®<br />

Writing the mixed air control program<br />

Figure 166: Economize decision with communicated values<br />

sequence of operation. Modify the first part of the decision to accommodate<br />

the following communicated values:<br />

• Outdoor air temperature<br />

• Economizer enable<br />

The SCC profile contains a variable for the outdoor air temperature, nvi-<br />

OutdoorTemp.However,thereisnosuchvariabletoenableanddisable<br />

theeconomizer.Usea<strong>Tracer</strong>Summitbinaryvariabletosatisfythisneed<br />

(Figure 166).<br />

Network variable input<br />

<strong>Tracer</strong><br />

Summit<br />

binary<br />

variable<br />

In Chapter 7, a second stage of decision making was added to accommodate<br />

night heat/cool mode. Figure 167 on page 202 shows how consideration<br />

of pre-cool and warm-up modes changes the second stage of decision<br />

making. Add the Warm-Up and Pre-Cool binary variable blocks and the<br />

logic to consider them in the decision whether to close the outdoor air<br />

damper.<br />

CNT-APG001-EN 201