Applications Guide Tracer Graphical Programming - Trane

Applications Guide Tracer Graphical Programming - Trane Applications Guide Tracer Graphical Programming - Trane

28.09.2014 Views

® Chapter 4 Cooling tower with two-speed fan example Figure 80: Deadbands used to control fan speed Use a Math block to incorporate this functionality. Math blocks perform standard math operations and functions. Specifically, use an Add block to adjust the setpoint value by adding 5.0°F. The result of the addition serves as the setpoint input to the Deadband block. To transition the fan based on supply temp: 1. Place a Deadband block in the design space and set it as Greater Than. 2. From the Blocks menu, choose Math. From the Math menu, choose Add. 3. Click in the design space to place an Add block. 4. Place a Constant block in the design space and assign the value 5.0 to it. 5. Connect the SupplyTemp wireless read block to the Input port of the Deadband block. 6. Connect the Supply Temp Setpoint variable block and the 5.0 constant block to the Add block. 7. Connect the Add block to the Setpoint port of the Deadband block. 8. Place a Constant block in the design space and assign the value 2.5 to it. 9. Connect the 2.5 constant block to the Deadband port of the Deadband block (Figure 81 on page 75). 74 CNT-APG001-EN

® Writing the cooling tower fan module Figure 81: Adding the fan at high speed Transitioning the fan based on time To implement the time delay, use the Delay on Start block. The on/off control input of the Delay on Start block comes from the output of the And block. The delay countdown begins when the fan starts at low speed. Use another And block to ensure that both of the previously mentioned criteria apply to control of the binary output, Fan High. To transition the fan based on time: 1. Place a Delay on Start block in the design space and assign its units to seconds. 2. Place a Constant block in the design space and assign the value 30.0 to it. 3. Place another And block in the design space. 4. Connect the first And block to the On/Off Control port of the Delay on Start block. 5. Connect the 30.0 constant block to the Delay port of the Delay on Start block. 6. Connect the Delay on Start block and the second Deadband block to the second And block. 7. Connect the second And block to the Fan High output block. CNT-APG001-EN 75

®<br />

Chapter 4 Cooling tower with two-speed fan example<br />

Figure 80: Deadbands used to control fan speed<br />

Use a Math block to incorporate this functionality. Math blocks perform<br />

standard math operations and functions. Specifically, use an Add block to<br />

adjust the setpoint value by adding 5.0°F. The result of the addition<br />

serves as the setpoint input to the Deadband block.<br />

To transition the fan based on supply temp:<br />

1. Place a Deadband block in the design space and set it as Greater<br />

Than.<br />

2. From the Blocks menu, choose Math. From the Math menu, choose<br />

Add.<br />

3. Click in the design space to place an Add block.<br />

4. Place a Constant block in the design space and assign the value 5.0 to<br />

it.<br />

5. Connect the SupplyTemp wireless read block to the Input port of the<br />

Deadband block.<br />

6. Connect the Supply Temp Setpoint variable block and the 5.0 constant<br />

block to the Add block.<br />

7. Connect the Add block to the Setpoint port of the Deadband block.<br />

8. Place a Constant block in the design space and assign the value 2.5 to<br />

it.<br />

9. Connect the 2.5 constant block to the Deadband port of the Deadband<br />

block (Figure 81 on page 75).<br />

74 CNT-APG001-EN

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!