Reviewing the sequence of operation<br />
Table 19: Constant-volume AHU variables data definition<br />
Variable Name Notes<br />
<strong>Tracer</strong> Summit binary variables Not Used<br />
Local binary variables Supply Fan Failure Sourced from a program<br />
Exhaust Fan Failure<br />
Sourced from a program<br />
Sensor Failure<br />
Sourced from a program<br />
Duct Humidity Limit Sourced from a program<br />
Low OA Temp Alarm Sourced from a program<br />
Fan Failure Reset<br />
Sourced from operator display and a program<br />
Alarm Reset<br />
Sourced from operator display and a program<br />
Manual Reset Alarm Sourced from a program<br />
Auto Reset Alarm<br />
Sourced from a program<br />
Thumbwheel SP Enable Sourced from operator display<br />
Economizer Enable<br />
Sourced from operator display<br />
Heat/Cool Mode<br />
Sourced from a program<br />
OK to Economize<br />
Sourced from a program<br />
Humidify<br />
Sourced from a program<br />
Dehumidify<br />
Sourced from a program<br />
Night Heat/Cool<br />
Sourced from a program<br />
<strong>Tracer</strong> Summit analog variables Not Used<br />
Local analog variables Space Temp SP (OD) Setpoint sourced from the operator display<br />
Eff Occ Cool SP<br />
Sourced from a program<br />
Eff Occ Heat SP<br />
Sourced from a program<br />
Effective Cool SP<br />
Sourced from a program<br />
Effective Heat SP<br />
Sourced from a program<br />
Economizer Changeover SP Sourced from the operator display<br />
Discharge Air SP<br />
Sourced from a program<br />
Low OA Temp SP<br />
Setpoint sourced from the operator display<br />
Mixed Air Temp SP<br />
Setpoint sourced from the operator display<br />
Dehumidification SP Setpoint sourced from the operator display<br />
Humidification SP<br />
Setpoint sourced from the operator display<br />
Ex Fan OA Damper SP Setpoint sourced from the operator display<br />
Ex Fan OA Damper Dbd Setpoint sourced from the operator display<br />
Before you write the program, configure these inputs, outputs, and variables<br />
in your <strong>Tracer</strong> MP580/581 controller.<br />
Also, because you are programming a constant-volume air-handling unit,<br />
set the controller to use the SCC profile. For more information about configuring<br />
the controller, including setting it to use the SCC profile, see the<br />
<strong>Tracer</strong> MP580/581 Programmable Controller <strong>Programming</strong> guide<br />