Reviewing the sequence of operation<br />

The corresponding data definition is presented in Table 23 and Table 24,<br />

and a wiring diagram is presented in Figure 165 on page 198.<br />

Table 23: Modified constant-volume AHU inputs and outputs data definition<br />

Inputs and<br />

outputs<br />

Type Name Notes<br />

Inputs 1 Analog Space Temp Universal input configured as thermistor or RTD<br />

2 Analog Thumbwheel SP Universal input configured as thermistor or RTD<br />

3 Analog Mixed Air Temp Universal input configured as thermistor or RTD<br />

4 Analog Discharge Air Temp Universal input configured as thermistor or RTD<br />

5 Analog Outdoor Air Temp Universal input configured as thermistor<br />

6 Analog Duct Humidity<br />

7 Binary Low Temp Detect<br />

8 Binary Run/Stop Interlock<br />

9 Binary Occupancy/Generic<br />

10 Binary Supply Fan Status<br />

11 Binary Filter Status<br />

12 Binary Exhaust Fan Status<br />

Pressure Duct Static Pressure*<br />

Binary outputs 1 Supply Fan Start/Stop<br />

2 Exhaust Fan Start/Stop<br />

3 Not Used<br />

4 Not Used<br />

5 Not Used<br />

6 Alarm Output Status/custom alarm indicator<br />

Analog outputs 1 Supply Fan Speed* Analog output configured as voltage, 0–10 V<br />

2 Cooling Valve Position Analog output configured as voltage, 0–10 V<br />

3 Heating Valve Position Analog output configured as voltage, 0–10 V<br />

4 Face and Bypass Damper* Analog output configured as voltage, 0–10 V<br />

5 OA Damper Position Analog output configured as voltage, 0–10 V<br />

6 Humidifier Analog output configured as voltage, 0–10 V<br />

* These inputs and outputs are not used in this program but are often used in air-handler programs.<br />

Note: The inputs and outputs in this table are configured so that a <strong>Tracer</strong> AH540 main logic board could be replaced with a <strong>Tracer</strong><br />

MP580/581 board, except for the Mixed Air Temp, which is input 6 on the <strong>Tracer</strong> AH540.<br />

Table 24: Modified constant-volume AHU variables data definition<br />

Variable Name Notes<br />

<strong>Tracer</strong> Summit binary variables<br />

Economizer Enable<br />

BAS Setpoint Enable<br />

Alarm Reset (BAS)<br />

CNT-APG001-EN 195