Applications Guide Tracer Graphical Programming - Trane
Applications Guide Tracer Graphical Programming - Trane Applications Guide Tracer Graphical Programming - Trane
® Summary-question answers Figure 196: Effective setpoint calculation 4. Replace the network configuration inputs, nciDAClSP and nciDAHtSP, with analog variables that are adjustable from the operator display. 240 CNT-APG001-EN
® Chapter 7, “Constant-volume AHU example” Chapter 7, “Constant-volume AHU example” 1. A universal input configured as a a binary input must be selected as the occupancy sensor input in the Schedule application. See Figure 197. Figure 197: Schedule application occupancy inputs 2. The Occupancy block, used in both the modes and setpoints program and the fan control program, provides the occupancy mode of the controller. Remember, the Occupancy block outputs one of four states, which is determined by the Schedule application for the controller: 0 = Occupied 1 = Unoccupied 2 = Occupied Bypass 3 = Occupied Standby When the controller enters occupied bypass mode, the Occupancy block outputs a value of 2. Take a closer look at the application of the Occupancy block in the modes and setpoints program (Figure 158 on page 182). The associated De-Enumerator block is setup to distinguish between occupied standby and unoccupied modes. In occupied and occupied bypass modes, the Switch block remains at its normally CNT-APG001-EN 241
- Page 214 and 215: ® Chapter 8 Constant-volume AHU wi
- Page 216 and 217: ® Chapter 8 Constant-volume AHU wi
- Page 218 and 219: ® Chapter 8 Constant-volume AHU wi
- Page 220 and 221: ® Chapter 8 Constant-volume AHU wi
- Page 222 and 223: ® Chapter 8 Constant-volume AHU wi
- Page 224 and 225: ® Chapter 8 Constant-volume AHU wi
- Page 226 and 227: ® Chapter 8 Constant-volume AHU wi
- Page 228 and 229: ® Chapter 8 Constant-volume AHU wi
- Page 230 and 231: ® Chapter 8 Constant-volume AHU wi
- Page 232 and 233: ® Chapter 8 Constant-volume AHU wi
- Page 234 and 235: ® Chapter 8 Constant-volume AHU wi
- Page 236 and 237: ® Chapter 8 Constant-volume AHU wi
- Page 238 and 239: ® Chapter 8 Constant-volume AHU wi
- Page 240 and 241: ® Chapter 8 Constant-volume AHU wi
- Page 242 and 243: ® Chapter 8 Constant-volume AHU wi
- Page 244 and 245: ® Chapter 8 Constant-volume AHU wi
- Page 246 and 247: ® Chapter 8 Constant-volume AHU wi
- Page 248 and 249: ® Chapter 8 Constant-volume AHU wi
- Page 250 and 251: ® Chapter 8 Constant-volume AHU wi
- Page 252 and 253: ® Programming best practices Set t
- Page 254 and 255: ® Programming best practices Figur
- Page 256 and 257: ® Programming best practices Use c
- Page 258 and 259: ® Programming best practices 234 C
- Page 260 and 261: ® Summary-question answers Figure
- Page 262 and 263: ® Summary-question answers Figure
- Page 266 and 267: ® Summary-question answers closed
- Page 268 and 269: ® Summary-question answers Figure
- Page 270 and 271: ® Summary-question answers Figure
- Page 272 and 273: ® Summary-question answers PROGRAM
- Page 274 and 275: ® Index dehumidification, 166-169,
- Page 276: Trane An American Standard Company
®<br />
Chapter 7, “Constant-volume AHU example”<br />
Chapter 7, “Constant-volume AHU<br />
example”<br />
1. A universal input configured as a a binary input must be selected as<br />
the occupancy sensor input in the Schedule application. See<br />
Figure 197.<br />
Figure 197: Schedule application occupancy inputs<br />
2. The Occupancy block, used in both the modes and setpoints program<br />
and the fan control program, provides the occupancy mode of the controller.<br />
Remember, the Occupancy block outputs one of four states,<br />
which is determined by the Schedule application for the controller:<br />
0 = Occupied<br />
1 = Unoccupied<br />
2 = Occupied Bypass<br />
3 = Occupied Standby<br />
When the controller enters occupied bypass mode, the Occupancy<br />
block outputs a value of 2. Take a closer look at the application of the<br />
Occupancy block in the modes and setpoints program (Figure 158 on<br />
page 182). The associated De-Enumerator block is setup to distinguish<br />
between occupied standby and unoccupied modes. In occupied<br />
and occupied bypass modes, the Switch block remains at its normally<br />
CNT-APG001-EN 241