Chapter 7 Constant-volume AHU example<br />

(CNT-SVP01A-EN). The SCC profile provides the configuration data<br />

listed in Table 20.<br />

Table 20: Network configuration inputs for the SCC profile<br />

nci SNVT Notes<br />

nciBypassTime SNVT_time_min Occupied bypass time<br />

nciOAMinPos SNVT_lev_percent Outdoor air damper minimum position<br />

nciSpaceCO2Lim SNVT_ppm Space CO 2 limit<br />

nciSpaceRHSetpt SNVT_lev_percent Space relative humidity setpoint<br />

nciSetpoints SNVT_temp_setpt Provides default unoccupied, occupied,<br />

and occupied standby cooling<br />

and heating setpoints<br />

The air-handling unit receives the space relative humidity from a peer<br />

Comm5 device, a <strong>Tracer</strong> MP503 I/O module in this scenario. The space<br />

relative humidity is sent to the <strong>Tracer</strong> MP580/581 controller through a<br />

network variable input nviCurrent_mA01. See Table 21 for more information.<br />

Table 21: Network variable inputs<br />

nvi SNVT Notes<br />

nviCurrent_mA01 SNVT_amp_mil Space relative humidity, measured<br />

in current (mA)<br />

Note:The <strong>Tracer</strong> MP503 module communicates this value that must be converted to<br />

units of humidity at the <strong>Tracer</strong> MP580/581 controller using TGP.<br />

Then make sure that the TGP editor is open and ready to go.<br />

152 CNT-APG001-EN