Writing the communications program<br />

Figure 178: Communications program properties<br />

Use Network Variable Output blocks to transmit the space, discharge air,<br />

and mixed air temperatures through the SCC Profile (Figure 179). The<br />

Network Variable Output block works just like the Network Variable<br />

Input block, but it transmits information on the Comm5 network instead<br />

of receiving it. Be sure to specify the units in which the Network Variable<br />

Output block receives the data from the program using the properties dialog<br />

box for the block.<br />

Figure 179: Transmitting temperatures<br />

Transmit the effective setpoint. Remember, the effective setpoint may<br />

vary depending on the heat/cool mode and occupancy. So, incorporate the<br />

necessary logic to determine the appropriate setpoint to send. The SCC<br />

profile provides a variable, nviEffectSetpt. Use a Switch block to select<br />

the appropriate effective setpoint, cooling or heating, based on the<br />

heat/cool mode (Figure 180 on page 220).<br />

CNT-APG001-EN 219