Applications Guide Tracer Graphical Programming - Trane
Applications Guide Tracer Graphical Programming - Trane Applications Guide Tracer Graphical Programming - Trane
® Chapter 4 Cooling tower with two-speed fan example Figure 80: Deadbands used to control fan speed Use a Math block to incorporate this functionality. Math blocks perform standard math operations and functions. Specifically, use an Add block to adjust the setpoint value by adding 5.0°F. The result of the addition serves as the setpoint input to the Deadband block. To transition the fan based on supply temp: 1. Place a Deadband block in the design space and set it as Greater Than. 2. From the Blocks menu, choose Math. From the Math menu, choose Add. 3. Click in the design space to place an Add block. 4. Place a Constant block in the design space and assign the value 5.0 to it. 5. Connect the SupplyTemp wireless read block to the Input port of the Deadband block. 6. Connect the Supply Temp Setpoint variable block and the 5.0 constant block to the Add block. 7. Connect the Add block to the Setpoint port of the Deadband block. 8. Place a Constant block in the design space and assign the value 2.5 to it. 9. Connect the 2.5 constant block to the Deadband port of the Deadband block (Figure 81 on page 75). 74 CNT-APG001-EN
® Writing the cooling tower fan module Figure 81: Adding the fan at high speed Transitioning the fan based on time To implement the time delay, use the Delay on Start block. The on/off control input of the Delay on Start block comes from the output of the And block. The delay countdown begins when the fan starts at low speed. Use another And block to ensure that both of the previously mentioned criteria apply to control of the binary output, Fan High. To transition the fan based on time: 1. Place a Delay on Start block in the design space and assign its units to seconds. 2. Place a Constant block in the design space and assign the value 30.0 to it. 3. Place another And block in the design space. 4. Connect the first And block to the On/Off Control port of the Delay on Start block. 5. Connect the 30.0 constant block to the Delay port of the Delay on Start block. 6. Connect the Delay on Start block and the second Deadband block to the second And block. 7. Connect the second And block to the Fan High output block. CNT-APG001-EN 75
- Page 48 and 49: ® Chapter 2 Writing the exhaust fa
- Page 50 and 51: ® Chapter 2 Writing the exhaust fa
- Page 52 and 53: ® Chapter 2 Writing the exhaust fa
- Page 54 and 55: ® Chapter 3 Modifying the exhaust
- Page 56 and 57: ® Chapter 3 Modifying the exhaust
- Page 58 and 59: ® Chapter 3 Modifying the exhaust
- Page 60 and 61: ® Chapter 3 Modifying the exhaust
- Page 62 and 63: ® Chapter 3 Modifying the exhaust
- Page 64 and 65: ® Chapter 3 Modifying the exhaust
- Page 66 and 67: ® Chapter 3 Modifying the exhaust
- Page 68 and 69: ® Chapter 3 Modifying the exhaust
- Page 70 and 71: ® Chapter 3 Modifying the exhaust
- Page 72 and 73: ® Chapter 4 Cooling tower with two
- Page 74 and 75: ® Chapter 4 Cooling tower with two
- Page 76 and 77: ® Chapter 4 Cooling tower with two
- Page 78 and 79: ® Chapter 4 Cooling tower with two
- Page 80 and 81: ® Chapter 4 Cooling tower with two
- Page 82 and 83: ® Chapter 4 Cooling tower with two
- Page 84 and 85: ® Chapter 4 Cooling tower with two
- Page 86 and 87: ® Chapter 4 Cooling tower with two
- Page 88 and 89: ® Chapter 4 Cooling tower with two
- Page 90 and 91: ® Chapter 4 Cooling tower with two
- Page 92 and 93: ® Chapter 4 Cooling tower with two
- Page 94 and 95: ® Chapter 4 Cooling tower with two
- Page 96 and 97: ® Chapter 4 Cooling tower with two
- Page 100 and 101: ® Chapter 4 Cooling tower with two
- Page 102 and 103: ® Chapter 4 Cooling tower with two
- Page 104 and 105: ® Chapter 5 Cooling tower with var
- Page 106 and 107: ® Chapter 5 Cooling tower with var
- Page 108 and 109: ® Chapter 5 Cooling tower with var
- Page 110 and 111: ® Chapter 5 Cooling tower with var
- Page 112 and 113: ® Chapter 5 Cooling tower with var
- Page 114 and 115: ® Chapter 5 Cooling tower with var
- Page 116 and 117: ® Chapter 5 Cooling tower with var
- Page 118 and 119: ® Chapter 5 Cooling tower with var
- Page 120 and 121: ® Chapter 5 Cooling tower with var
- Page 122 and 123: ® Chapter 5 Cooling tower with var
- Page 124 and 125: ® Chapter 5 Cooling tower with var
- Page 126 and 127: ® Chapter 5 Cooling tower with var
- Page 128 and 129: ® Chapter 5 Cooling tower with var
- Page 130 and 131: ® Chapter 6 VAV AHU example Review
- Page 132 and 133: ® Chapter 6 VAV AHU example contro
- Page 134 and 135: ® Chapter 6 VAV AHU example Table
- Page 136 and 137: ® Chapter 6 VAV AHU example Figure
- Page 138 and 139: ® Chapter 6 VAV AHU example Figure
- Page 140 and 141: ® Chapter 6 VAV AHU example Figure
- Page 142 and 143: ® Chapter 6 VAV AHU example Figure
- Page 144 and 145: ® Chapter 6 VAV AHU example Figure
- Page 146 and 147: ® Chapter 6 VAV AHU example Figure
®<br />
Chapter 4 Cooling tower with two-speed fan example<br />
Figure 80: Deadbands used to control fan speed<br />
Use a Math block to incorporate this functionality. Math blocks perform<br />
standard math operations and functions. Specifically, use an Add block to<br />
adjust the setpoint value by adding 5.0°F. The result of the addition<br />
serves as the setpoint input to the Deadband block.<br />
To transition the fan based on supply temp:<br />
1. Place a Deadband block in the design space and set it as Greater<br />
Than.<br />
2. From the Blocks menu, choose Math. From the Math menu, choose<br />
Add.<br />
3. Click in the design space to place an Add block.<br />
4. Place a Constant block in the design space and assign the value 5.0 to<br />
it.<br />
5. Connect the SupplyTemp wireless read block to the Input port of the<br />
Deadband block.<br />
6. Connect the Supply Temp Setpoint variable block and the 5.0 constant<br />
block to the Add block.<br />
7. Connect the Add block to the Setpoint port of the Deadband block.<br />
8. Place a Constant block in the design space and assign the value 2.5 to<br />
it.<br />
9. Connect the 2.5 constant block to the Deadband port of the Deadband<br />
block (Figure 81 on page 75).<br />
74 CNT-APG001-EN