Writing the discharge air control program<br />

Figure 171: Modulate or open the cooling valve?<br />

As in Chapter 7, when the cooling valve is enabled, a PID loop controls<br />

the discharge air temperature. And if dehumidification is also active, a<br />

second PID loop calculates the cooling valve position based on the space<br />

relative humidity. Control the valve to the greater of the two calculated<br />

valve positions.<br />

If pre-cool mode is active and economizing is not allowed, use a Switch<br />

block to bypass the PID outputs and open the valve completely<br />

(Figure 172 on page 208).<br />

CNT-APG001-EN 207