Reviewing the sequence of operation<br />

Control<br />

The following parameters for the sequence of operation are presented<br />

according to the equipment that must be controlled.<br />

Supply fan<br />

Operate the supply fan continuously whenever the air handler is in occupied<br />

or night heat/cool modes. Turn the supply fan off whenever one of the<br />

following occurs:<br />

• The air handler is unoccupied.<br />

• The run/stop interlock is open.<br />

• The mixed air temperature is too cold, and the low limit detection is<br />

closed.<br />

• The supply fan status indicates a fan failure after a 1-minute delay.<br />

Note:<br />

Afailureduetolowmixedairtemperatureorfanfailure<br />

requires a manual reset. Also, the low limit switch may require<br />

a manual, hardware reset.<br />

Outdoor air damper<br />

When the economizer function is enabled and the outdoor air temperature<br />

is less than the economizer changeover setpoint, modulate the outdoor<br />

air damper between the adjustable minimum position and fully open<br />

to maintain the discharge air cooling setpoint. Modulate the outdoor air<br />

damper closed, overriding the minimum position, to maintain the mixed<br />

air temperature at or above the mixed air setpoint.<br />

If the economizer function is disabled or the air handler is in the heat<br />

mode, control the outdoor air damper to its minimum position. If the outdoor<br />

air temperature falls below a low ambient damper lockout setpoint,<br />

control the outdoor air damper to its closed position. In unoccupied mode,<br />

control the outdoor air damper to its closed position. Also, if the supply<br />

fan is off or the mixed air temperature sensor is failed, control the outdoor<br />

air damper to its closed position.<br />

Exhaust fan<br />

Coordinate exhaust fan operation with the unit supply fan and outdoor<br />

air damper position. Energize the exhaust fan whenever the supply fan is<br />

on and the outdoor air damper is open beyond 30%. Keep the exhaust fan<br />

on until the outdoor air damper closes to below 20% open or the supply<br />

fan is turned off.<br />

Cooling valve<br />

Modulate the cooling valve to maintain the discharge air temperature at<br />

the discharge air cooling setpoint. If the economizer function is enabled<br />

and the outdoor air damper is not open at least 90%, control the cooling<br />

valve to its closed position. Also, close the cooling valve if the air handler<br />

CNT-APG001-EN 193