®<br />

Writing the mode and setpoints program<br />

Figure 124: Mode and setpoints program properties<br />

When complete, this program will perform the following tasks:<br />

• Effective space setpoint calculation<br />

• Discharge air setpoint validation<br />

• Heat/Cool mode determination<br />

Calculating the effective space setpoints<br />

Study the sequence of operation to determine the logic to use to construct<br />

your program. In this case, the following logical points apply to setpoint<br />

calculation.<br />

• Calculate the effective occupied cooling and heating setpoints as in<br />

other Comm5 devices.<br />

• In occupied mode, use the default occupied cooling and heating setpoints<br />

to determine an offset.<br />

• In occupied standby mode, use the default occupied standby cooling<br />

and heating setpoints to determine an offset.<br />

• In either mode, apply the calculated offset to the space temperature<br />

setpoint to determine the effective cooling and heating setpoints.<br />

• Because this is a VAV air-handling unit, controlling the discharge air<br />

temperature is not based on the effective occupied cooling and heating<br />

setpoints but on the cooling and heating setpoints for the dis-<br />

CNT-APG001-EN 135