®<br />

Writing the alarms program<br />

Indicating auto-reset alarms<br />

The remaining diagnostic conditions require auto-reset alarms. Use the<br />

TGP module in Figure 121.<br />

Figure 121: Auto-reset alarms<br />

Controlling alarm indication and reset<br />

Based on the status of both auto-reset and manual reset alarms, the last<br />

module manages alarm indication and reset (Figure 122 on page 132).<br />

• Use a Latch block to indicate the alarm status.<br />

• Be sure that auto-reset alarms clear automatically, but manual reset<br />

alarms require a manual reset.<br />

• Use a Switch block to automatically return the binary variable,<br />

Alarm Reset, to a value of off (as presented in the cooling tower program<br />

in Chapter 4, “Cooling tower with two-speed fan example”).<br />

CNT-APG001-EN 131