Reviewing the sequence of operation<br />

mode, the supply fan is off, or the discharge air temperature sensor is<br />

failed.<br />

Heating valve<br />

Modulatetheheatingvalvetomaintainthedischargeairtemperatureat<br />

the discharge air setpoint. Close the heating valve if the air handler is in<br />

cool mode, the supply fan is off, or the discharge air temperature sensor is<br />

failed. Open the heating valve if the supply fan is off and the outdoor air<br />

temperature falls below the adjustable freeze avoidance setpoint.<br />

Humidification<br />

Enable humidification mode when the air handler is in occupied mode,<br />

the supply fan is on, and the outdoor air temperature falls below 55°F.<br />

Modulate the humidifier to maintain the space relative humidity setpoint.<br />

If the duct relative humidity exceeds 85%, turn off the humidifier<br />

to prevent condensation in the duct work and indicate an alarm.<br />

Dehumidification<br />

Enable dehumidification mode when the air handler is occupied, the supply<br />

fan is on, the outdoor air temperature is above 55°F, and the space relative<br />

humidity is above the space dehumidification setpoint. Modulate<br />

the cooling valve to maintain space relative humidity and the heating<br />

valve to maintain discharge air temperature.<br />

Alarms<br />

In addition to the alarm requirements mentioned above, indicate an<br />

alarm at the operator display and turn on the alarm output when any<br />

sensor fails. Alarms must be resettable at the operator display. Diagnostic<br />

conditions include the following:<br />

• Dirty filter<br />

• Duct humidity high limit<br />

• Exhaust fan failure<br />

• Low outdoor air temperature<br />

• Low (mixed air) temperature detection<br />

• Sensor failure (including discharge air temperature, mixed air temperature,<br />

outdoor air temperature, space temperature, and duct static<br />

pressure)<br />

• Supply fan failure<br />

The following failures shutdown the air handler and require a manual<br />

reset:<br />

• Discharge or mixed air temperature sensor failure<br />

• Fan failure<br />

• Low mixed air temperature<br />

CNT-APG001-EN 149