Applications Guide Tracer Graphical Programming - Trane
Applications Guide Tracer Graphical Programming - Trane Applications Guide Tracer Graphical Programming - Trane
® Chapter 8 Constant-volume AHU with warm-up, pre-cool, and communications Writing the communications program The only new program in this chapter is concerned solely with communications. The sequence of operation requires that the following items be communicated to the air handler: • Occupancy • Space temperature setpoint • Outdoor air temperature • Space relative humidity • Economizer enable If communication with the BAS is lost, the air handler should use its predetermined default setpoints and operate in the occupied mode. The following information is communicated to the air handler in the programs you modified so far in this chapter. • The occupancy mode, whether it is communicated or based on the local schedule, is accounted for by using the Occupancy block in both the mode and setpoints and the fan control programs. The outdoor air temperature and economizer enable are received in the mixed air control program. • The space relative humidity is communicated as part of the SCC profile using the nviSpaceRH network variable input in the discharge air control program. • The space temperature setpoint is communicated as part of the SCC profile using the nviSetpoint network variable input in the mode and setpoints program. Send some information building automation system (BAS). The air handler must communicate the following items to the building automation system: • Space temperature • Discharge air temperature • Mixed air temperature • Effective setpoint • Effective occupancy • Supply fan status • Cooling valve status • Heating valve status • Outdoor air damper status • Alarm status • Application mode Theseitemsarecommunicatedsothatthebuildingoperatorcanviewthe status of the air-handling unit. Because communications to the building automation system are not critical to air-handler operation, this program executes once per minute. Create a new program and set its properties as shown in Figure 178 on page 219. 218 CNT-APG001-EN
® Writing the communications program Figure 178: Communications program properties Use Network Variable Output blocks to transmit the space, discharge air, and mixed air temperatures through the SCC Profile (Figure 179). The Network Variable Output block works just like the Network Variable Input block, but it transmits information on the Comm5 network instead of receiving it. Be sure to specify the units in which the Network Variable Output block receives the data from the program using the properties dialog box for the block. Figure 179: Transmitting temperatures Transmit the effective setpoint. Remember, the effective setpoint may vary depending on the heat/cool mode and occupancy. So, incorporate the necessary logic to determine the appropriate setpoint to send. The SCC profile provides a variable, nviEffectSetpt. Use a Switch block to select the appropriate effective setpoint, cooling or heating, based on the heat/cool mode (Figure 180 on page 220). CNT-APG001-EN 219
- Page 192 and 193: ® Chapter 7 Constant-volume AHU ex
- Page 194 and 195: ® Chapter 7 Constant-volume AHU ex
- Page 196 and 197: ® Chapter 7 Constant-volume AHU ex
- Page 198 and 199: ® Chapter 7 Constant-volume AHU ex
- Page 200 and 201: ® Chapter 7 Constant-volume AHU ex
- Page 202 and 203: ® Chapter 7 Constant-volume AHU ex
- Page 204 and 205: ® Chapter 7 Constant-volume AHU ex
- Page 206 and 207: ® Chapter 7 Constant-volume AHU ex
- Page 208 and 209: ® Chapter 7 Constant-volume AHU ex
- Page 210 and 211: ® Chapter 7 Constant-volume AHU ex
- Page 212 and 213: ® Chapter 7 Constant-volume AHU ex
- Page 214 and 215: ® Chapter 8 Constant-volume AHU wi
- Page 216 and 217: ® Chapter 8 Constant-volume AHU wi
- Page 218 and 219: ® Chapter 8 Constant-volume AHU wi
- Page 220 and 221: ® Chapter 8 Constant-volume AHU wi
- Page 222 and 223: ® Chapter 8 Constant-volume AHU wi
- Page 224 and 225: ® Chapter 8 Constant-volume AHU wi
- Page 226 and 227: ® Chapter 8 Constant-volume AHU wi
- Page 228 and 229: ® Chapter 8 Constant-volume AHU wi
- Page 230 and 231: ® Chapter 8 Constant-volume AHU wi
- Page 232 and 233: ® Chapter 8 Constant-volume AHU wi
- Page 234 and 235: ® Chapter 8 Constant-volume AHU wi
- Page 236 and 237: ® Chapter 8 Constant-volume AHU wi
- Page 238 and 239: ® Chapter 8 Constant-volume AHU wi
- Page 240 and 241: ® Chapter 8 Constant-volume AHU wi
- Page 244 and 245: ® Chapter 8 Constant-volume AHU wi
- Page 246 and 247: ® Chapter 8 Constant-volume AHU wi
- Page 248 and 249: ® Chapter 8 Constant-volume AHU wi
- Page 250 and 251: ® Chapter 8 Constant-volume AHU wi
- Page 252 and 253: ® Programming best practices Set t
- Page 254 and 255: ® Programming best practices Figur
- Page 256 and 257: ® Programming best practices Use c
- Page 258 and 259: ® Programming best practices 234 C
- Page 260 and 261: ® Summary-question answers Figure
- Page 262 and 263: ® Summary-question answers Figure
- Page 264 and 265: ® Summary-question answers Figure
- Page 266 and 267: ® Summary-question answers closed
- Page 268 and 269: ® Summary-question answers Figure
- Page 270 and 271: ® Summary-question answers Figure
- Page 272 and 273: ® Summary-question answers PROGRAM
- Page 274 and 275: ® Index dehumidification, 166-169,
- Page 276: Trane An American Standard Company
®<br />
Chapter 8 Constant-volume AHU with warm-up, pre-cool, and communications<br />
Writing the communications program<br />
The only new program in this chapter is concerned solely with communications.<br />
The sequence of operation requires that the following items be<br />
communicated to the air handler:<br />
• Occupancy<br />
• Space temperature setpoint<br />
• Outdoor air temperature<br />
• Space relative humidity<br />
• Economizer enable<br />
If communication with the BAS is lost, the air handler should use its predetermined<br />
default setpoints and operate in the occupied mode. The following<br />
information is communicated to the air handler in the programs<br />
you modified so far in this chapter.<br />
• The occupancy mode, whether it is communicated or based on the<br />
local schedule, is accounted for by using the Occupancy block in both<br />
the mode and setpoints and the fan control programs. The outdoor air<br />
temperature and economizer enable are received in the mixed air control<br />
program.<br />
• The space relative humidity is communicated as part of the SCC profile<br />
using the nviSpaceRH network variable input in the discharge air<br />
control program.<br />
• The space temperature setpoint is communicated as part of the SCC<br />
profile using the nviSetpoint network variable input in the mode and<br />
setpoints program.<br />
Send some information building automation system (BAS). The air handler<br />
must communicate the following items to the building automation<br />
system:<br />
• Space temperature<br />
• Discharge air temperature<br />
• Mixed air temperature<br />
• Effective setpoint<br />
• Effective occupancy<br />
• Supply fan status<br />
• Cooling valve status<br />
• Heating valve status<br />
• Outdoor air damper status<br />
• Alarm status<br />
• Application mode<br />
Theseitemsarecommunicatedsothatthebuildingoperatorcanviewthe<br />
status of the air-handling unit. Because communications to the building<br />
automation system are not critical to air-handler operation, this program<br />
executes once per minute. Create a new program and set its properties as<br />
shown in Figure 178 on page 219.<br />
218 CNT-APG001-EN