Chapter 7 Constant-volume AHU example<br />

Determining a programming approach<br />

As in the previous chapter, the programming instructions in this chapter<br />

are in a modular form. Remember that this sequence of operation could<br />

result in a large number of variations in program content and programming<br />

technique.<br />

From the sequence of operation, determine the basic control functions<br />

required. The required control functions are very similar to those for the<br />

Chapter 6, “VAV AHU example.” Address the following control functions:<br />

• Effective space setpoint calculation<br />

• Mode determination, including night heat/cool<br />

• Supply fan control<br />

• Exhaust fan control<br />

• Mixed air and outdoor air damper control<br />

• Discharge air setpoint calculation<br />

• Cooling valve control, including dehumidification<br />

• Heating valve control, including dehumidification<br />

• Alarm management<br />

Not every control function fits into one program. Determine the number<br />

of programs required by grouping control functions together that require<br />

the same information, and/or the same run frequency as shown in<br />

Table 22.<br />

Table 22: Control functions within each program<br />

Program name<br />

FanControl<br />

MixedAirControl<br />

DischargeAirControl<br />

Alarms<br />

ModeAndSetpoints<br />

Control functions<br />

Supply fan control<br />

Exhaust fan control<br />

Mixed air/outdoor air damper control<br />

Discharge air setpoint calculation<br />

Cooling valve control<br />

Heating valve control<br />

Dehumidification<br />

Humidification<br />

Alarm management<br />

Effective space setpoint calculation<br />

Setpoint source determination<br />

Mode determination<br />

The functionality of many components of the constant-volume air handler<br />

is similar to that of the VAV air handler. Keep in mind that you can modify<br />

those programs and re-use them for the constant-volume air handler.<br />

154 CNT-APG001-EN