Writing the mixed air control program<br />

Figure 137: Mixed air control program properties<br />

Operation of the outdoor air damper and subsequent mixed air temperature<br />

control must satisfy a number of scenarios according to the sequence<br />

of operation.<br />

Modulate the outdoor air damper between the adjustable minimum position<br />

and fully open to maintain the discharge air cooling setpoint when<br />

all ofthefollowingaretrue:<br />

• The economizer is enabled.<br />

• The outdoor air temperature is less than the economizer changeover<br />

(or outdoor air temperature) setpoint.<br />

• The air handler is in cooling mode, including when it is in night<br />

heat/cool mode.<br />

Modulate the outdoor air damper closed, overriding the minimum position,<br />

to maintain the mixed air temperature at or above the mixed air setpoint.<br />

Control the outdoor air damper to its minimum position when either of<br />

the following is true:<br />

• The economizer function is disabled.<br />

• The air handler is in heating mode.<br />

CNT-APG001-EN 159