Applications Guide Tracer Graphical Programming - Trane
Applications Guide Tracer Graphical Programming - Trane Applications Guide Tracer Graphical Programming - Trane
® Chapter 4 Cooling tower with two-speed fan example Determining a programming approach Dividing the sequence of operation into logical program modules makes programming easier. In a single program, you can write several program modules. This sequence can be subdivided into the following four modules: • Alarms • Sump heater • Cooling tower fan • Condenser water pump (Assume for this chapter that the chiller does this.) Programming tip: When possible, subdivide graphical programs according to the sequence of operation. Doing so makes the program easier to read and understand. Setting the program properties Set the program properties as shown in Figure 49 on page 53. Set the program run frequency to 30 seconds, which is appropriate for this cooling tower application. 52 CNT-APG001-EN
® Writing the alarms module Figure 49: Cooling tower with two-speed fan drive program properties Writing the alarms module Start by compiling the alarms requirements from the various parts of the sequence of operation, including the following: • If the condenser water pump fails, indicate a general alarm. A user must be able to reset the alarm at the operator display. • If the sump temperature remains below 36°F (this value is adjustable at the operator display) for 15 minutes, or if the sump temperature falls below 32°F, indicate an alarm at the operator display and turn on the Alarm output. • Indicate an alarm when any temperature sensor fails. These temperatures include Sump Temp, Supply Temp, and the Outdoor Air Temp inputs. • Alarms must be resettable at the operator display. Note the following important points and questions about the alarm control requirements: • The pump failure is determined by another part of the program. The alarms module merely uses the result. CNT-APG001-EN 53
- Page 26 and 27: ® Chapter 1 Using the Tracer Graph
- Page 28 and 29: ® Chapter 1 Using the Tracer Graph
- Page 30 and 31: ® Chapter 1 Using the Tracer Graph
- Page 32 and 33: ® Chapter 1 Using the Tracer Graph
- Page 34 and 35: ® Chapter 1 Using the Tracer Graph
- Page 36 and 37: ® Chapter 2 Writing the exhaust fa
- Page 38 and 39: ® Chapter 2 Writing the exhaust fa
- Page 40 and 41: ® Chapter 2 Writing the exhaust fa
- Page 42 and 43: ® Chapter 2 Writing the exhaust fa
- Page 44 and 45: ® Chapter 2 Writing the exhaust fa
- Page 46 and 47: ® Chapter 2 Writing the exhaust fa
- Page 48 and 49: ® Chapter 2 Writing the exhaust fa
- Page 50 and 51: ® Chapter 2 Writing the exhaust fa
- Page 52 and 53: ® Chapter 2 Writing the exhaust fa
- Page 54 and 55: ® Chapter 3 Modifying the exhaust
- Page 56 and 57: ® Chapter 3 Modifying the exhaust
- Page 58 and 59: ® Chapter 3 Modifying the exhaust
- Page 60 and 61: ® Chapter 3 Modifying the exhaust
- Page 62 and 63: ® Chapter 3 Modifying the exhaust
- Page 64 and 65: ® Chapter 3 Modifying the exhaust
- Page 66 and 67: ® Chapter 3 Modifying the exhaust
- Page 68 and 69: ® Chapter 3 Modifying the exhaust
- Page 70 and 71: ® Chapter 3 Modifying the exhaust
- Page 72 and 73: ® Chapter 4 Cooling tower with two
- Page 74 and 75: ® Chapter 4 Cooling tower with two
- Page 78 and 79: ® Chapter 4 Cooling tower with two
- Page 80 and 81: ® Chapter 4 Cooling tower with two
- Page 82 and 83: ® Chapter 4 Cooling tower with two
- Page 84 and 85: ® Chapter 4 Cooling tower with two
- Page 86 and 87: ® Chapter 4 Cooling tower with two
- Page 88 and 89: ® Chapter 4 Cooling tower with two
- Page 90 and 91: ® Chapter 4 Cooling tower with two
- Page 92 and 93: ® Chapter 4 Cooling tower with two
- Page 94 and 95: ® Chapter 4 Cooling tower with two
- Page 96 and 97: ® Chapter 4 Cooling tower with two
- Page 98 and 99: ® Chapter 4 Cooling tower with two
- Page 100 and 101: ® Chapter 4 Cooling tower with two
- Page 102 and 103: ® Chapter 4 Cooling tower with two
- Page 104 and 105: ® Chapter 5 Cooling tower with var
- Page 106 and 107: ® Chapter 5 Cooling tower with var
- Page 108 and 109: ® Chapter 5 Cooling tower with var
- Page 110 and 111: ® Chapter 5 Cooling tower with var
- Page 112 and 113: ® Chapter 5 Cooling tower with var
- Page 114 and 115: ® Chapter 5 Cooling tower with var
- Page 116 and 117: ® Chapter 5 Cooling tower with var
- Page 118 and 119: ® Chapter 5 Cooling tower with var
- Page 120 and 121: ® Chapter 5 Cooling tower with var
- Page 122 and 123: ® Chapter 5 Cooling tower with var
- Page 124 and 125: ® Chapter 5 Cooling tower with var
®<br />
Chapter 4 Cooling tower with two-speed fan example<br />
Determining a programming approach<br />
Dividing the sequence of operation into logical program modules makes<br />
programming easier. In a single program, you can write several program<br />
modules. This sequence can be subdivided into the following four modules:<br />
• Alarms<br />
• Sump heater<br />
• Cooling tower fan<br />
• Condenser water pump (Assume for this chapter that the chiller does<br />
this.)<br />
<strong>Programming</strong> tip:<br />
When possible, subdivide graphical programs according to the<br />
sequence of operation. Doing so makes the program easier to<br />
read and understand.<br />
Setting the program properties<br />
Set the program properties as shown in Figure 49 on page 53. Set the program<br />
run frequency to 30 seconds, which is appropriate for this cooling<br />
tower application.<br />
52 CNT-APG001-EN