Chapter 8, “Constant-volume AHU with warm-up, pre-cool, and communica-<br />

Figure 200: Valve override interpretation<br />

Selected enumerations for the state, or override mode, are shown in<br />

Table 36. Remember, you are checking for values of 0, 4, or 5.<br />

Table 36: SNVT_hvac_overrid (hvac_overrid_t) enumerations<br />

Value Identifier Notes<br />

0 HVO_OFF Not overridden<br />

1 HVO_POSITION Override position—use percent field<br />

2 HVO_FLOW_VALUE Override flow in liters/second—use<br />

flow field<br />

3 HVO_FLOW_PERCENT Override flow percentage—uses<br />

percent field<br />

4 HVO_OPEN Override to position = 100%<br />

5 HVO_CLOSE Override to position = 0%<br />

6 HVO_MINIMUM Override to configured minimum<br />

7 HVO_MAXIMUM Override to configured maximum<br />

–1 HVO_NUL Invalid value<br />

Note:This table was adapted from the LonMark Standard Enumeration Master List.<br />

Figure 200 shows the logic used to interpret the valve override. The<br />

De-Enumerator block interprets the override mode. The Switch blocks<br />

select the appropriate desired valve position based on the override<br />

mode. The resulting wireless connections are used to communicate<br />

the override values to both the cooling and heating valves as shown in<br />

Figure 201 on page 246 and Figure 202 on page 246.<br />

Next,startwiththecoolingvalvemodulepicturedinFigure172on<br />

page 208. Substitute a wireless connection, CoolValve, for the cooling<br />

valve analog output. Then add another Switch block to select the<br />

source of the cooling valve control. In normal operation, the calculated<br />

cooling valve position is passed to the analog output. When an override<br />

exists, the override value is passed to the analog output<br />

(Figure 201 on page 246).<br />

CNT-APG001-EN 245