Applications Guide Tracer Graphical Programming - Trane
Applications Guide Tracer Graphical Programming - Trane Applications Guide Tracer Graphical Programming - Trane
® Chapter 4 Cooling tower with two-speed fan example Figure 70: Using Wireless connection block 9. Under Block, click the Read (Use) option to use a Wireless connection block. 10. Under Use, in the Name list, click SumpTemp. 11. Click OK. The Wireless read block appears in the design space (Figure 71). Figure 71: Wireless read Adding the other input blocks Add the remaining input blocks needed for the sump heater module. To add the input blocks: 1. Place a Variable block in the design space and assign the analog variable Sump Heater Setpoint (sourced from the operator display/service tool) to it. 2. In the alarms module, create a Wireless write block, name it OutdoorAirTemp, and connect it to the Outdoor Air Temp input block. 3. Place a Constant block in the design space and assign the value 2.0 to it to represent a 2.0°F deadband. 4. Place another Constant block in the design space and assign the value32.0toittorepresentthefreezingpoint(Figure72onpage69). 68 CNT-APG001-EN
® Writing the sump heater module Figure 72: Input blocks for sump heater module Figure 73: Output block for sump heater module Adding the output block ◆ Place an Output (Hardware) block in the design space and assign the binary output, Sump Heater, to it as shown in Figure 73. Controlling the sump heater under normal conditions Use the Deadband block to control the sump heater under normal conditions. To control the sump heater under normal conditions: 1. Place a Deadband block in the design space and set it to assume heating. Chooseassumeheatingbecauseyouwanttheheatertocomeonifthe Sump Temp falls below the Sump Heater Setpoint (40°F). You want the heater to stay on until the Sump Temp rises to the Sump Heater Setpoint plus the deadband constant (2.0°F). 2. Connect the SumpTemp wireless read block to the Input port of the Deadband block. 3. Connect the Sump Heater Setpoint variable block to the Setpoint port of the Deadband block. CNT-APG001-EN 69
- Page 42 and 43: ® Chapter 2 Writing the exhaust fa
- Page 44 and 45: ® Chapter 2 Writing the exhaust fa
- Page 46 and 47: ® Chapter 2 Writing the exhaust fa
- Page 48 and 49: ® Chapter 2 Writing the exhaust fa
- Page 50 and 51: ® Chapter 2 Writing the exhaust fa
- Page 52 and 53: ® Chapter 2 Writing the exhaust fa
- Page 54 and 55: ® Chapter 3 Modifying the exhaust
- Page 56 and 57: ® Chapter 3 Modifying the exhaust
- Page 58 and 59: ® Chapter 3 Modifying the exhaust
- Page 60 and 61: ® Chapter 3 Modifying the exhaust
- Page 62 and 63: ® Chapter 3 Modifying the exhaust
- Page 64 and 65: ® Chapter 3 Modifying the exhaust
- Page 66 and 67: ® Chapter 3 Modifying the exhaust
- Page 68 and 69: ® Chapter 3 Modifying the exhaust
- Page 70 and 71: ® Chapter 3 Modifying the exhaust
- Page 72 and 73: ® Chapter 4 Cooling tower with two
- Page 74 and 75: ® Chapter 4 Cooling tower with two
- Page 76 and 77: ® Chapter 4 Cooling tower with two
- Page 78 and 79: ® Chapter 4 Cooling tower with two
- Page 80 and 81: ® Chapter 4 Cooling tower with two
- Page 82 and 83: ® Chapter 4 Cooling tower with two
- Page 84 and 85: ® Chapter 4 Cooling tower with two
- Page 86 and 87: ® Chapter 4 Cooling tower with two
- Page 88 and 89: ® Chapter 4 Cooling tower with two
- Page 90 and 91: ® Chapter 4 Cooling tower with two
- Page 94 and 95: ® Chapter 4 Cooling tower with two
- Page 96 and 97: ® Chapter 4 Cooling tower with two
- Page 98 and 99: ® Chapter 4 Cooling tower with two
- Page 100 and 101: ® Chapter 4 Cooling tower with two
- Page 102 and 103: ® Chapter 4 Cooling tower with two
- Page 104 and 105: ® Chapter 5 Cooling tower with var
- Page 106 and 107: ® Chapter 5 Cooling tower with var
- Page 108 and 109: ® Chapter 5 Cooling tower with var
- Page 110 and 111: ® Chapter 5 Cooling tower with var
- Page 112 and 113: ® Chapter 5 Cooling tower with var
- Page 114 and 115: ® Chapter 5 Cooling tower with var
- Page 116 and 117: ® Chapter 5 Cooling tower with var
- Page 118 and 119: ® Chapter 5 Cooling tower with var
- Page 120 and 121: ® Chapter 5 Cooling tower with var
- Page 122 and 123: ® Chapter 5 Cooling tower with var
- Page 124 and 125: ® Chapter 5 Cooling tower with var
- Page 126 and 127: ® Chapter 5 Cooling tower with var
- Page 128 and 129: ® Chapter 5 Cooling tower with var
- Page 130 and 131: ® Chapter 6 VAV AHU example Review
- Page 132 and 133: ® Chapter 6 VAV AHU example contro
- Page 134 and 135: ® Chapter 6 VAV AHU example Table
- Page 136 and 137: ® Chapter 6 VAV AHU example Figure
- Page 138 and 139: ® Chapter 6 VAV AHU example Figure
- Page 140 and 141: ® Chapter 6 VAV AHU example Figure
®<br />
Writing the sump heater module<br />
Figure 72: Input blocks for sump heater module<br />
Figure 73: Output block for sump heater module<br />
Adding the output block<br />
◆<br />
Place an Output (Hardware) block in the design space and assign the<br />
binary output, Sump Heater, to it as shown in Figure 73.<br />
Controlling the sump heater under normal conditions<br />
Use the Deadband block to control the sump heater under normal conditions.<br />
To control the sump heater under normal conditions:<br />
1. Place a Deadband block in the design space and set it to assume heating.<br />
Chooseassumeheatingbecauseyouwanttheheatertocomeonifthe<br />
Sump Temp falls below the Sump Heater Setpoint (40°F). You want<br />
the heater to stay on until the Sump Temp rises to the Sump Heater<br />
Setpoint plus the deadband constant (2.0°F).<br />
2. Connect the SumpTemp wireless read block to the Input port of the<br />
Deadband block.<br />
3. Connect the Sump Heater Setpoint variable block to the Setpoint port<br />
of the Deadband block.<br />
CNT-APG001-EN 69