Reviewing the sequence of operation<br />
mode, the supply fan is off, or the discharge air temperature sensor is<br />
failed.<br />
Heating valve<br />
Modulatetheheatingvalvetomaintainthedischargeairtemperatureat<br />
the discharge air setpoint. Close the heating valve if the air handler is in<br />
cool mode, the supply fan is off, or the discharge air temperature sensor is<br />
failed. Open the heating valve if the supply fan is off and the outdoor air<br />
temperature falls below the adjustable freeze avoidance setpoint.<br />
Humidification<br />
Enable humidification mode when the air handler is in occupied mode,<br />
the supply fan is on, and the outdoor air temperature falls below 55°F.<br />
Modulate the humidifier to maintain the space relative humidity setpoint.<br />
If the duct relative humidity exceeds 85%, turn off the humidifier<br />
to prevent condensation in the duct work and indicate an alarm.<br />
Dehumidification<br />
Enable dehumidification mode when the air handler is occupied, the supply<br />
fan is on, the outdoor air temperature is above 55°F, and the space relative<br />
humidity is above the space dehumidification setpoint. Modulate<br />
the cooling valve to maintain space relative humidity and the heating<br />
valve to maintain discharge air temperature.<br />
Alarms<br />
In addition to the alarm requirements mentioned above, indicate an<br />
alarm at the operator display and turn on the alarm output when any<br />
sensor fails. Alarms must be resettable at the operator display. Diagnostic<br />
conditions include the following:<br />
• Dirty filter<br />
• Duct humidity high limit<br />
• Exhaust fan failure<br />
• Low outdoor air temperature<br />
• Low (mixed air) temperature detection<br />
• Sensor failure (including discharge air temperature, mixed air temperature,<br />
outdoor air temperature, space temperature, and duct static<br />
pressure)<br />
• Supply fan failure<br />
The following failures shutdown the air handler and require a manual<br />
reset:<br />
• Discharge or mixed air temperature sensor failure<br />
• Fan failure<br />
• Low mixed air temperature<br />
CNT-APG001-EN 149