Chapter 8 Constant-volume AHU with warm-up, pre-cool, and communications<br />

Adding the pre-cool and warm-up decisions<br />

The heat/cool mode and night heat/cool decisions are the same as those in<br />

Chapter 7. See “Adding night heat/cool” on page 184 for more information.<br />

However, the mode and setpoints program must incorporate additional<br />

decisions to accommodate pre-cool and warm-up modes. These decisions<br />

arespecifiedinthesequenceofoperationandsummarizedhere:<br />

Enter pre-cool when all of the following are true:<br />

• The unit is occupied (including occupied, occupied standby, and occupied<br />

bypass modes).<br />

• The unit is in cooling mode.<br />

• The space temperature is at least 3°F above the effective cooling setpoint.<br />

Exit pre-cool mode when the space temperature falls to within 2°F of the<br />

effective cooling setpoint.<br />

Enter warm-up mode when all of the following are true:<br />

• The unit is occupied (including occupied, occupied standby, and occupied<br />

bypass modes).<br />

• The unit is in heating mode.<br />

• The space temperature is at least 3°F below the effective heating setpoint.<br />

Exit warm-up mode when the space temperature rises to within 2°F of<br />

the effective heating setpoint.<br />

Implement these decisions in graphical programming using the night<br />

heat/cool decision as a model. Note that you must base the decision for<br />

each mode on a value that is offset by 3°F from the effective cooling and<br />

heating setpoints (Figure 176 on page 215).<br />

• Use Add and Subtract blocks to calculate the setpoints for each Deadband<br />

block.<br />

• Configure the Deadband block for pre-cool as greater than, but configure<br />

the Deadband block for warm-up as less than.<br />

214 CNT-APG001-EN