Reviewing the sequence of operation<br />
occupied standby setpoints and maintain the outdoor air damper to its<br />
minimum position.<br />
Unoccupied mode (including night heat/cool)<br />
When the air handler is in unoccupied mode, turn the supply fan off, close<br />
the outside air damper fully, and close the cooling and heating valves<br />
fully. Open the heating valve completely if the outdoor air temperature<br />
falls below the freeze avoidance setpoint, 35°F (adjustable).<br />
If the space temperature falls below the unoccupied heating setpoint,<br />
start the supply fan and transition the air handler to heating and keep<br />
the outdoor air damper closed to maintain the unoccupied heating setpoint.<br />
When the space temperature rises above the unoccupied heating<br />
setpoint, shut down the air handler.<br />
If the space temperature rises above the unoccupied cooling setpoint,<br />
start the supply fan and transition the air handler to cooling to maintain<br />
the unoccupied cooling setpoint. Modulate the outside air damper if the<br />
outside air temperature is less than the economizer changeover setpoint.<br />
When the space temperature falls below the unoccupied cooling setpoint,<br />
shut down the air handler.<br />
Warm-up and pre-cool modes<br />
During occupied and occupied standby modes, when there is a call for<br />
heating and the space temperature is 3°F or more below the effective<br />
occupied heating setpoint, initiate a warm-up sequence. During warm-up,<br />
operate the supply fan continuously, close the outdoor air damper, and<br />
opentheheatingvalveto100%.Whenthespacetemperaturecomes<br />
within 2°F of the heating setpoint, open the outside air damper to the<br />
occupied minimum position and transition the air handler to occupied<br />
mode.<br />
During occupied and occupied standby modes, when there is a call for<br />
cooling and the space temperature is 3°F or more above the effective occupied<br />
cooling setpoint, initiate a morning cool-down sequence. Operate the<br />
supply fan continuously and the air handler in the economizing mode, if<br />
possible. If economizing is not possible, open the cooling valve to 100%<br />
and keep the outside air damper closed. When the space temperature<br />
reaches the cooling setpoint, open the outside air damper to the occupied<br />
minimum position and transition the air handler to occupied mode.<br />
Setpoints<br />
For occupied, occupied standby, and occupied bypass modes, calculate<br />
effective cooling and heating setpoints based on a single space temperature<br />
setpoint and the configured default occupied and occupied standby<br />
setpoints. The space temperature setpoint source may be the building<br />
automation system, the operator display, or a wired thumbwheel setpoint<br />
CNT-APG001-EN 191