Chapter 7 Constant-volume AHU example<br />

Figure 145: Reset block linear equation plot<br />

• SNVT_amp_mil is not a network variable input (nvi) type that<br />

includes the flag for the Fail block, so use a Between block to check<br />

that the value from the nvi is in a valid range.<br />

➤ Using a Between block<br />

Use a Between block to check an analog value against a range and<br />

then output a binary value accordingly. If the analog value is<br />

between the upper and lower limits, the output is true.<br />

• Use wireless connections to carry the resultant data to the portions of<br />

the program controlling the cooling and heating valves and controlling<br />

the humidifier.<br />

Note:<br />

This module enables or disables only the ability to humidify or<br />

dehumidify. Control of the cooling and heating valves to accomplish<br />

dehumidification is incorporated into the appropriate<br />

modules. Control of the humidifier itself requires a separate<br />

module.<br />

168 CNT-APG001-EN