Applications Guide Tracer Graphical Programming - Trane
Applications Guide Tracer Graphical Programming - Trane Applications Guide Tracer Graphical Programming - Trane
® Chapter 3 Modifying the exhaust fan program 5. Add a comment below the Deadband block indicating its mode for documentation purposes (Figure 34). Figure 34: Program with Deadband block Deadband block Adding a variable In the first version of the Exhaust Fan program, you used a constant value as the temperature setpoint. In this scenario the operator must be able to adjust the setpoint using the operator display. Use an analog variable to incorporate this functionality. For more information on using constants and variables, see “Constants and variables” on page 19. ➤ Reading from and writing to a variable using the variable block Read and write privileges depend on the selected variable and its source. Read refers to the ability of a program to know the value of the variable. On the other hand, write refers to the ability of a program to change the value of a variable. Table 4 summarizes the rules regarding reading from and writing to variables in graphical programming. See the Tracer MP580/581 Programmable Controller Programming guide (CNT-SVP01A-EN) for more information about variables and control sources. Table 4: Variable block read or write rules for each control source Source Read Write Program X X Tracer Summit X Operator display/service tool X Operator display/service tool and program X X To add a variable: 1. Move the 85.0 constant block and the Equip Rm Temp Setpoint comment down to make space for a variable block. 2. From the Blocks menu, choose Input/Output. From the Input/Output menu, choose Variable. 34 CNT-APG001-EN
® Adding a deadband 3. Click in the design space to place the Variable block between the Equip Rm Space Temp input block and the 85.0 constant block. 4. Double-click on the block to set the properties. The Variable Properties dialog box appears (Figure 35). Figure 35: Variable Properties dialog box 5. Under Type, click the Analog option to set the variable as an analog variable. 6. Under Source, click the Operator Display/Service Tool option. 7. In the Name list, click Equip Rm Temp Setpoint. 8. Under Block, click the Read option. Because the Equip Rm Temp Setpoint variable source is the operator display/service tool, it is a read-only variable. 9. Click OK. The Variable block is assigned to the Equip Rm Temp Setpoint value (Figure 36). Figure 36: Equip Rm Temp Setpoint variable block Variable block CNT-APG001-EN 35
- Page 8 and 9: ® Contents Arrangingblocks........
- Page 10 and 11: ® Contents Chapter 5 Cooling tower
- Page 12 and 13: ® Contents Chapter7 Constant-volum
- Page 14 and 15: ® Contents Summary-question answer
- Page 16 and 17: ® Figures Chapter3 Modifyingtheexh
- Page 18 and 19: ® Figures Figure 96: Input blocks
- Page 20 and 21: ® Figures Chapter 8 Constant-volum
- Page 22 and 23: ® Figures xx CNT-APG001-EN
- Page 24 and 25: ® Tables Chapter7 Constant-volumeA
- Page 26 and 27: ® Chapter 1 Using the Tracer Graph
- Page 28 and 29: ® Chapter 1 Using the Tracer Graph
- Page 30 and 31: ® Chapter 1 Using the Tracer Graph
- Page 32 and 33: ® Chapter 1 Using the Tracer Graph
- Page 34 and 35: ® Chapter 1 Using the Tracer Graph
- Page 36 and 37: ® Chapter 2 Writing the exhaust fa
- Page 38 and 39: ® Chapter 2 Writing the exhaust fa
- Page 40 and 41: ® Chapter 2 Writing the exhaust fa
- Page 42 and 43: ® Chapter 2 Writing the exhaust fa
- Page 44 and 45: ® Chapter 2 Writing the exhaust fa
- Page 46 and 47: ® Chapter 2 Writing the exhaust fa
- Page 48 and 49: ® Chapter 2 Writing the exhaust fa
- Page 50 and 51: ® Chapter 2 Writing the exhaust fa
- Page 52 and 53: ® Chapter 2 Writing the exhaust fa
- Page 54 and 55: ® Chapter 3 Modifying the exhaust
- Page 56 and 57: ® Chapter 3 Modifying the exhaust
- Page 60 and 61: ® Chapter 3 Modifying the exhaust
- Page 62 and 63: ® Chapter 3 Modifying the exhaust
- Page 64 and 65: ® Chapter 3 Modifying the exhaust
- Page 66 and 67: ® Chapter 3 Modifying the exhaust
- Page 68 and 69: ® Chapter 3 Modifying the exhaust
- Page 70 and 71: ® Chapter 3 Modifying the exhaust
- Page 72 and 73: ® Chapter 4 Cooling tower with two
- Page 74 and 75: ® Chapter 4 Cooling tower with two
- Page 76 and 77: ® Chapter 4 Cooling tower with two
- Page 78 and 79: ® Chapter 4 Cooling tower with two
- Page 80 and 81: ® Chapter 4 Cooling tower with two
- Page 82 and 83: ® Chapter 4 Cooling tower with two
- Page 84 and 85: ® Chapter 4 Cooling tower with two
- Page 86 and 87: ® Chapter 4 Cooling tower with two
- Page 88 and 89: ® Chapter 4 Cooling tower with two
- Page 90 and 91: ® Chapter 4 Cooling tower with two
- Page 92 and 93: ® Chapter 4 Cooling tower with two
- Page 94 and 95: ® Chapter 4 Cooling tower with two
- Page 96 and 97: ® Chapter 4 Cooling tower with two
- Page 98 and 99: ® Chapter 4 Cooling tower with two
- Page 100 and 101: ® Chapter 4 Cooling tower with two
- Page 102 and 103: ® Chapter 4 Cooling tower with two
- Page 104 and 105: ® Chapter 5 Cooling tower with var
- Page 106 and 107: ® Chapter 5 Cooling tower with var
®<br />
Chapter 3 Modifying the exhaust fan program<br />
5. Add a comment below the Deadband block indicating its mode for documentation<br />
purposes (Figure 34).<br />
Figure 34: Program with Deadband block<br />
Deadband block<br />
Adding a variable<br />
In the first version of the Exhaust Fan program, you used a constant<br />
value as the temperature setpoint. In this scenario the operator must be<br />
able to adjust the setpoint using the operator display. Use an analog variable<br />
to incorporate this functionality. For more information on using constants<br />
and variables, see “Constants and variables” on page 19.<br />
➤ Reading from and writing to a variable using the variable<br />
block<br />
Read and write privileges depend on the selected variable and its<br />
source. Read refers to the ability of a program to know the value of<br />
the variable. On the other hand, write refers to the ability of a program<br />
to change the value of a variable. Table 4 summarizes the rules<br />
regarding reading from and writing to variables in graphical programming.<br />
See the <strong>Tracer</strong> MP580/581 Programmable Controller <strong>Programming</strong><br />
guide (CNT-SVP01A-EN) for more information about<br />
variables and control sources.<br />
Table 4: Variable block read or write rules for each control source<br />
Source<br />
Read<br />
Write<br />
Program X X<br />
<strong>Tracer</strong> Summit<br />
X<br />
Operator display/service tool<br />
X<br />
Operator display/service tool<br />
and program<br />
X<br />
X<br />
To add a variable:<br />
1. Move the 85.0 constant block and the Equip Rm Temp Setpoint comment<br />
down to make space for a variable block.<br />
2. From the Blocks menu, choose Input/Output. From the Input/Output<br />
menu, choose Variable.<br />
34 CNT-APG001-EN