Reviewing the sequence of operation<br />
The corresponding data definition is presented in Table 23 and Table 24,<br />
and a wiring diagram is presented in Figure 165 on page 198.<br />
Table 23: Modified constant-volume AHU inputs and outputs data definition<br />
Inputs and<br />
outputs<br />
Type Name Notes<br />
Inputs 1 Analog Space Temp Universal input configured as thermistor or RTD<br />
2 Analog Thumbwheel SP Universal input configured as thermistor or RTD<br />
3 Analog Mixed Air Temp Universal input configured as thermistor or RTD<br />
4 Analog Discharge Air Temp Universal input configured as thermistor or RTD<br />
5 Analog Outdoor Air Temp Universal input configured as thermistor<br />
6 Analog Duct Humidity<br />
7 Binary Low Temp Detect<br />
8 Binary Run/Stop Interlock<br />
9 Binary Occupancy/Generic<br />
10 Binary Supply Fan Status<br />
11 Binary Filter Status<br />
12 Binary Exhaust Fan Status<br />
Pressure Duct Static Pressure*<br />
Binary outputs 1 Supply Fan Start/Stop<br />
2 Exhaust Fan Start/Stop<br />
3 Not Used<br />
4 Not Used<br />
5 Not Used<br />
6 Alarm Output Status/custom alarm indicator<br />
Analog outputs 1 Supply Fan Speed* Analog output configured as voltage, 0–10 V<br />
2 Cooling Valve Position Analog output configured as voltage, 0–10 V<br />
3 Heating Valve Position Analog output configured as voltage, 0–10 V<br />
4 Face and Bypass Damper* Analog output configured as voltage, 0–10 V<br />
5 OA Damper Position Analog output configured as voltage, 0–10 V<br />
6 Humidifier Analog output configured as voltage, 0–10 V<br />
* These inputs and outputs are not used in this program but are often used in air-handler programs.<br />
Note: The inputs and outputs in this table are configured so that a <strong>Tracer</strong> AH540 main logic board could be replaced with a <strong>Tracer</strong><br />
MP580/581 board, except for the Mixed Air Temp, which is input 6 on the <strong>Tracer</strong> AH540.<br />
Table 24: Modified constant-volume AHU variables data definition<br />
Variable Name Notes<br />
<strong>Tracer</strong> Summit binary variables<br />
Economizer Enable<br />
BAS Setpoint Enable<br />
Alarm Reset (BAS)<br />
CNT-APG001-EN 195