®<br />

Writing the mode and setpoints program<br />

Then use these offset values to calculate the heating and cooling effective<br />

occupied and occupied standby setpoints.<br />

CSP EffectiveOcc = 72.0 + 1.5 = 73.5<br />

HSP EffectiveOcc = 72.0 – 1.5 = 70.5<br />

CSP EffectiveOccStby = 72.0 + 5.5 = 77.5<br />

HSP EffectiveOccStby = 72.0 – 5.5 = 66.5<br />

Table 17 displays the effective setpoint values when the space temperature<br />

setpoint is set to 72.0°F<br />

Table 17: Effective setpoint values<br />

Setpoints<br />

Effective<br />

setpoints<br />

Space temperature setpoint<br />

72.0°F<br />

Unoccupied cooling 85.0°F 85.0°F<br />

Occupied standby cooling 78.0°F 77.5°F<br />

Occupied cooling 74.0°F 73.5°F<br />

Occupied heating 71.0°F 70.5°F<br />

Occupied standby heating 67.0°F 66.5°F<br />

Unoccupied heating 60.0°F 60.0°F<br />

Default setpoints<br />

Use the module in Figure 126 on page 140 to complete the second part of<br />

the program that calculates the effective setpoint values.<br />

• Use the Add block to add the offset to the space temperature setpoint<br />

to obtain the effective cooling setpoint.<br />

• Use the Subtract block to subtract the offset from the space temperature<br />

setpoint to obtain the effective heating setpoint.<br />

• Use two Switch blocks to determine the effective setpoints based on<br />

the occupancy mode. In unoccupied mode, set the effective setpoints<br />

to the default unoccupied setpoints. Otherwise, calculate the effective<br />

setpoints based on the effective offset and the space temperature setpoint.<br />

• Use Network Configuration Input (nci) blocks to access the unoccupied<br />

default setpoints associated with the DAC profile.<br />

• Use wireless connections to transfer the effective setpoints to other<br />

parts of the program.<br />

CNT-APG001-EN 139