Chapter 7 Constant-volume AHU example<br />

Figure 147: Operate the cooling valve?<br />

Think of the cooling valve control in two parts.<br />

• Use a combination of logic blocks to determine if the cooling valve<br />

operates.<br />

• Apply the output of the economizer decision here.<br />

• Use a Deadband block to consider the position of the outdoor air<br />

damperasshowninFigure147.<br />

When the cooling valve is enabled, use a PID loop to perform discharge<br />

air temperature control. However, if dehumidification is also active, you<br />

need a second PID loop to calculate the cooling valve position based on<br />

the space relative humidity. Control the valve to the greater of the two<br />

calculated valve positions (Figure 148 on page 171).<br />

170 CNT-APG001-EN