Applications Guide Tracer Graphical Programming - Trane

Applications Guide Tracer Graphical Programming - Trane Applications Guide Tracer Graphical Programming - Trane

28.09.2014 Views

® Summary-question answers Figure 196: Effective setpoint calculation 4. Replace the network configuration inputs, nciDAClSP and nciDAHtSP, with analog variables that are adjustable from the operator display. 240 CNT-APG001-EN

® Chapter 7, “Constant-volume AHU example” Chapter 7, “Constant-volume AHU example” 1. A universal input configured as a a binary input must be selected as the occupancy sensor input in the Schedule application. See Figure 197. Figure 197: Schedule application occupancy inputs 2. The Occupancy block, used in both the modes and setpoints program and the fan control program, provides the occupancy mode of the controller. Remember, the Occupancy block outputs one of four states, which is determined by the Schedule application for the controller: 0 = Occupied 1 = Unoccupied 2 = Occupied Bypass 3 = Occupied Standby When the controller enters occupied bypass mode, the Occupancy block outputs a value of 2. Take a closer look at the application of the Occupancy block in the modes and setpoints program (Figure 158 on page 182). The associated De-Enumerator block is setup to distinguish between occupied standby and unoccupied modes. In occupied and occupied bypass modes, the Switch block remains at its normally CNT-APG001-EN 241

®<br />

Chapter 7, “Constant-volume AHU example”<br />

Chapter 7, “Constant-volume AHU<br />

example”<br />

1. A universal input configured as a a binary input must be selected as<br />

the occupancy sensor input in the Schedule application. See<br />

Figure 197.<br />

Figure 197: Schedule application occupancy inputs<br />

2. The Occupancy block, used in both the modes and setpoints program<br />

and the fan control program, provides the occupancy mode of the controller.<br />

Remember, the Occupancy block outputs one of four states,<br />

which is determined by the Schedule application for the controller:<br />

0 = Occupied<br />

1 = Unoccupied<br />

2 = Occupied Bypass<br />

3 = Occupied Standby<br />

When the controller enters occupied bypass mode, the Occupancy<br />

block outputs a value of 2. Take a closer look at the application of the<br />

Occupancy block in the modes and setpoints program (Figure 158 on<br />

page 182). The associated De-Enumerator block is setup to distinguish<br />

between occupied standby and unoccupied modes. In occupied<br />

and occupied bypass modes, the Switch block remains at its normally<br />

CNT-APG001-EN 241

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!