Applications Guide Tracer Graphical Programming - Trane
Applications Guide Tracer Graphical Programming - Trane Applications Guide Tracer Graphical Programming - Trane
® Chapter 4 Cooling tower with two-speed fan example Table 5: Cooling tower with two-speed fan drive data definition (continued) Data Type Name Notes Variables Analog Supply Temp Setpoint Source set to operator display/service tool Sump Heater Setpoint Source set to operator display/service tool Sump Alarm Setpoint Source set to operator display/service tool Binary Pump Fail Source set to program Alarm Reset Source set to operator display/service tool and program* * The binary variable, Alarm Reset, is sourced from both the operator display/service tool and the program. This allows the user to turn on the Alarm Reset variable, and once the alarm is reset, the program turns the Alarm Reset variable off. Before you write the program, configure these inputs, outputs, and variables in your Tracer MP580/581 controller. Then open the TGP editor. 50 CNT-APG001-EN
® Reviewing the sequence of operation Figure 48: Cooling tower with two-speed fan drive wiring diagram CNT-APG001-EN 51
- Page 24 and 25: ® Tables Chapter7 Constant-volumeA
- Page 26 and 27: ® Chapter 1 Using the Tracer Graph
- Page 28 and 29: ® Chapter 1 Using the Tracer Graph
- Page 30 and 31: ® Chapter 1 Using the Tracer Graph
- Page 32 and 33: ® Chapter 1 Using the Tracer Graph
- Page 34 and 35: ® Chapter 1 Using the Tracer Graph
- Page 36 and 37: ® Chapter 2 Writing the exhaust fa
- Page 38 and 39: ® Chapter 2 Writing the exhaust fa
- Page 40 and 41: ® Chapter 2 Writing the exhaust fa
- Page 42 and 43: ® Chapter 2 Writing the exhaust fa
- Page 44 and 45: ® Chapter 2 Writing the exhaust fa
- Page 46 and 47: ® Chapter 2 Writing the exhaust fa
- Page 48 and 49: ® Chapter 2 Writing the exhaust fa
- Page 50 and 51: ® Chapter 2 Writing the exhaust fa
- Page 52 and 53: ® Chapter 2 Writing the exhaust fa
- Page 54 and 55: ® Chapter 3 Modifying the exhaust
- Page 56 and 57: ® Chapter 3 Modifying the exhaust
- Page 58 and 59: ® Chapter 3 Modifying the exhaust
- Page 60 and 61: ® Chapter 3 Modifying the exhaust
- Page 62 and 63: ® Chapter 3 Modifying the exhaust
- Page 64 and 65: ® Chapter 3 Modifying the exhaust
- Page 66 and 67: ® Chapter 3 Modifying the exhaust
- Page 68 and 69: ® Chapter 3 Modifying the exhaust
- Page 70 and 71: ® Chapter 3 Modifying the exhaust
- Page 72 and 73: ® Chapter 4 Cooling tower with two
- Page 76 and 77: ® Chapter 4 Cooling tower with two
- Page 78 and 79: ® Chapter 4 Cooling tower with two
- Page 80 and 81: ® Chapter 4 Cooling tower with two
- Page 82 and 83: ® Chapter 4 Cooling tower with two
- Page 84 and 85: ® Chapter 4 Cooling tower with two
- Page 86 and 87: ® Chapter 4 Cooling tower with two
- Page 88 and 89: ® Chapter 4 Cooling tower with two
- Page 90 and 91: ® Chapter 4 Cooling tower with two
- Page 92 and 93: ® Chapter 4 Cooling tower with two
- Page 94 and 95: ® Chapter 4 Cooling tower with two
- Page 96 and 97: ® Chapter 4 Cooling tower with two
- Page 98 and 99: ® Chapter 4 Cooling tower with two
- Page 100 and 101: ® Chapter 4 Cooling tower with two
- Page 102 and 103: ® Chapter 4 Cooling tower with two
- Page 104 and 105: ® Chapter 5 Cooling tower with var
- Page 106 and 107: ® Chapter 5 Cooling tower with var
- Page 108 and 109: ® Chapter 5 Cooling tower with var
- Page 110 and 111: ® Chapter 5 Cooling tower with var
- Page 112 and 113: ® Chapter 5 Cooling tower with var
- Page 114 and 115: ® Chapter 5 Cooling tower with var
- Page 116 and 117: ® Chapter 5 Cooling tower with var
- Page 118 and 119: ® Chapter 5 Cooling tower with var
- Page 120 and 121: ® Chapter 5 Cooling tower with var
- Page 122 and 123: ® Chapter 5 Cooling tower with var
®<br />
Chapter 4 Cooling tower with two-speed fan example<br />
Table 5: Cooling tower with two-speed fan drive data definition (continued)<br />
Data Type Name Notes<br />
Variables Analog Supply Temp Setpoint Source set to operator display/service tool<br />
Sump Heater Setpoint Source set to operator display/service tool<br />
Sump Alarm Setpoint Source set to operator display/service tool<br />
Binary Pump Fail Source set to program<br />
Alarm Reset<br />
Source set to operator display/service tool and program*<br />
* The binary variable, Alarm Reset, is sourced from both the operator display/service tool and the program. This allows the user<br />
to turn on the Alarm Reset variable, and once the alarm is reset, the program turns the Alarm Reset variable off.<br />
Before you write the program, configure these inputs, outputs, and variables<br />
in your <strong>Tracer</strong> MP580/581 controller. Then open the TGP editor.<br />
50 CNT-APG001-EN