Applications Guide Tracer Graphical Programming - Trane
Applications Guide Tracer Graphical Programming - Trane Applications Guide Tracer Graphical Programming - Trane
® Chapter 6 VAV AHU example Summary questions Answer the following questions to review the skills, concepts, and definitions you learned in this chapter. The answers to these questions are on page 237. 1. How would you use the outdoor air enthalpy to determine whether to economize? 2. Use the calculation application in combination with a program to create a fan maintenance timer. Every 4,000 hours, turn on a binary variable to indicate that fan maintenance is required. Also, use another binary variable to reset the maintenance timer. 3. Implement a binary variable to enable the operator to switch between a space temperature setpoint source of operator display or a local, wired zone sensor with a thumbwheel setpoint adjustment knob. Be sure to apply limits to the resulting setpoint. Modify the modes and setpoints program to accommodate this new feature. 4. What modifications are necessary to the Mode and Setpoints program to allow the operator to adjust the discharge air cooling and heating setpoints? 144 CNT-APG001-EN
® Chapter 7 Constant-volume AHU example In this chapter, you will expand your programming skills. You will use what you learned in Chapters 1 through 6 to program a constant-volume air handler with space temperature control. Note: Many of the chapters in this book build on previous chapters, so be sure to complete the chapters in the order presented. See “About this book” on page 1 for additional instructions. What you will learn In this chapter, you will learn a variety of skills, concepts, and definitions. Skills You will learn how to interpret increasingly complex sequences of operation, with a focus on constant-volume air-handler applications. Concepts and definitions You will understand the following concepts and definitions: • Writing program modules to meet a sequence of operation • Reusing and modifying program modules from previous programs • Incorporating peer-to-peer binding with another Comm5 device Block You will learn how to use the following blocks: • Reset • Between CNT-APG001-EN 145
- Page 118 and 119: ® Chapter 5 Cooling tower with var
- Page 120 and 121: ® Chapter 5 Cooling tower with var
- Page 122 and 123: ® Chapter 5 Cooling tower with var
- Page 124 and 125: ® Chapter 5 Cooling tower with var
- Page 126 and 127: ® Chapter 5 Cooling tower with var
- Page 128 and 129: ® Chapter 5 Cooling tower with var
- Page 130 and 131: ® Chapter 6 VAV AHU example Review
- Page 132 and 133: ® Chapter 6 VAV AHU example contro
- Page 134 and 135: ® Chapter 6 VAV AHU example Table
- Page 136 and 137: ® Chapter 6 VAV AHU example Figure
- Page 138 and 139: ® Chapter 6 VAV AHU example Figure
- Page 140 and 141: ® Chapter 6 VAV AHU example Figure
- Page 142 and 143: ® Chapter 6 VAV AHU example Figure
- Page 144 and 145: ® Chapter 6 VAV AHU example Figure
- Page 146 and 147: ® Chapter 6 VAV AHU example Figure
- Page 148 and 149: ® Chapter 6 VAV AHU example Figure
- Page 150 and 151: ® Chapter 6 VAV AHU example Figure
- Page 152 and 153: ® Chapter 6 VAV AHU example Writin
- Page 154 and 155: ® Chapter 6 VAV AHU example Indica
- Page 156 and 157: ® Chapter 6 VAV AHU example Figure
- Page 158 and 159: ® Chapter 6 VAV AHU example Alarm
- Page 160 and 161: ® Chapter 6 VAV AHU example charge
- Page 162 and 163: ® Chapter 6 VAV AHU example In thi
- Page 164 and 165: ® Chapter 6 VAV AHU example Figure
- Page 166 and 167: ® Chapter 6 VAV AHU example Effect
- Page 170 and 171: ® Chapter 7 Constant-volume AHU ex
- Page 172 and 173: ® Chapter 7 Constant-volume AHU ex
- Page 174 and 175: ® Chapter 7 Constant-volume AHU ex
- Page 176 and 177: ® Chapter 7 Constant-volume AHU ex
- Page 178 and 179: ® Chapter 7 Constant-volume AHU ex
- Page 180 and 181: ® Chapter 7 Constant-volume AHU ex
- Page 182 and 183: ® Chapter 7 Constant-volume AHU ex
- Page 184 and 185: ® Chapter 7 Constant-volume AHU ex
- Page 186 and 187: ® Chapter 7 Constant-volume AHU ex
- Page 188 and 189: ® Chapter 7 Constant-volume AHU ex
- Page 190 and 191: ® Chapter 7 Constant-volume AHU ex
- Page 192 and 193: ® Chapter 7 Constant-volume AHU ex
- Page 194 and 195: ® Chapter 7 Constant-volume AHU ex
- Page 196 and 197: ® Chapter 7 Constant-volume AHU ex
- Page 198 and 199: ® Chapter 7 Constant-volume AHU ex
- Page 200 and 201: ® Chapter 7 Constant-volume AHU ex
- Page 202 and 203: ® Chapter 7 Constant-volume AHU ex
- Page 204 and 205: ® Chapter 7 Constant-volume AHU ex
- Page 206 and 207: ® Chapter 7 Constant-volume AHU ex
- Page 208 and 209: ® Chapter 7 Constant-volume AHU ex
- Page 210 and 211: ® Chapter 7 Constant-volume AHU ex
- Page 212 and 213: ® Chapter 7 Constant-volume AHU ex
- Page 214 and 215: ® Chapter 8 Constant-volume AHU wi
- Page 216 and 217: ® Chapter 8 Constant-volume AHU wi
®<br />
Chapter 6 VAV AHU example<br />
Summary questions<br />
Answer the following questions to review the skills, concepts, and definitions<br />
you learned in this chapter. The answers to these questions are on<br />
page 237.<br />
1. How would you use the outdoor air enthalpy to determine whether to<br />
economize?<br />
2. Use the calculation application in combination with a program to create<br />
a fan maintenance timer. Every 4,000 hours, turn on a binary<br />
variable to indicate that fan maintenance is required. Also, use<br />
another binary variable to reset the maintenance timer.<br />
3. Implement a binary variable to enable the operator to switch between<br />
a space temperature setpoint source of operator display or a local,<br />
wired zone sensor with a thumbwheel setpoint adjustment knob. Be<br />
sure to apply limits to the resulting setpoint. Modify the modes and<br />
setpoints program to accommodate this new feature.<br />
4. What modifications are necessary to the Mode and Setpoints program<br />
to allow the operator to adjust the discharge air cooling and heating<br />
setpoints?<br />
144 CNT-APG001-EN