Summary-question answers<br />

closed position and as a result, the calculated offset value is based on<br />

the occupied setpoints.<br />

The Occupancy and De-Enumerator block combination appears again<br />

in the fan control program (Figure 134 on page 156). The fan is<br />

requested to start in any occupancy mode with the exception of unoccupied<br />

mode.<br />

The last piece of the puzzle answers the following question: How does<br />

the Occupancy block know to indicate occupied bypass mode? For the<br />

controller to sense that it must enter occupied bypass mode, a universal<br />

input configured as a thermistor (zone sensor) must be selected as<br />

the timed override input in the Schedule application. See Figure 197<br />

on page 241.<br />

3. The network variable input providing a temperature may be checked<br />

for an invalid value using the Fail block (Figure 198).<br />

Figure 198: Checking a network variable input for valid data<br />

In some cases, a Fail block may be used to check the network variable<br />

inputs for invalid data. Table 33 shows the network variable types<br />

(SNVTs) that the Fail block checks for invalid data. You see the hexadecimal<br />

invalid values when setting up custom bindings in the Rover<br />

service tool, and you see the decimal values when debugging graphical<br />

programs in the TGP editor.<br />

Table 33: Network variable input (nvi) and network configuration input<br />

(nci) invalid values<br />

SNVT<br />

Hexadecimal<br />

Invalid state<br />

Decimal<br />

SNVT_flow 0xFFFF 65535<br />

SNVT_hvac_emerg 0xFF 255<br />

SNVT_hvac_mode 0xFF 255<br />

SNVT_hvac_overid 0xFF 255<br />

SNVT_hvac_status 0xFF 255<br />

SNVT_lev_percent 0x7FFF 32767<br />

SNVT_occupancy 0xFF 255<br />

SNVT_press_p 0x7FFF 32767<br />

SNVT_switch 0xFF 255<br />

SNVT_temp_p 0x7FFF 327.67<br />

Note: The hexadecimal invalid values appear when setting up custom<br />

bindings in the Rover service tool. The decimal values appear when<br />

debugging graphical programs in the TGP editor.<br />

242 CNT-APG001-EN