®<br />

Summary-question answers<br />

Figure 199: Adding nviEmergOverride<br />

2. As noted in the question, the valve override may be set to off, open, or<br />

closed. Although additional parts of the variable may be used to communicate<br />

a percentage or flow value, the <strong>Tracer</strong> Summit system supports<br />

use of only the first element of the structure. Here, values of 0%<br />

and 100% are assumed for override modes of closed and open, respectively<br />

(Table 35).<br />

Table 35: SNVT_hvac_overrid structure contents<br />

Element SNVT Notes<br />

State hvac_overrid_t Override mode, enumerated<br />

Percent SNVT_lev_percent From –163.83% to 163.83%<br />

Flow SNVT_lev_percent From –32,768 to 32,767<br />