28.09.2014 Views

Applications Guide Tracer Graphical Programming - Trane

Applications Guide Tracer Graphical Programming - Trane

Applications Guide Tracer Graphical Programming - Trane

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

®<br />

Chapter 7 Constant-volume AHU example<br />

Controlling the humidifier<br />

Writing the alarms program<br />

The alarms program indicates diagnostic conditions to the operator and<br />

protects the equipment from potential harm when such a condition exists.<br />

According to the sequence of operations, the following diagnostic conditions<br />

require an alarm indication:<br />

• Dirty filter<br />

• Duct humidity high limit<br />

• Exhaust fan failure<br />

• Low outdoor air temperature<br />

• Low (mixed air) temperature detection<br />

• Sensor failure (including discharge air temperature, mixed air temperature,<br />

outdoor air temperature, and space temperature)<br />

• Supply fan failure<br />

The following failures shutdown the air handler and require a manual<br />

reset:<br />

• Discharge air or mixed air temperature sensor failure<br />

• Fan failure<br />

• Low mixed air temperature<br />

All alarms must be resettable at the operator display.<br />

The requirements for the Alarms program are nearly identical to the<br />

same program in the VAV air handler with one exception: The duct static<br />

pressure high limit is no longer needed. The duct humidity high limit was<br />

added. The high limit for the duct static pressure is not applicable to a<br />

constant-volume AHU. The use of humidification requires the addition of<br />

a duct humidity high limit. Set the program properties as shown in<br />

Figure 152 on page 177.<br />

176 CNT-APG001-EN

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!