®<br />

Chapter 8, “Constant-volume AHU with warm-up, pre-cool, and communica-<br />

Figure 203: Modified manual reset alarm logic<br />

In <strong>Tracer</strong> Summit software, create a binary output to represent the<br />

alarm reset at the system level. In the <strong>Tracer</strong> MP580/581 editor, reference<br />

the desired binary variable to the newly created binary output.<br />

For instance, if the first <strong>Tracer</strong> Summit binary variable in the <strong>Tracer</strong><br />

MP580/581 controller is configured as Alarm Reset (BAS) and you<br />

created a binary output in <strong>Tracer</strong> Summit called AHU Alarm Reset,<br />

reference the binary variable to the present value of the binary output<br />

in <strong>Tracer</strong> Summit. The operator uses this binary output to turn on<br />

the alarm reset.<br />

Then write a CPL program to automatically turn the alarm reset off.<br />

The following CPL program has an execution frequency of 10 seconds<br />

and turns off the alarm reset after 1 minute, allowing sufficient time<br />

forittobecommunicatedtothe<strong>Tracer</strong>MP580/581controller.<br />