Deleting a block<br />

Analyzing this scenario might result in Figure 30. The corresponding<br />

data definition is presented in Table 3, and a wiring diagram is presented<br />

in Figure 11 on page 14.<br />

Figure 30: Modified equipment room exhaust fan data<br />

Table 3: Modified equipment room exhaust fan data definition<br />

Data Type Name Notes<br />

Input Analog Equip Rm Space Temp Universal input configured as thermistor or<br />

RTD (Balco, Platinum)<br />

Output Binary Equip Rm Fan On/Off Set minimum on/off times to 2 minutes.<br />

Variables Analog Equip Rm Temp Setpoint Analog variable, source set to operator<br />

display/service tool<br />

Binary Equip Rm Alarm Binary variable, source set to program<br />

Before you actually start to write the program, verify that these inputs,<br />

outputs, and variables are configured in your <strong>Tracer</strong> MP580/581. For<br />

more information, see the <strong>Tracer</strong> MP580/581 Programmable Controller<br />

<strong>Programming</strong> guide (CNT-SVP01A-EN).<br />

Deleting a block<br />

In the Equip Room Exhaust Fan program, you used the Greater Than<br />

blocktocomparethespacetemperatureandthetemperaturesetpoint.<br />

Now you do not want to just compare the space temperature to the setpoint;<br />

you want to incorporate a deadband. A 5-degree deadband will<br />

keep the fan from cycling on and off as the space temperature fluctuates<br />

around 85ºF. The fan should stay on until the space temperature falls<br />

below 80ºF. Replace the Greater Than block with a Deadband block.<br />

To delete a block:<br />

1. Click on the Greater Than block. The block is outlined in yellow.<br />

CNT-APG001-EN 31