® Summary-question answers Figure 201: Cooling valve override Figure 202: Heating valve control with override Theheatingvalveworksthesameway,butthereisenoughspacein the heating valve module to add the override implementation on the same page (Figure 202). 3. To accomplish the same alarm reset functionality, you must do a combination of configuration and programming in the Tracer MP580/581 controller and at the Tracer Summit workstation. First, configure a binary variable to communicate the alarm reset value from the Tracer Summit system. One minor change is required to the alarms program. Add a binary variable to the manual reset alarm logic of the alarms program, as shown in Figure 203 on page 247. 246 CNT-APG001-EN
® Chapter 8, “Constant-volume AHU with warm-up, pre-cool, and communica- Figure 203: Modified manual reset alarm logic In Tracer Summit software, create a binary output to represent the alarm reset at the system level. In the Tracer MP580/581 editor, reference the desired binary variable to the newly created binary output. For instance, if the first Tracer Summit binary variable in the Tracer MP580/581 controller is configured as Alarm Reset (BAS) and you created a binary output in Tracer Summit called AHU Alarm Reset, reference the binary variable to the present value of the binary output in Tracer Summit. The operator uses this binary output to turn on the alarm reset. Then write a CPL program to automatically turn the alarm reset off. The following CPL program has an execution frequency of 10 seconds and turns off the alarm reset after 1 minute, allowing sufficient time forittobecommunicatedtotheTracerMP580/581controller. CNT-APG001-EN 247
- Page 220 and 221: ® Chapter 8 Constant-volume AHU wi
- Page 222 and 223: ® Chapter 8 Constant-volume AHU wi
- Page 224 and 225: ® Chapter 8 Constant-volume AHU wi
- Page 226 and 227: ® Chapter 8 Constant-volume AHU wi
- Page 228 and 229: ® Chapter 8 Constant-volume AHU wi
- Page 230 and 231: ® Chapter 8 Constant-volume AHU wi
- Page 232 and 233: ® Chapter 8 Constant-volume AHU wi
- Page 234 and 235: ® Chapter 8 Constant-volume AHU wi
- Page 236 and 237: ® Chapter 8 Constant-volume AHU wi
- Page 238 and 239: ® Chapter 8 Constant-volume AHU wi
- Page 240 and 241: ® Chapter 8 Constant-volume AHU wi
- Page 242 and 243: ® Chapter 8 Constant-volume AHU wi
- Page 244 and 245: ® Chapter 8 Constant-volume AHU wi
- Page 246 and 247: ® Chapter 8 Constant-volume AHU wi
- Page 248 and 249: ® Chapter 8 Constant-volume AHU wi
- Page 250 and 251: ® Chapter 8 Constant-volume AHU wi
- Page 252 and 253: ® Programming best practices Set t
- Page 254 and 255: ® Programming best practices Figur
- Page 256 and 257: ® Programming best practices Use c
- Page 258 and 259: ® Programming best practices 234 C
- Page 260 and 261: ® Summary-question answers Figure
- Page 262 and 263: ® Summary-question answers Figure
- Page 264 and 265: ® Summary-question answers Figure
- Page 266 and 267: ® Summary-question answers closed
- Page 268 and 269: ® Summary-question answers Figure
- Page 272 and 273: ® Summary-question answers PROGRAM
- Page 274 and 275: ® Index dehumidification, 166-169,
- Page 276: Trane An American Standard Company
®<br />
Summary-question answers<br />
Figure 201: Cooling valve override<br />
Figure 202: Heating valve control with override<br />
Theheatingvalveworksthesameway,butthereisenoughspacein<br />
the heating valve module to add the override implementation on the<br />
same page (Figure 202).<br />
3. To accomplish the same alarm reset functionality, you must do a combination<br />
of configuration and programming in the <strong>Tracer</strong> MP580/581<br />
controller and at the <strong>Tracer</strong> Summit workstation. First, configure a<br />
binary variable to communicate the alarm reset value from the<br />
<strong>Tracer</strong> Summit system. One minor change is required to the alarms<br />
program. Add a binary variable to the manual reset alarm logic of the<br />
alarms program, as shown in Figure 203 on page 247.<br />
246 CNT-APG001-EN