® Chapter 8 Constant-volume AHU with warm-up, pre-cool, and communications Controlling the cooling valve How do the additional modes and profile considerations change control of the cooling valve? Examine the sequence of operation with regard to the cooling valve. The changes for this chapter are shown in italics. Modulate the cooling valve to maintain the discharge air temperature at the discharge air cooling setpoint when all ofthefollowingaretrue: • The supply fan is on. • The air handler is in cooling mode. • The economizer function is not enabled. Or when all ofthefollowingaretrue: • The supply fan is on. • The air handler is in cooling mode (including pre-cool). • The economizer function is enabled. • The outdoor air damper is open at least 90%. Modulate the cooling valve to maintain the space relative humidity at the space relative humidity setpoint when all ofthefollowingaretrue: • The supply fan is on. • The air handler is in cooling mode. • Dehumidification is enabled. Open the cooling valve completely when all of the following are true: • The supply fan is on. • The air handler is in cooling mode. • The pre-cool mode is active. • Economizing is not allowed, or the outdoor air damper is open at least 90%. Close the cooling valve when any of the following is true: • The air handler is in heating mode. • The supply fan is off. • The discharge air temperature sensor is failed. Incorporatepre-coolmodeintothedecisiontoenablethecoolingvalve. Add another And block and complete the logic to determine whether the cooling valve is enabled or if it should open completely (Figure 171 on page 207). 206 CNT-APG001-EN
® Writing the discharge air control program Figure 171: Modulate or open the cooling valve? As in Chapter 7, when the cooling valve is enabled, a PID loop controls the discharge air temperature. And if dehumidification is also active, a second PID loop calculates the cooling valve position based on the space relative humidity. Control the valve to the greater of the two calculated valve positions. If pre-cool mode is active and economizing is not allowed, use a Switch block to bypass the PID outputs and open the valve completely (Figure 172 on page 208). CNT-APG001-EN 207
- Page 180 and 181: ® Chapter 7 Constant-volume AHU ex
- Page 182 and 183: ® Chapter 7 Constant-volume AHU ex
- Page 184 and 185: ® Chapter 7 Constant-volume AHU ex
- Page 186 and 187: ® Chapter 7 Constant-volume AHU ex
- Page 188 and 189: ® Chapter 7 Constant-volume AHU ex
- Page 190 and 191: ® Chapter 7 Constant-volume AHU ex
- Page 192 and 193: ® Chapter 7 Constant-volume AHU ex
- Page 194 and 195: ® Chapter 7 Constant-volume AHU ex
- Page 196 and 197: ® Chapter 7 Constant-volume AHU ex
- Page 198 and 199: ® Chapter 7 Constant-volume AHU ex
- Page 200 and 201: ® Chapter 7 Constant-volume AHU ex
- Page 202 and 203: ® Chapter 7 Constant-volume AHU ex
- Page 204 and 205: ® Chapter 7 Constant-volume AHU ex
- Page 206 and 207: ® Chapter 7 Constant-volume AHU ex
- Page 208 and 209: ® Chapter 7 Constant-volume AHU ex
- Page 210 and 211: ® Chapter 7 Constant-volume AHU ex
- Page 212 and 213: ® Chapter 7 Constant-volume AHU ex
- Page 214 and 215: ® Chapter 8 Constant-volume AHU wi
- Page 216 and 217: ® Chapter 8 Constant-volume AHU wi
- Page 218 and 219: ® Chapter 8 Constant-volume AHU wi
- Page 220 and 221: ® Chapter 8 Constant-volume AHU wi
- Page 222 and 223: ® Chapter 8 Constant-volume AHU wi
- Page 224 and 225: ® Chapter 8 Constant-volume AHU wi
- Page 226 and 227: ® Chapter 8 Constant-volume AHU wi
- Page 228 and 229: ® Chapter 8 Constant-volume AHU wi
- Page 232 and 233: ® Chapter 8 Constant-volume AHU wi
- Page 234 and 235: ® Chapter 8 Constant-volume AHU wi
- Page 236 and 237: ® Chapter 8 Constant-volume AHU wi
- Page 238 and 239: ® Chapter 8 Constant-volume AHU wi
- Page 240 and 241: ® Chapter 8 Constant-volume AHU wi
- Page 242 and 243: ® Chapter 8 Constant-volume AHU wi
- Page 244 and 245: ® Chapter 8 Constant-volume AHU wi
- Page 246 and 247: ® Chapter 8 Constant-volume AHU wi
- Page 248 and 249: ® Chapter 8 Constant-volume AHU wi
- Page 250 and 251: ® Chapter 8 Constant-volume AHU wi
- Page 252 and 253: ® Programming best practices Set t
- Page 254 and 255: ® Programming best practices Figur
- Page 256 and 257: ® Programming best practices Use c
- Page 258 and 259: ® Programming best practices 234 C
- Page 260 and 261: ® Summary-question answers Figure
- Page 262 and 263: ® Summary-question answers Figure
- Page 264 and 265: ® Summary-question answers Figure
- Page 266 and 267: ® Summary-question answers closed
- Page 268 and 269: ® Summary-question answers Figure
- Page 270 and 271: ® Summary-question answers Figure
- Page 272 and 273: ® Summary-question answers PROGRAM
- Page 274 and 275: ® Index dehumidification, 166-169,
- Page 276: Trane An American Standard Company
®<br />
Chapter 8 Constant-volume AHU with warm-up, pre-cool, and communications<br />
Controlling the cooling valve<br />
How do the additional modes and profile considerations change control of<br />
the cooling valve? Examine the sequence of operation with regard to the<br />
cooling valve. The changes for this chapter are shown in italics.<br />
Modulate the cooling valve to maintain the discharge air temperature at<br />
the discharge air cooling setpoint when all ofthefollowingaretrue:<br />
• The supply fan is on.<br />
• The air handler is in cooling mode.<br />
• The economizer function is not enabled.<br />
Or when all ofthefollowingaretrue:<br />
• The supply fan is on.<br />
• The air handler is in cooling mode (including pre-cool).<br />
• The economizer function is enabled.<br />
• The outdoor air damper is open at least 90%.<br />
Modulate the cooling valve to maintain the space relative humidity at the<br />
space relative humidity setpoint when all ofthefollowingaretrue:<br />
• The supply fan is on.<br />
• The air handler is in cooling mode.<br />
• Dehumidification is enabled.<br />
Open the cooling valve completely when all of the following are true:<br />
• The supply fan is on.<br />
• The air handler is in cooling mode.<br />
• The pre-cool mode is active.<br />
• Economizing is not allowed, or the outdoor air damper is open at least<br />
90%.<br />
Close the cooling valve when any of the following is true:<br />
• The air handler is in heating mode.<br />
• The supply fan is off.<br />
• The discharge air temperature sensor is failed.<br />
Incorporatepre-coolmodeintothedecisiontoenablethecoolingvalve.<br />
Add another And block and complete the logic to determine whether the<br />
cooling valve is enabled or if it should open completely (Figure 171 on<br />
page 207).<br />
206 CNT-APG001-EN