Applications Guide Tracer Graphical Programming - Trane

Applications Guide Tracer Graphical Programming - Trane Applications Guide Tracer Graphical Programming - Trane

28.09.2014 Views

® Chapter 7 Constant-volume AHU example Figure 138: Determining whether to economize Close the outdoor air damper completely when any of the following is true: • The unit is in unoccupied mode. • The unit is in night heat/cool mode and heating. • The unit is in night heat/cool mode and cooling, and economizing is not allowed. • The outdoor air temperature falls below the low outdoor air temperature setpoint. • The supply fan is off. • The mixed air temperature sensor is failed. Simplifytheprogrambyseparatingthedecisiontoeconomizefromthe actual control of the damper. Add a second stage of decision making to close the outdoor air damper in night heat/cool mode. Economizing is only permitted in night heat/cool mode when the unit is cooling, the economizer is enabled, and the outdoor air temperature is less than the economizer changeover setpoint. Add the OK to Economize binary variable to the same program for the VAV air handler, as shown in Figure 138. Use this Variable block to pass the result of the economize decision to other programs, such as the discharge air control program. Figure 139 on page 161 shows the modifying decision based on night heat/cool mode. 160 CNT-APG001-EN

® Writing the mixed air control program Figure 139: Night heat/cool incorporated into outside air damper control Control of the outdoor air damper position remains the same, but with the following exceptions (as shown in Figure 140 on page 162): • The constant-volume air handler employs a single discharge air temperature setpoint, instead of both cooling and heating discharge air temperature setpoints. • Unlike the DAC profile, the SCC profile provides the outdoor air damper minimum position, but does not provide the mixed air low limit setpoint. Use an NC Input (network configuration input) block to supply the outdoor air damper minimum position, and a Variable block to supply the mixed air temperature setpoint. • Use the Wireless block, Enable_OADamper to enable and disable the primary PID loop. • Use the Close_OADamper wireless block to communicate the result of the decision in Figure 140 on page 162, based on night heat/cool mode. CNT-APG001-EN 161

®<br />

Chapter 7 Constant-volume AHU example<br />

Figure 138: Determining whether to economize<br />

Close the outdoor air damper completely when any of the following is<br />

true:<br />

• The unit is in unoccupied mode.<br />

• The unit is in night heat/cool mode and heating.<br />

• The unit is in night heat/cool mode and cooling, and economizing is<br />

not allowed.<br />

• The outdoor air temperature falls below the low outdoor air temperature<br />

setpoint.<br />

• The supply fan is off.<br />

• The mixed air temperature sensor is failed.<br />

Simplifytheprogrambyseparatingthedecisiontoeconomizefromthe<br />

actual control of the damper. Add a second stage of decision making to<br />

close the outdoor air damper in night heat/cool mode. Economizing is only<br />

permitted in night heat/cool mode when the unit is cooling, the economizer<br />

is enabled, and the outdoor air temperature is less than the economizer<br />

changeover setpoint.<br />

Add the OK to Economize binary variable to the same program for the<br />

VAV air handler, as shown in Figure 138. Use this Variable block to pass<br />

the result of the economize decision to other programs, such as the discharge<br />

air control program.<br />

Figure 139 on page 161 shows the modifying decision based on night<br />

heat/cool mode.<br />

160 CNT-APG001-EN

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!