® Chapter 8 Constant-volume AHU with warm-up, pre-cool, and communications Controlling the cooling valve How do the additional modes and profile considerations change control of the cooling valve? Examine the sequence of operation with regard to the cooling valve. The changes for this chapter are shown in italics. Modulate the cooling valve to maintain the discharge air temperature at the discharge air cooling setpoint when all ofthefollowingaretrue: • The supply fan is on. • The air handler is in cooling mode. • The economizer function is not enabled. Or when all ofthefollowingaretrue: • The supply fan is on. • The air handler is in cooling mode (including pre-cool). • The economizer function is enabled. • The outdoor air damper is open at least 90%. Modulate the cooling valve to maintain the space relative humidity at the space relative humidity setpoint when all ofthefollowingaretrue: • The supply fan is on. • The air handler is in cooling mode. • Dehumidification is enabled. Open the cooling valve completely when all of the following are true: • The supply fan is on. • The air handler is in cooling mode. • The pre-cool mode is active. • Economizing is not allowed, or the outdoor air damper is open at least 90%. Close the cooling valve when any of the following is true: • The air handler is in heating mode. • The supply fan is off. • The discharge air temperature sensor is failed. Incorporatepre-coolmodeintothedecisiontoenablethecoolingvalve. Add another And block and complete the logic to determine whether the cooling valve is enabled or if it should open completely (Figure 171 on page 207). 206 CNT-APG001-EN

® Writing the discharge air control program Figure 171: Modulate or open the cooling valve? As in Chapter 7, when the cooling valve is enabled, a PID loop controls the discharge air temperature. And if dehumidification is also active, a second PID loop calculates the cooling valve position based on the space relative humidity. Control the valve to the greater of the two calculated valve positions. If pre-cool mode is active and economizing is not allowed, use a Switch block to bypass the PID outputs and open the valve completely (Figure 172 on page 208). CNT-APG001-EN 207

®<br />

Chapter 8 Constant-volume AHU with warm-up, pre-cool, and communications<br />

Controlling the cooling valve<br />

How do the additional modes and profile considerations change control of<br />

the cooling valve? Examine the sequence of operation with regard to the<br />

cooling valve. The changes for this chapter are shown in italics.<br />

Modulate the cooling valve to maintain the discharge air temperature at<br />

the discharge air cooling setpoint when all ofthefollowingaretrue:<br />

• The supply fan is on.<br />

• The air handler is in cooling mode.<br />

• The economizer function is not enabled.<br />

Or when all ofthefollowingaretrue:<br />

• The supply fan is on.<br />

• The air handler is in cooling mode (including pre-cool).<br />

• The economizer function is enabled.<br />

• The outdoor air damper is open at least 90%.<br />

Modulate the cooling valve to maintain the space relative humidity at the<br />

space relative humidity setpoint when all ofthefollowingaretrue:<br />

• The supply fan is on.<br />

• The air handler is in cooling mode.<br />

• Dehumidification is enabled.<br />

Open the cooling valve completely when all of the following are true:<br />

• The supply fan is on.<br />

• The air handler is in cooling mode.<br />

• The pre-cool mode is active.<br />

• Economizing is not allowed, or the outdoor air damper is open at least<br />

90%.<br />

Close the cooling valve when any of the following is true:<br />

• The air handler is in heating mode.<br />

• The supply fan is off.<br />

• The discharge air temperature sensor is failed.<br />

Incorporatepre-coolmodeintothedecisiontoenablethecoolingvalve.<br />

Add another And block and complete the logic to determine whether the<br />

cooling valve is enabled or if it should open completely (Figure 171 on<br />

page 207).<br />

206 CNT-APG001-EN