Chapter 7 Constant-volume AHU example<br />

Figure 131: Constant-volume air handler<br />

Reviewing the sequence of operation<br />

In this scenario a constant-volume air handler provides comfort heating<br />

and cooling to a space. The air handler contains a variable-speed fan, both<br />

cooling and heating coils, and an outdoor air damper. The air handler is a<br />

stand-alone unit (Figure 131).<br />

Modes and setpoints<br />

The following parameters for the sequence of operation are presented<br />

according to the occupancy mode, the heat/cool mode, or the setpoint.<br />

Occupied mode (including occupied bypass)<br />

When the air handler is in occupied mode, operate the supply fan continuously<br />

and modulate the cooling valve, heating valve, and outside air<br />

damper to maintain space comfort conditions. During unoccupied periods,<br />

when the local timed override button (the ON button on the space temperature<br />

sensor) is pressed, transition the air handler to occupied bypass<br />

mode for the configured occupied bypass time period. When the local<br />

CANCEL button is pressed, terminate the timed override request and<br />

revert the air handler to the scheduled mode.<br />

Occupied standby mode<br />

When the air handler is in occupied standby mode, operate the supply fan<br />

continuously and modulate the cooling valve, heating valve, and outside<br />

air damper to maintain space comfort conditions. Use occupied standby<br />

mode to save energy by using lower heating and higher cooling temperature<br />

setpoints and reduced ventilation requirements during intermittent<br />

unoccupied periods.<br />

An occupancy sensor determines the presence of people in the space<br />

served by the air-handling unit. When the space is occupied, operate the<br />

air handler in occupied mode. When the space is unoccupied during a<br />

146 CNT-APG001-EN