. OF PERF. (LOW TEMP.) = 1.98<br />
OUTDOOR FAN POWER = 214 WATTS<br />
INDOOR FAN POWER = 440 WATTS<br />
NOTE: RATED WITH 7.62 METERS OF 22 MM<br />
SUCTION AND 9.5 MM LIQUID LINE<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(VALUE AT 1868 CMH TIMES CORR. FACTOR<br />
= VALUE AT NEW AIRFLOW)<br />
AIRFLOW 1656 2165<br />
HEATING CAP. X0.99 X1.01<br />
COMPR. KW X1.02 X0.98<br />
VALUES AT ARI RATING CONDITIONS OF:<br />
21.1& 8.3/6.1(HIGH TEMP. POINT)<br />
21.1&-8.3/-9.4(LOW TEMP. POINT)<br />
AIRFLOW = 1910 CMH<br />
HEATING CAP. (HIGH TEMP.) = 8.32 KW<br />
HEATING CAP. (LOW TEMP.) = 4.75 KW<br />
COMPR. POWER (HIGH TEMP.) = 2097 WATTS<br />
COMPR. POWER (LOW TEMP.) = 1698 WATTS<br />
COEFF. OF PERF. (HIGH TEMP.) = 3.16<br />
COEFF. OF PERF. (LOW TEMP.) = 2.14<br />
OUTDOOR FAN POWER = 214 WATTS<br />
INDOOR FAN POWER = 300 WATTS<br />
NOTE: RATED WITH 7.62 METERS OF 22 MM<br />
SUCTION AND 9.5 MM LIQUID LINE<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(VALUE AT 2547 CMH TIMES CORR. FACTOR<br />
= VALUE AT NEW AIRFLOW)<br />
AIRFLOW 2250 2887<br />
HEATING CAP. X0.99 X1.01<br />
COMPR. KW X1.02 X0.98<br />
VALUES AT ARI RATING CONDITIONS OF:<br />
21.1& 8.3/6.1(HIGH TEMP. POINT)<br />
21.1&-8.3/-9.4(LOW TEMP. POINT)<br />
AIRFLOW = 2547 CMH<br />
HEATING CAP. (HIGH TEMP.) = 10.49 KW<br />
HEATING CAP. (LOW TEMP.) = 5.98 KW<br />
COMPR. POWER (HIGH TEMP.) = 2612 WATTS<br />
COMPR. POWER (LOW TEMP.) = 1918 WATTS<br />
COEFF. OF PERF. (HIGH TEMP.) = 3.18<br />
COEFF. OF PERF. (LOW TEMP.) = 2.32<br />
OUTDOOR FAN POWER = 244 WATTS<br />
INDOOR FAN POWER = 420 WATTS<br />
NOTE: RATED WITH 7.62 METERS OF 28.6 MM<br />
SUCTION AND 9.5 MM LIQUID LINE<br />
TWE5-PRC001-EN-10-15-99 21
Performance<br />
<strong>Data</strong> Heating<br />
English Units<br />
TWA040CD WITH TWE050CA5-C AT 1500 CFM<br />
O.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT<br />
TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.<br />
F. 60 70 75 80 60 70 75 80<br />
-18 9.68 9.46 9.36 9.25 1.94 2.04 2.08 2.13<br />
-13 11.3 11.1 11.0 10.8 2.02 2.13 2.18 2.23<br />
-8 13.0 12.7 12.6 12.4 2.10 2.21 2.27 2.32<br />
-3 14.6 14.3 14.2 14.0 2.19 2.30 2.36 2.42<br />
2 16.3 15.9 15.8 15.6 2.27 2.39 2.45 2.51<br />
7 17.9 17.6 17.4 17.2 2.35 2.48 2.54 2.61<br />
12 19.6 19.2 19.0 18.8 2.43 2.57 2.63 2.70<br />
17 21.2 20.8 20.6 20.4 2.51 2.65 2.73 2.80<br />
22 22.6 22.1 21.8 21.6 2.59 2.74 2.82 2.89<br />
27 23.9 23.4 23.1 22.8 2.67 2.83 2.91 2.99<br />
32 25.2 24.6 24.4 24.1 2.76 2.92 3.00 3.08<br />
37 26.5 25.9 25.6 25.3 2.84 3.01 3.09 3.17<br />
42 27.8 27.2 26.9 26.6 2.92 3.09 3.18 3.27<br />
47 37.2 36.4 36.0 35.6 3.13 3.32 3.41 3.51<br />
52 39.9 39.0 38.6 38.1 3.23 3.43 3.53 3.63<br />
57 42.5 41.6 41.1 40.7 3.34 3.54 3.64 3.75<br />
62 45.2 44.2 43.7 43.2 3.44 3.65 3.76 3.86<br />
67 47.9 46.8 46.3 45.7 3.54 3.76 3.87 3.98<br />
72 50.5 49.4 48.8 48.3 3.65 3.88 3.99 4.10<br />
TWA050CD WITH TWE050CA5-C AT 1800 CFM<br />
O.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT<br />
TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.<br />
F. 60 70 75 80 60 70 75 80<br />
-18 12.5 12.2 12.1 12.0 2.50 2.62 2.67 2.73<br />
-13 14.9 14.6 14.4 14.2 2.60 2.72 2.78 2.84<br />
-8 17.3 16.9 16.7 16.5 2.69 2.82 2.88 2.94<br />
-3 19.7 19.2 19.0 18.8 2.78 2.92 2.98 3.05<br />
2 22.0 21.6 21.3 21.1 2.87 3.02 3.09 3.16<br />
7 24.4 23.9 23.7 23.4 2.97 3.12 3.19 3.27<br />
12 26.8 26.3 26.0 25.7 3.06 3.22 3.30 3.38<br />
17 29.2 28.6 28.3 28.0 3.15 3.32 3.40 3.48<br />
22 30.2 29.5 29.2 28.9 3.25 3.42 3.51 3.59<br />
27 31.1 30.5 30.2 29.8 3.34 3.52 3.61 3.70<br />
32 32.1 31.4 31.1 30.8 3.44 3.63 3.72 3.81<br />
37 33.1 32.4 32.0 31.7 3.54 3.73 3.83 3.92<br />
42 34.0 33.3 33.0 32.6 3.63 3.83 3.93 4.03<br />
47 48.0 47.0 46.5 46.0 4.00 4.23 4.34 4.45<br />
52 51.2 50.1 49.5 49.0 4.14 4.38 4.50 4.61<br />
57 54.3 53.1 52.5 52.0 4.28 4.53 4.65 4.78<br />
62 57.5 56.2 55.6 54.9 4.43 4.68 4.81 4.94<br />
67 60.6 59.3 58.6 57.9 4.57 4.83 4.97 5.10<br />
72 63.7 62.3 61.6 60.9 4.71 4.98 5.12 5.26<br />
TWA060CD WITH TWE050CA5-C AT 1800 CFM<br />
O.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT<br />
TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.<br />
F. 60 70 75 80 60 70 75 80<br />
-18 14.0 13.8 13.7 13.5 3.24 3.37 3.43 3.50<br />
-13 16.9 16.6 16.4 16.3 3.36 3.50 3.57 3.64<br />
-8 19.7 19.4 19.2 19.1 3.49 3.64 3.71 3.79<br />
-3 22.6 22.2 22.0 21.8 3.62 3.77 3.85 3.93<br />
2 25.4 25.0 24.8 24.6 3.74 3.91 3.99 4.07<br />
7 28.3 27.8 27.6 27.3 3.87 4.04 4.13 4.22<br />
12 31.1 30.6 30.3 30.1 3.99 4.18 4.27 4.36<br />
17 34.0 33.4 33.1 32.8 4.12 4.31 4.41 4.50<br />
22 35.7 35.1 34.8 34.5 4.52 4.74 4.85 4.95<br />
27 37.4 36.8 36.5 36.2 4.93 5.17 5.28 5.40<br />
32 39.1 38.5 38.2 37.8 5.33 5.59 5.72 5.85<br />
37 40.9 40.2 39.8 39.5 5.74 6.02 6.16 6.30<br />
42 42.6 41.9 41.5 41.2 6.14 6.45 6.60 6.76<br />
47 53.9 53.0 52.5 52.1 5.33 5.59 5.72 5.85<br />
52 57.2 56.3 55.8 55.3 5.53 5.80 5.94 6.08<br />
57 60.6 59.5 59.0 58.5 5.73 6.02 6.16 6.30<br />
62 63.9 62.8 62.3 61.7 5.94 6.23 6.38 6.53<br />
67 67.2 66.1 65.5 64.9 6.14 6.44 6.60 6.75<br />
72 70.5 69.3 68.7 68.1 6.34 6.66 6.82 6.98<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(VALUE AT 1500 CFM TIMES CORR. FACTOR<br />
= VALUE AT NEW AIRFLOW)<br />
AIRFLOW 1325 1700<br />
HEATING CAP. X0.99 X1.01<br />
COMPR. KW X1.02 X0.98<br />
VALUES AT ARI RATING CONDITIONS OF:<br />
70&47/43 (HIGH TEMP. POINT)<br />
70&17/15 (LOW TEMP. POINT)<br />
AIRFLOW = 1500 CFM<br />
HEATING CAP. (HIGH TEMP.) = 36400 BTUH<br />
HEATING CAP. (LOW TEMP.) = 20800 BTUH<br />
COMPR. POWER (HIGH TEMP.) = 2566 WATTS<br />
COMPR. POWER (LOW TEMP.) = 1900 WATTS<br />
COEFF. OF PERF. (HIGH TEMP.) = 3.18<br />
COEFF. OF PERF. (LOW TEMP.) = 2.30<br />
OUTDOOR FAN POWER = 244 WATTS<br />
INDOOR FAN POWER = 510 WATTS<br />
NOTE: RATED WITH 25 FEET OF 1-1/8<br />
SUCTION AND 3/8 LIQUID LINE<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(VALUE AT 1800 CFM TIMES CORR. FACTOR<br />
= VALUE AT NEW AIRFLOW)<br />
AIRFLOW 1575 2025<br />
HEATING CAP. X0.99 X1.01<br />
COMPR. KW X1.02 X0.98<br />
VALUES AT ARI RATING CONDITIONS OF:<br />
70&47/43 (HIGH TEMP. POINT)<br />
70&17/15 (LOW TEMP. POINT)<br />
AIRFLOW = 1800 CFM<br />
HEATING CAP. (HIGH TEMP.) = 47000 BTUH<br />
HEATING CAP. (LOW TEMP.) = 28600 BTUH<br />
COMPR. POWER (HIGH TEMP.) = 3222 WATTS<br />
COMPR. POWER (LOW TEMP.) = 2313 WATTS<br />
COEFF. OF PERF. (HIGH TEMP.) = 3.24<br />
COEFF. OF PERF. (LOW TEMP.) = 2.50<br />
OUTDOOR FAN POWER = 255 WATTS<br />
INDOOR FAN POWER = 750 WATTS<br />
NOTE: RATED WITH 25 FEET OF 1-1/8<br />
SUCTION AND 3/8 LIQUID LINE<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(VALUE AT 1800 CFM TIMES CORR. FACTOR<br />
= VALUE AT NEW AIRFLOW)<br />
AIRFLOW 1575 2025<br />
HEATING CAP. X0.99 X1.01<br />
COMPR. KW X1.02 X0.98<br />
VALUES AT ARI RATING CONDITIONS OF:<br />
70&47/43 (HIGH TEMP. POINT)<br />
70&17/15 (LOW TEMP. POINT)<br />
AIRFLOW = 1800 CFM<br />
HEATING CAP. (HIGH TEMP.) = 53000 BTUH<br />
HEATING CAP. (LOW TEMP.) = 33400 BTUH<br />
COMPR. POWER (HIGH TEMP.) = 4446 WATTS<br />
COMPR. POWER (LOW TEMP.) = 3166 WATTS<br />
COEFF. OF PERF. (HIGH TEMP.) = 2.76<br />
COEFF. OF PERF. (LOW TEMP.) = 2.26<br />
OUTDOOR FAN POWER = 395 WATTS<br />
INDOOR FAN POWER = 750 WATTS<br />
NOTE: RATED WITH 25 FEET OF 1-1/8<br />
SUCTION AND 3/8 LIQUID LINE<br />
22 TWE5-PRC001-EN-10-15-99
Performance<br />
<strong>Data</strong> Heating<br />
Metric Units<br />
TWA040CD WITH TWE050CA5-C AT 2547 CMH<br />
O.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT<br />
TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.<br />
C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7<br />
-27.8 2.8 2.8 2.7 2.7 1.9 2.0 2.1 2.1<br />
-25.0 3.3 3.3 3.2 3.2 2.0 2.1 2.2 2.2<br />
-22.2 3.8 3.7 3.7 3.6 2.1 2.2 2.3 2.3<br />
-19.4 4.3 4.2 4.2 4.1 2.2 2.3 2.4 2.4<br />
-16.7 4.8 4.7 4.6 4.6 2.3 2.4 2.5 2.5<br />
-13.9 5.2 5.2 5.1 5.0 2.3 2.5 2.5 2.6<br />
-11.1 5.7 5.6 5.6 5.5 2.4 2.6 2.6 2.7<br />
-8.3 6.2 6.1 6.0 6.0 2.5 2.7 2.7 2.8<br />
-5.6 6.6 6.5 6.4 6.3 2.6 2.7 2.8 2.9<br />
-2.8 7.0 6.9 6.8 6.7 2.7 2.8 2.9 3.0<br />
0.0 7.4 7.2 7.1 7.1 2.8 2.9 3.0 3.1<br />
2.8 7.8 7.6 7.5 7.4 2.8 3.0 3.1 3.2<br />
5.6 8.1 8.0 7.9 7.8 2.9 3.1 3.2 3.3<br />
8.3 10.9 10.7 10.5 10.4 3.1 3.3 3.4 3.5<br />
11.1 11.7 11.4 11.3 11.2 3.2 3.4 3.5 3.6<br />
13.9 12.5 12.2 12.0 11.9 3.3 3.5 3.6 3.8<br />
16.7 13.2 13.0 12.8 12.7 3.4 3.7 3.8 3.9<br />
19.4 14.0 13.7 13.6 13.4 3.5 3.8 3.9 4.0<br />
22.2 14.8 14.5 14.3 14.2 3.7 3.9 4.0 4.1<br />
TWA050CD WITH TWE050CA5-C AT 3057 CMH<br />
O.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT<br />
TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.<br />
C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7<br />
-27.8 3.7 3.6 3.5 3.5 2.5 2.6 2.7 2.7<br />
-25.0 4.4 4.3 4.2 4.2 2.6 2.7 2.8 2.8<br />
-22.2 5.1 5.0 4.9 4.8 2.7 2.8 2.9 2.9<br />
-19.4 5.8 5.6 5.6 5.5 2.8 2.9 3.0 3.0<br />
-16.7 6.4 6.3 6.2 6.2 2.9 3.0 3.1 3.2<br />
-13.9 7.1 7.0 6.9 6.9 3.0 3.1 3.2 3.3<br />
-11.1 7.9 7.7 7.6 7.5 3.1 3.2 3.3 3.4<br />
-8.3 8.6 8.4 8.3 8.2 3.2 3.3 3.4 3.5<br />
-5.6 8.8 8.6 8.6 8.5 3.3 3.4 3.5 3.6<br />
-2.8 9.1 8.9 8.8 8.7 3.3 3.5 3.6 3.7<br />
0.0 9.4 9.2 9.1 9.0 3.4 3.6 3.7 3.8<br />
2.8 9.7 9.5 9.4 9.3 3.5 3.7 3.8 3.9<br />
5.6 10.0 9.8 9.7 9.6 3.6 3.8 3.9 4.0<br />
8.3 14.1 13.8 13.6 13.5 4.0 4.2 4.3 4.4<br />
11.1 15.0 14.7 14.5 14.4 4.1 4.4 4.5 4.6<br />
13.9 15.9 15.6 15.4 15.2 4.3 4.5 4.7 4.8<br />
16.7 16.8 16.5 16.3 16.1 4.4 4.7 4.8 4.9<br />
19.4 17.8 17.4 17.2 17.0 4.6 4.8 5.0 5.1<br />
22.2 18.7 18.3 18.0 17.8 4.7 5.0 5.1 5.3<br />
TWA060CD WITH TWE050CA5-C AT 3057 CMH<br />
O.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT<br />
TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.<br />
C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7<br />
-27.8 4.1 4.0 4.0 4.0 3.2 3.4 3.4 3.5<br />
-25.0 5.0 4.9 4.8 4.8 3.4 3.5 3.6 3.6<br />
-22.2 5.8 5.7 5.6 5.6 3.5 3.6 3.7 3.8<br />
-19.4 6.6 6.5 6.4 6.4 3.6 3.8 3.8 3.9<br />
-16.7 7.4 7.3 7.3 7.2 3.7 3.9 4.0 4.1<br />
-13.9 8.3 8.1 8.1 8.0 3.9 4.0 4.1 4.2<br />
-11.1 9.1 9.0 8.9 8.8 4.0 4.2 4.3 4.4<br />
-8.3 10.0 9.8 9.7 9.6 4.1 4.3 4.4 4.5<br />
-5.6 10.5 10.3 10.2 10.1 4.5 4.7 4.8 4.9<br />
-2.8 11.0 10.8 10.7 10.6 4.9 5.2 5.3 5.4<br />
0.0 11.5 11.3 11.2 11.1 5.3 5.6 5.7 5.8<br />
2.8 12.0 11.8 11.7 11.6 5.7 6.0 6.2 6.3<br />
5.6 12.5 12.3 12.2 12.1 6.1 6.4 6.6 6.8<br />
8.3 15.8 15.5 15.4 15.3 5.3 5.6 5.7 5.8<br />
11.1 16.8 16.5 16.3 16.2 5.5 5.8 5.9 6.1<br />
13.9 17.8 17.4 17.3 17.1 5.7 6.0 6.2 6.3<br />
16.7 18.7 18.4 18.3 18.1 5.9 6.2 6.4 6.5<br />
19.4 19.7 19.4 19.2 19.0 6.1 6.4 6.6 6.8<br />
22.2 20.7 20.3 20.1 20.0 6.3 6.7 6.8 7.0<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(VALUE AT 2547 CMH TIMES CORR. FACTOR<br />
= VALUE AT NEW AIRFLOW)<br />
AIRFLOW 2250 2887<br />
HEATING CAP. X0.99 X1.01<br />
COMPR. KW X1.02 X0.98<br />
VALUES AT ARI RATING CONDITIONS OF:<br />
21.1& 8.3/6.1(HIGH TEMP. POINT)<br />
21.1&-8.3/-9.4(LOW TEMP. POINT)<br />
AIRFLOW = 2547 CMH<br />
HEATING CAP. (HIGH TEMP.) = 10.67 KW<br />
HEATING CAP. (LOW TEMP.) = 6.09 KW<br />
COMPR. POWER (HIGH TEMP.) = 2566 WATTS<br />
COMPR. POWER (LOW TEMP.) = 1900 WATTS<br />
COEFF. OF PERF. (HIGH TEMP.) = 3.18<br />
COEFF. OF PERF. (LOW TEMP.) = 2.30<br />
OUTDOOR FAN POWER = 244 WATTS<br />
INDOOR FAN POWER = 510 WATTS<br />
NOTE: RATED WITH 7.62 METERS OF 28.6 MM<br />
SUCTION AND 9.5 MM LIQUID LINE<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(VALUE AT 3057 CMH TIMES CORR. FACTOR<br />
= VALUE AT NEW AIRFLOW)<br />
AIRFLOW 2675 3439<br />
HEATING CAP. X0.99 X1.01<br />
COMPR. KW X1.02 X0.98<br />
VALUES AT ARI RATING CONDITIONS OF:<br />
21.1& 8.3/6.1(HIGH TEMP. POINT)<br />
21.1&-8.3/-9.4(LOW TEMP. POINT)<br />
AIRFLOW = 3057 CMH<br />
HEATING CAP. (HIGH TEMP.) = 13.77 KW<br />
HEATING CAP. (LOW TEMP.) = 8.38 KW<br />
COMPR. POWER (HIGH TEMP.) = 3222 WATTS<br />
COMPR. POWER (LOW TEMP.) = 2313 WATTS<br />
COEFF. OF PERF. (HIGH TEMP.) = 3.24<br />
COEFF. OF PERF. (LOW TEMP.) = 2.50<br />
OUTDOOR FAN POWER = 255 WATTS<br />
INDOOR FAN POWER = 750 WATTS<br />
NOTE: RATED WITH 7.62 METERS OF 28.6 MM<br />
SUCTION AND 9.5 MM LIQUID LINE<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(VALUE AT 3057 CMH TIMES CORR. FACTOR<br />
= VALUE AT NEW AIRFLOW)<br />
AIRFLOW 2675 3439<br />
HEATING CAP. X0.99 X1.01<br />
COMPR. KW X1.02 X0.98<br />
VALUES AT ARI RATING CONDITIONS OF:<br />
21.1& 8.3/6.1(HIGH TEMP. POINT)<br />
21.1&-8.3/-9.4(LOW TEMP. POINT)<br />
AIRFLOW = 3057 CMH<br />
HEATING CAP. (HIGH TEMP.) = 15.53 KW<br />
HEATING CAP. (LOW TEMP.) = 9.79 KW<br />
COMPR. POWER (HIGH TEMP.) = 4446 WATTS<br />
COMPR. POWER (LOW TEMP.) = 3166 WATTS<br />
COEFF. OF PERF. (HIGH TEMP.) = 2.76<br />
COEFF. OF PERF. (LOW TEMP.) = 2.26<br />
OUTDOOR FAN POWER = 395 WATTS<br />
INDOOR FAN POWER = 750 WATTS<br />
NOTE: RATED WITH 7.62 METERS OF 28.6 MM<br />
SUCTION AND 9.5 MM LIQUID LINE<br />
TWE5-PRC001-EN-10-15-99 23
Performance<br />
<strong>Data</strong><br />
Blower Performance — TWE030CA40B — Wet Coil<br />
Evaporator Fan Performance<br />
EXTERNAL STATIC PRESSURE INCHES OF WATER (PASCALS)<br />
UPFLOW & DOWNFLOW (See Notes)<br />
HORIZONTAL; NO FILTER (See Notes)<br />
220 VOLTS 220 VOLTS<br />
CFM CMH Hl MED LO Hl MED LO<br />
600 1018.8 0.72 (179.4) 0.71 (176.9)<br />
650 1103.7 0.62 (154.4) 0.61 (152.0)<br />
700 1188.6 0.86 (214.2) 0.51 (127.0) 0.84 (209.2) 0.50 (124.6)<br />
750 1273.5 0.75 (186.8) 0.40 (99.6) 0.72 (179.4) 0.39 (97.1)<br />
800 1358.4 0.89 (221.7) 0.65 (161.9) 0.29 (72.2) 0.87 (216.7) 0.62 (154.4) 0.28 (69.7)<br />
850 1443.3 0.81 (201.8) 0.54 (134.5) 0.18 (44.8) 0.79 (196.8) 0.51 (127.0) 0.17 (42.3)<br />
900 1528.2 0.72 (179.4) 0.43 (107.1) 0.06 (14.9) 0.69 (171.9) 0.40 (99.6) 0.08 (19.9)<br />
950 1613.1 0.63 (156.9) 0.32 (79.7) 0.61 (152.0) 0.30 (74.7)<br />
1000 1698.0 0.53 (132.0) 0.21 (52.3) 0.51 (127.0) 0.17 (42.3)<br />
1050 1782.9 0.42 (104.6) 0.10 (24.9) 0.40 (99.6) 0.02 (5.0)<br />
1100 1867.8 0.31 (77.2) 0.31 (77.2)<br />
1150 1952.7 0.20 (49.8) 0.22 (54.8)<br />
1200 2037.6 0.08 (19.9) 0.10 (24.9)<br />
NOTES:<br />
Vertical: With filter, no horizontal drip tray. Subtract 0.06" W.G. (15) for downflow.<br />
Horizontal: As shipped, but without filter. Subtract 0.05" W.G. (12.5) for horizontal left.<br />
Blower Performance — TWE040CA40C — Wet Coil<br />
EXTERNAL STATIC PRESSURE INCHES OF WATER (PASCALS)<br />
UPFLOW & DOWNFLOW (See Notes)<br />
HORIZONTAL; NO FILTER (See Notes)<br />
220 VOLTS 220 VOLTS<br />
CFM CMH Hl MED LO Hl MED LO<br />
700 1188.6 0.58 (144.5)<br />
750 1273.5 0.61 (152.0) 0.55 (137.0)<br />
800 1358.4 0.61 (152.0) 0.58 (144.5) 0.52 (129.5) 0.58 (144.5)<br />
850 1443.3 0.57 (142.0) 0.54 (134.5) 0.48 (119.6) 0.52 (129.5)<br />
900 1528.2 0.53 (132.0) 0.51 (127.0) 0.44 (109.6) 0.49 (122.1)<br />
950 1613.1 0.49 (122.1) 0.47 (117.1) 0.40 (99.6) 0.57 (142.0) 0.45 (112.1)<br />
1000 1698.0 0.45 (112.1) 0.43 (107.1) 0.34 (84.7) 0.53 (132.0) 0.50 (124.6) 0.40 (99.6)<br />
1050 1782.9 0.40 (99.6) 0.38 (94.7) 0.28 (69.7) 0.48 (119.6) 0.45 (112.1) 0.35 (87.2)<br />
1100 1867.8 0.36 (89.7) 0.34 (84.7) 0.22 (54.8) 0.43 (107.1) 0.40 (99.6) 0.30 (74.7)<br />
1150 1952.7 0.31 (77.2) 0.29 (72.2) 0.15 (37.4) 0.39 (97.1) 0.37 (92.2) 0.22 (54.8)<br />
1200 2037.6 0.26 (64.8) 0.24 (59.8) 0.08 (19.9) 0.35 (87.2) 0.32 (79.7) 0.17 (42.3)<br />
1250 2122.5 0.21 (52.3) 0.18 (44.8) 0.00 (0.0) 0.31 (77.2) 0.28 (69.7) 0.10 (24.9)<br />
1300 2207.4 0.17 (42.3) 0.13 (32.4) 0.26 (64.8) 0.22 (54.8) 0.01 (2.5)<br />
1350 2292.3 0.11 (27.4) 0.07 (17.4) 0.21 (52.3) 0.18 (44.8)<br />
1400 2377.2 0.06 (14.9) 0.01 (2.5) 0.15 (37.4) 0.12 (29.9)<br />
1450 2462.1 0.01 (2.5) 0.11 (27.4) 0.08 (19.9)<br />
1500 2547.0 0.00 0.05 (12.5) 0.02 (5.0)<br />
NOTES:<br />
Vertical: With filter, no horizontal drip tray. Small apex baffle. Subtract 0.06" W.G. (15) for downflow.<br />
Horizontal: As shipped, but without filter. Subtract 0.05" W.G. (12.5) for horizontal left.<br />
24 TWE5-PRC001-EN-10-15-99
Performance<br />
<strong>Data</strong><br />
Blower Performance — TWE050CA50D — Wet Coil<br />
Evaporator Fan Performance<br />
EXTERNAL STATIC PRESSURE INCHES OF WATER (PASCALS)<br />
UPFLOW & DOWNFLOW (See Notes)<br />
HORIZONTAL; NO FILTER (See Notes)<br />
220 VOLTS 220 VOLTS<br />
CFM CMH Hl MED LO Hl MED LO<br />
900 1528.2<br />
950 1613.1 0.63 (156.9)<br />
1000 1698.0 0.61 (152.0) 0.62 (154.4)<br />
1050 1782.9 0.58 (144.5) 0.60 (149.5)<br />
1100 1867.8 0.54 (134.5) 0.57 (142.0)<br />
1150 1952.7 0.50 (124.6) 0.53 (132.0)<br />
1200 2037.6 0.45 (112.1) 0.49 (122.1)<br />
1250 2122.5 0.61 (152.0) 0.39 (97.1) 0.64 (159.4) 0.44 (109.6)<br />
1300 2207.4 0.59 (147.0) 0.57 (142.0) 0.33 (82.2) 0.62 (154.4) 0.61 (152.0) 0.38 (94.7)<br />
1350 2292.3 0.56 (139.5) 0.53 (132.0) 0.26 (64.8) 0.59 (147.0) 0.58 (144.5) 0.32 (79.7)<br />
1400 2377.2 0.52 (129.5) 0.49 (122.1) 0.18 (44.8) 0.56 (139.5) 0.55 (137.0) 0.25 (62.3)<br />
1450 2462.1 0.48 (119.6) 0.45 (112.1) 0.10 (24.9) 0.52 (129.5) 0.52 (129.5) 0.18 (44.8)<br />
1500 2547.0 0.44 (109.6) 0.40 (99.6) 0.01 (2.5) 0.49 (122.1) 0.48 (119.6) 0.11 (27.4)<br />
1550 2631.9 0.40 (99.6) 0.35 (87.2) 0.47 (117.1) 0.44 (109.6) 0.00 (0.0)<br />
1600 2716.8 0.35 (87.2) 0.30 (74.7) 0.45 (112.1) 0.40 (99.6)<br />
1650 2801.7 0.31 (77.2) 0.25 (62.3) 0.41 (102.1) 0.35 (87.2)<br />
1700 2886.6 0.26 (64.8) 0.20 (49.8) 0.36 (89.7) 0.28 (69.7)<br />
1750 2971.5 0.21 (52.3) 0.14 (34.9) 0.30 (74.7) 0.20 (49.8)<br />
1800 3056.4 0.16 (39.9) 0.08 (19.9) 0.24 (59.8) 0.13 (32.4)<br />
1850 3141.3 0.11 (27.4) 0.02 (5.0) 0.17 (42.3) 0.07 (17.4)<br />
1900 3226.2 0.05 (12.5) 0.10 (24.9) 0.01 (2.5)<br />
1950 3311.1 0.02 (5.0)<br />
NOTES:<br />
Vertical: With filter, no horizontal drip tray. Small apex baffle. Subtract 0.06" W.G. (15) for downflow.<br />
Horizontal: As shipped, but without filter. Subtract 0.05" W.G (12.5) for horizontal left.<br />
TWE5-PRC001-EN-10-15-99 25
Performance<br />
<strong>Data</strong><br />
<strong>Air</strong> Pressure Drop (Inches) - Electric Heaters<br />
Pressure Drop For Electric Heaters In <strong>Air</strong> <strong>Handler</strong> Models<br />
NUMBER OF RACKS<br />
1 2 3 4 5<br />
AIRFLOW AIRFLOW AIR PRESSURE DROP<br />
CFM CMH IN. W.G. (PASCALS)<br />
600 1018.8 0.01 (2.5) 0.02 (5.0) 0.02 (5.0)<br />
700 1188.6 0.01 (2.5) 0.02 (5.0) 0.02 (5.0)<br />
800 1358.4 0.02 (5.0) 0.03 (7.5) 0.03 (7.5) 0.04 (10.0)<br />
900 1528.2 0.03 (7.5) 0.03 (7.5) 0.04 (10.0) 0.05 (12.5)<br />
1000 1698.0 0.04 (10.0) 0.04 (10.0) 0.05 (12.5) 0.06 (14.9)<br />
1100 1867.8 0.04 (10.0) 0.05 (12.5) 0.06 (14.9) 0.07 (17.4) 0.08 (19.9)<br />
1200 2037.6 0.05 (12.5) 0.06 (14.9) 0.07 (17.4) 0.08 (19.9) 0.09 (22.4)<br />
1300 2207.4 0.06 (14.9) 0.07 (17.4) 0.08 (19.9) 0.09 (22.4) 0.11 (27.4)<br />
1400 2377.2 0.07 (17.4) 0.08 (19.9) 0.10 (24.9) 0.11 (27.4) 0.13 (32.4)<br />
1500 2547.0 0.08 (19.9) 0.09 (22.4) 0.11 (27.4) 0.13 (32.4) 0.15 (37.4)<br />
1600 2716.8 0.09 (22.4) 0.10 (24.9) 0.12 (29.9) 0.15 (37.4) 0.17 (42.3)<br />
1700 2886.6 0.10 (24.9) 0.11 (27.4) 0.14 (34.9) 0.17 (42.3) 0.19 (47.3)<br />
1800 3056.4 0.11 (27.4) 0.13 (32.4) 0.16 (39.9) 0.19 (47.3) 0.21 (52.3)<br />
1900 3226.2 0.13 (32.4) 0.15 (37.4) 0.18 (44.8) 0.21 (52.3) 0.23 (57.3)<br />
2000 3396.0 0.14 (34.9) 0.17 (42.3) 0.20 (49.8) 0.23 (57.3) 0.26 (64.8)<br />
NOTES:<br />
1. See <strong>Product</strong> <strong>Data</strong> or <strong>Air</strong> <strong>Handler</strong> nameplate for approved combinations of <strong>Air</strong> <strong>Handler</strong>s and Heaters.<br />
2. Heater model numbers may have additional suffix digits.<br />
HEATER RACKS<br />
HEATER NO. OF<br />
MODEL NO. RACKS<br />
BAY96X1405 1<br />
BAY96X1406 2<br />
BAY96X1408 2<br />
BAY96X1410 2<br />
BAY96X1411 3<br />
BAY96X1415 3<br />
BAY96X1419 4<br />
BAY96X1421 4<br />
BAY96X1426 5<br />
BAY96X3411 3<br />
BAY96X3415 3<br />
26 TWE5-PRC001-EN-10-15-99
Supplementary<br />
Heaters<br />
THESE AIR HANDLERS ARE CONVERTIBLE AND MOTOR SPEED TAPS VARY BY THE UNIT ORIENTATION.<br />
TWE030C-Heater Model Number BAY96X<br />
Unit 1405 1406 1408,F 1410,F 1410A 1411 1411A 1415 1419 1421 3411 3415<br />
Position Application 4.0 KW 4.8 KW 6.4 KW 8.0 KW 8.8 KW 8.8 KW 8.8 KW 12.8 KW 16.0 KW 17.6 KW 8.8 KW 12.8 KW<br />
Vertical A/C or Elec. Furnace L L L L L L L L L L L L<br />
Upflow Heat Pump L L L L L L L L M M L L<br />
Vertical A/C or Elec. Furnace L L L L L L L L L L L L<br />
Downflow Heat Pump L L L L L L L L H H L H<br />
Horizontal A/C or Elec. Furnace L L L L L L L L L L L L<br />
Left Heat Pump L L L L L L L L M M L L<br />
Horizontal A/C or Elec. Furnace L L L L L L L L L L L L<br />
Right Heat Pump L L L L L L L L H H L L<br />
(L) Low, (M) Medium, (H) High indicate minimum heating speed setting for blower/motor operation. 1414 and 1426 not approved for this model.<br />
TWE040C-Heater Model Number BAY96X<br />
Unit 1405 1406 1408,F 1410,F 1410A 1411 1411A 1415 1419 1421 3411 3415<br />
Position Application 4.0 KW 4.8 KW 6.4 KW 8.0 KW 8.8 KW 8.8 KW 8.8 KW 12.8 KW 16.0 KW 17.6 KW 8.8 KW 12.8 KW<br />
Vertical A/C or Elec. Furnace L L L L L L L L L L L L<br />
Upflow Heat Pump L L L L L M M H H H M M<br />
Vertical A/C or Elec. Furnace L L L L L L L L L L L L<br />
Downflow Heat Pump L L L L L L L H H H L L<br />
Horizontal A/C or Elec. Furnace L L L L L L L L L L L L<br />
Left Heat Pump L L L L L L L H H H L L<br />
Horizontal A/C or Elec. Furnace L L L L L L L L L L L L<br />
Right Heat Pump L L L L L L L H H H L L<br />
(L) Low, (M) Medium, (H) High indicate minimum heating speed setting for blower/motor operation. 1414 not approved for this model.<br />
TWE050C-Heater Model Number BAY96X<br />
Unit 1405 1406 1408,F 1410,F 1410A 1415 1419 1421 1426 3415<br />
Position Application 4.0 KW 4.8 KW 6.4 KW 8.0 KW 8.8 KW 12.8 KW 16.0 KW 17.6 KW 21.6 KW 12.8 KW<br />
Vertical A/C or Elec. Furnace — — L L L L L L L L<br />
Upflow Heat Pump L L L L L L M M H L<br />
Vertical A/C or Elec. Furnace — — L L L L L L L L<br />
Downflow Heat Pump L L L L L L H H H L<br />
Horizontal A/C or Elec. Furnace — — L L L L L L L L<br />
Left Heat Pump L L L L L L H H H L<br />
Horizontal A/C or Elec. Furnace — — L L L L L L L L<br />
Right Heat Pump L L L L L L M M H L<br />
(L) Low, (M) Medium, (H) High indicate minimum heating speed setting for blower/motor operation. 14141,A and 1414 not approved for this model.<br />
TWE5-PRC001-EN-10-15-99 27
Electrical<br />
<strong>Data</strong><br />
System Wiring Diagram<br />
Legend<br />
Symbols<br />
NOTES:<br />
1. DO NOT USE REQ TRANSFORMER LEAD IN THIS APPLICATION<br />
2. ACCESSORY KIT BAY24X038 MAY BE USED WHEN AUTOMATIC SPEED<br />
CHANGE FOR HEATING/COOLING OPERATION IS DESIRED.<br />
28 TWE5-PRC001-EN-10-15-99
Dimensions<br />
TWE030-050C Outline Drawing<br />
ALL DIMENSIONS ARE IN INCHES (MM)<br />
MINIMUM UNIT CLEARANCE SALE<br />
TO COMBUSTIBLE SERVICE CLEARANCE<br />
MATERIAL (REQUIRED) (RECOMMENDED)<br />
SIDES 0 (0) 2 (50.8)<br />
FRONT 0 (0) 21 (533.4)<br />
BACK 0 (0) 0 (0)<br />
INLET DUCT 0 (0) 1 (25.4)<br />
OUTLET DUCT 1 (25.4)<br />
FLOW<br />
MODEL NO. A B C D E F CONTROL<br />
TWE030CA4 43.00 15.57 21.50 19.50 20.28 21.63 FCCV<br />
(1092.2) (395.5) (761.1) (495.3) (515.1) (549.4)<br />
TWE040CA4 51.75 24.32 23.50 21.50 22.28 23.63 FCCV<br />
(1134.5) (617.7) (596.9) (761.1) (565.9) (600.2)<br />
TWE050CA5 57.90 30.47 23.50 21.50 22.28 23.63 TXV<br />
(1470.7) (773.9) (596.9) (761.1) (565.9) (600.2)<br />
TWE5-PRC001-EN-10-15-99 29
Dimensions<br />
TWJ020-036CA and TWA030-060CA Outline Drawing<br />
All dimensions are in inches (mm)<br />
SERVICE PANEL<br />
ELECTRICAL AND<br />
REFRIGERANT COMPONENTS<br />
CLEARANCES PER PREVAILING<br />
C<br />
B<br />
1 1 /8 (28.6) DIA. K.O. WITH<br />
7/8 (22.2) DIA. HOLE<br />
ELECTRICAL POWER<br />
9 3 /4<br />
(248)<br />
6 7 /8<br />
(175)<br />
1 1 /4<br />
(32)<br />
A<br />
TOP DISCHARGE AREA SHOULD BE<br />
UNRESTRICTED FOR AT LEAST FIVE (5)<br />
FEET ABOVE UNIT. UNIT SHOULD BE<br />
PLACED SO ROOF RUN-OFF WATER<br />
DOES NOT POUR DIRECTLY ON UNIT,<br />
AND SHOULD BE AT LEAST 12" (305)<br />
FROM WALL AND ALL SURROUNDING<br />
SHRUBBERY ON TWO SIDES. OTHER<br />
TWO SIDES UNRESTRICTED.<br />
7/8 (22.2) DIA. HOLE<br />
LOW VOLTAGE<br />
8 1 /4<br />
(210) 4 3 /4<br />
(121)<br />
2 (51)<br />
GAS LINE SERVICE VALVE, "D" O.D.<br />
FEMALE BRAZED CONNECTION WITH<br />
1/4" SAE FLARE PRESSURE TAP<br />
FITTING.<br />
9<br />
(229)<br />
5<br />
(127)<br />
1 5 /8 (41)<br />
2 3 /8 (60)<br />
FIG. 2<br />
FIG. 1<br />
GAS LINE BALL SERVICE VALVE, BALL<br />
1/4 TURN "D" O.D. FEMALE BRAZED<br />
CONNECTION WITH 1/4" SAE FLARE<br />
PRESSURE TAP FITTING.<br />
LIQUID LINE SERVICE VALVE, "E" O.D.<br />
FEMALE BRAZED CONNECTION WITH<br />
1/4" SAE FLARE PRESSURE TAP<br />
FITTING.<br />
LIQUID LINE SERVICE VALVE, "E" O.D.<br />
FEMALE BRAZED CONNECTION WITH<br />
1/4" SAE FLARE PRESSURE TAP<br />
FITTING.<br />
MODEL Figure A B C D E<br />
TWJ020CA00A 1 24 3 /8 28 1 /4 24 5 /8<br />
3<br />
/4<br />
5<br />
/16<br />
(619) (718) (625) (19) (8)<br />
TWJ024CA00A 1 32 3 /4 28 1 /4 24 5 /8<br />
3<br />
/4<br />
5<br />
/16<br />
(832) (718) (625) (19) (8)<br />
TWJ030CA00A 1 32 3 /4 28 1 /4 24 5 /8<br />
7<br />
/8<br />
3<br />
/8<br />
(832) (718) (625) (22.2) (9.53)<br />
TWJ036CA00A 2 37 32 7 /8 28 3 /4<br />
7<br />
/8<br />
3<br />
/8<br />
(940) (835) (730) (22.2) (9.53)<br />
TWA030CD00A 1 32 3 /4 28 1 /4 24 5 /8<br />
7<br />
/8<br />
3<br />
/8<br />
(832) (718) (625) (22.2) (9.53)<br />
TWA040CD00A 2 32 3 /4 32 7 /8 28 3 /4 1 1 /8<br />
3<br />
/8<br />
(832) (835) (730) (28.6) (9.53)<br />
TWA050CD00A 2 37 38 7 /8 34 3 /4 1 1 /8<br />
3<br />
/8<br />
(940) (987) (883) (28.6) (9.53)<br />
TWA060CD00A 2 44 3 /4 38 7 /8 34 3 /4 1 1 /8<br />
3<br />
/8<br />
(1137) (987) (883) (28.6) (9.53)<br />
From Dwg. 21D147562 Rev. 6<br />
30 TWE5-PRC001-EN-10-15-99
Convertibility<br />
TWE030 Through 050 Convertibility<br />
Six (6) Way Convertibility<br />
One Unit - 4 Applications<br />
Easy Conversion to Opposite Side Access<br />
TWE5-PRC001-EN-10-15-99 31
Mechanical<br />
Specification Options<br />
General<br />
Blower coil units shall be completely<br />
factory assembled including coil, condensate<br />
drain pan, fan, motor, filters and<br />
controls in an insulated casing that can<br />
be applied in horizontal or vertical<br />
configuration.<br />
This new line of TWE-C air handlers<br />
provides exclusive compact size combined<br />
with simple four-way convertibility<br />
in three sizes. The unit ships in the right<br />
hand horizontal configuration and<br />
converts to vertical upflow just by<br />
standing the unit on end. No tools<br />
required. Simple coil rotation provides<br />
downflow and horizontal left applications.<br />
The four-way convertibility provides you<br />
inventory benefits and service/installation<br />
flexibility. The simple conversion provides<br />
opposite side access for installation and<br />
service.<br />
Casing<br />
Units shall have rugged sheet metal and<br />
steel frame construction and shall be<br />
painted with an enamel finish. Casing<br />
shall be insulated and knockouts shall be<br />
provided for electrical power and control<br />
wiring.<br />
Refrigerant Circuits<br />
The TWE units shall have a single<br />
refrigerant circuit. TWE03-040C refrigerant<br />
circuit shall be controlled by a flow<br />
control check valve (FCCV). The<br />
TWE050C refrigerant circuit shall be<br />
controlled by a factory-installed thermal<br />
expansion valve.<br />
Coil<br />
Aluminum fin surface shall be mechanically<br />
bonded to 3/8-inch OD copper<br />
tubing. Coils shall be factory pressure<br />
and leak tested.<br />
Fan<br />
Forward curved, dynamically and<br />
statically balanced with three-speed<br />
direct drive shall be standard, fan motor<br />
bearing shall be permanently lubricated.<br />
Controls<br />
Fan contactor, and plug-in module for<br />
accessory electric heat control shall be<br />
included. TWE models shall also include<br />
check valves.<br />
Filters<br />
Filters shall be included as standard.<br />
Accessories<br />
Electric Heaters — Shall be available in<br />
a wide range of capacities and voltages<br />
with various staging options and plug in<br />
control wiring. Heaters shall fit inside<br />
internal compartment.<br />
The <strong>Trane</strong> Company<br />
<strong>Trane</strong> International Unitary Systems<br />
1789 Chaussée de Wavre<br />
1160 Brussels<br />
Belgium<br />
www.trane.com<br />
An American Standard Company<br />
File Number<br />
Supersedes<br />
Stocking Location<br />
TWE5-PRC001-EN-10-15-99<br />
TWE5-PRC000-EN<br />
P.I.-L<br />
Since The <strong>Trane</strong> Company has a policy of continuous product improvement, it reserves the right to change<br />
design and specifications without notice.<br />
P.I.