Summary-question answers<br />

Figure 189: Equip Room Exhaust Fan program with a modification<br />

7. Delete the ON constant block. Connect the output of the Fail block to<br />

both the Relay Control and Normally Open ports of the Switch block<br />

(Figure 189).<br />

Figure 190: Feedback Alarm block substitution<br />

Chapter 4, “Cooling tower with<br />

two-speed fan example”<br />

1. The Latch block may be configured in timed or manual mode. In manual<br />

mode, it does not provide for a time-interval input.<br />

2. Omit the Delay on Start block and its associated Constant block.<br />

Chapter 5, “Cooling tower with<br />

variable-speed fan example”<br />

1. The Feedback Alarm block is a combination of the XOR, Delay on<br />

Start, and Latch blocks. The sequence of operation might read as follows:<br />

Compare Request to Status. If Request does not equal Status for<br />

a period of 30 seconds, initiate an alarm. The alarm must be resettable.<br />

See Figure 190 for the possible substitution.<br />

2. See Figure 191 on page 237 for an example of how you could automatically<br />

reset the alarm reset without using a Switch block. Each time<br />

the program runs, the Alarm Reset is set to off.<br />

236 CNT-APG001-EN