Chapter 3 Modifying the exhaust fan program<br />

Figure 39: Program with Fail block<br />

Figure 40: Programwithswitchblock<br />

Using a Switch block<br />

The sequence requires that the fan be on when the input is failed. The<br />

mechanism, known as the Switch block, provides the ability to choose<br />

between two data paths based on a controlling binary value. See the block<br />

reference in the online Help for more information about the Switch block.<br />

Adding a Switch block<br />

1. Move the Equip Rm Temp Setpoint variable, the 5.0 constant, and the<br />

Deadband blocks down.<br />

2. Move the Equip Rm Alarm variable and Equip Rm Fan On/Off output<br />

blocks to the right to make room for the Switch block.<br />

3. Delete the connection between the Deadband block and the Equip Rm<br />

Fan On/Off output block.<br />

4. From the Blocks menu, choose Function. From the Function menu,<br />

choose Switch.<br />

5. ClickinthedesignspacetoaddaSwitchblock(Figure40).<br />

6. Set the Switch block property to binary.<br />

Switch block<br />

38 CNT-APG001-EN