Applications Guide Tracer Graphical Programming - Trane
Applications Guide Tracer Graphical Programming - Trane Applications Guide Tracer Graphical Programming - Trane
® Chapter 4 Cooling tower with two-speed fan example Writing the sump heater module Take another look at the part of the sequence of operation dealing with control of the sump heater. Cycle the sump heater if the sump temperature falls below 40°F (this value is adjustable at the operator display). If the outdoor air temperature falls below 32°F, turn on the sump heater continuously. The programming elements required to accomplish this task, including the following: • Use a deadband to cycle the sump heater under normal operating conditions. A deadband prevents excessive heater cycling. • Use a comparison to keep the sump heater on continuously when the outdoor air temperature is below the freezing point. Adding the input blocks Begin by adding blocks to represent the inputs to this part of the program. Adding wireless connections YouusedSumpTempandOutdoorAirTempinthealarmsmodule. Instead of adding these blocks again or trying to connect to them from another module, use wireless connections. ➤ Connecting blocks using wireless connections Use wireless connections to pass data from block to block when wired connections are impractical. In general, it is good programming practice to use an input in a program only once. By doing so, you will have an easier time debugging your program. By using the wireless connection, you can also prevent long and overlapping wired connections that are difficult to follow. First create a wireless connection for the Sump Temp input. To add a wireless connection: 1. From the Blocks menu, choose Wireless. The cursor changes to a cross-hair (✛) inthedesignspace. 2. Click in the design space to place a Wireless block. The Wireless Connection Properties dialog box appears (Figure 68 on page 67). 66 CNT-APG001-EN
® Writing the sump heater module Figure 68: Creating Wireless connection block 3. Under Block, click the Write (Create) option to create a Wireless connection block. 4. Under Create, click the Analog option to create an analog connection. 5. In the Name field, type: SumpTemp The name may be up to 16 characters in length. Spaces are not allowed. 6. Click OK. The Wireless write block appears in the design space. 7. Connect the Wireless write block with a wired connection to the Sump Temp input block (Figure 69). Figure 69: Wireless write connection 8. From the Blocks menu, choose Wireless. and click in the design space to place a Wireless block. The Wireless Connection Properties dialog box appears (Figure 70 on page 68). CNT-APG001-EN 67
- Page 40 and 41: ® Chapter 2 Writing the exhaust fa
- Page 42 and 43: ® Chapter 2 Writing the exhaust fa
- Page 44 and 45: ® Chapter 2 Writing the exhaust fa
- Page 46 and 47: ® Chapter 2 Writing the exhaust fa
- Page 48 and 49: ® Chapter 2 Writing the exhaust fa
- Page 50 and 51: ® Chapter 2 Writing the exhaust fa
- Page 52 and 53: ® Chapter 2 Writing the exhaust fa
- Page 54 and 55: ® Chapter 3 Modifying the exhaust
- Page 56 and 57: ® Chapter 3 Modifying the exhaust
- Page 58 and 59: ® Chapter 3 Modifying the exhaust
- Page 60 and 61: ® Chapter 3 Modifying the exhaust
- Page 62 and 63: ® Chapter 3 Modifying the exhaust
- Page 64 and 65: ® Chapter 3 Modifying the exhaust
- Page 66 and 67: ® Chapter 3 Modifying the exhaust
- Page 68 and 69: ® Chapter 3 Modifying the exhaust
- Page 70 and 71: ® Chapter 3 Modifying the exhaust
- Page 72 and 73: ® Chapter 4 Cooling tower with two
- Page 74 and 75: ® Chapter 4 Cooling tower with two
- Page 76 and 77: ® Chapter 4 Cooling tower with two
- Page 78 and 79: ® Chapter 4 Cooling tower with two
- Page 80 and 81: ® Chapter 4 Cooling tower with two
- Page 82 and 83: ® Chapter 4 Cooling tower with two
- Page 84 and 85: ® Chapter 4 Cooling tower with two
- Page 86 and 87: ® Chapter 4 Cooling tower with two
- Page 88 and 89: ® Chapter 4 Cooling tower with two
- Page 92 and 93: ® Chapter 4 Cooling tower with two
- Page 94 and 95: ® Chapter 4 Cooling tower with two
- Page 96 and 97: ® Chapter 4 Cooling tower with two
- Page 98 and 99: ® Chapter 4 Cooling tower with two
- Page 100 and 101: ® Chapter 4 Cooling tower with two
- Page 102 and 103: ® Chapter 4 Cooling tower with two
- Page 104 and 105: ® Chapter 5 Cooling tower with var
- Page 106 and 107: ® Chapter 5 Cooling tower with var
- Page 108 and 109: ® Chapter 5 Cooling tower with var
- Page 110 and 111: ® Chapter 5 Cooling tower with var
- Page 112 and 113: ® Chapter 5 Cooling tower with var
- Page 114 and 115: ® Chapter 5 Cooling tower with var
- Page 116 and 117: ® Chapter 5 Cooling tower with var
- Page 118 and 119: ® Chapter 5 Cooling tower with var
- Page 120 and 121: ® Chapter 5 Cooling tower with var
- Page 122 and 123: ® Chapter 5 Cooling tower with var
- Page 124 and 125: ® Chapter 5 Cooling tower with var
- Page 126 and 127: ® Chapter 5 Cooling tower with var
- Page 128 and 129: ® Chapter 5 Cooling tower with var
- Page 130 and 131: ® Chapter 6 VAV AHU example Review
- Page 132 and 133: ® Chapter 6 VAV AHU example contro
- Page 134 and 135: ® Chapter 6 VAV AHU example Table
- Page 136 and 137: ® Chapter 6 VAV AHU example Figure
- Page 138 and 139: ® Chapter 6 VAV AHU example Figure
®<br />
Chapter 4 Cooling tower with two-speed fan example<br />
Writing the sump heater module<br />
Take another look at the part of the sequence of operation dealing with<br />
control of the sump heater.<br />
Cycle the sump heater if the sump temperature falls below 40°F (this<br />
value is adjustable at the operator display). If the outdoor air temperature<br />
falls below 32°F, turn on the sump heater continuously.<br />
The programming elements required to accomplish this task, including<br />
the following:<br />
• Use a deadband to cycle the sump heater under normal operating conditions.<br />
A deadband prevents excessive heater cycling.<br />
• Use a comparison to keep the sump heater on continuously when the<br />
outdoor air temperature is below the freezing point.<br />
Adding the input blocks<br />
Begin by adding blocks to represent the inputs to this part of the program.<br />
Adding wireless connections<br />
YouusedSumpTempandOutdoorAirTempinthealarmsmodule.<br />
Instead of adding these blocks again or trying to connect to them from<br />
another module, use wireless connections.<br />
➤ Connecting blocks using wireless connections<br />
Use wireless connections to pass data from block to block when wired<br />
connections are impractical. In general, it is good programming practice<br />
to use an input in a program only once. By doing so, you will have<br />
an easier time debugging your program. By using the wireless connection,<br />
you can also prevent long and overlapping wired connections<br />
that are difficult to follow.<br />
First create a wireless connection for the Sump Temp input.<br />
To add a wireless connection:<br />
1. From the Blocks menu, choose Wireless. The cursor changes to a<br />
cross-hair (✛) inthedesignspace.<br />
2. Click in the design space to place a Wireless block. The Wireless Connection<br />
Properties dialog box appears (Figure 68 on page 67).<br />
66 CNT-APG001-EN