Determining a programming approach<br />

Determining a programming approach<br />

The programs created in Chapter 7 serve as the starting point for all of<br />

the programs in this chapter. Modify the programs to apply the new<br />

warm-up and pre-cool modes and write a new program to incorporate<br />

some of the communications functions with the <strong>Tracer</strong> Summit building<br />

automation system.<br />

From the sequence of operation, determine the basic control functions<br />

required. The required control functions are very similar to those in the<br />

Chapter 7, “Constant-volume AHU example.” In this case, the following<br />

control functions must be addressed.<br />

• Effective space setpoint calculation<br />

• Mode determination, including night heat/cool, pre-cool, and warm-up<br />

• Supply fan control<br />

• Exhaust fan control<br />

• Mixed air/outdoor air damper control<br />

• Discharge air setpoint calculation<br />

• Cooling valve control, including dehumidification<br />

• Heating valve control, including dehumidification<br />

• Humidification<br />

• Alarm management<br />

• Communications<br />

Not every control function fits into one program. Determine the number<br />

of programs required by grouping control functions that require the same<br />

information and/or the same run frequency as shown in Table 28.<br />

Table 28: Control functions within each program<br />

Program name<br />

FanControl<br />

MixedAirControl<br />

DischargeAirControl<br />

Alarms<br />

ModeAndSetpoints<br />

Communications<br />

Control functions<br />

Supply fan control<br />

Exhaust fan control<br />

Mixed air/outdoor air damper control<br />

Discharge air setpoint calculation<br />

Cooling valve control<br />

Heating valve control<br />

Dehumidification<br />

Humidification<br />

Alarm management<br />

Effective space setpoint calculation<br />

Setpoint source determination<br />

Mode determination<br />

Communications to BAS<br />

CNT-APG001-EN 199