® Chapter 6 VAV AHU example Writing the alarms program The alarms program indicates diagnostic conditions to the operator and protects the equipment from potential harm when such a condition exists. According to the sequence of operation, the following diagnostic conditions require an alarm indication: • Dirty filter • Duct static pressure high limit • Exhaust fan failure • Low outdoor air temperature • Low (mixed air) temperature detection • Sensor failure (including discharge air temperature, mixed air temperature, outdoor air temperature, space temperature, and duct static pressure) • Supply fan failure The following failures shutdown the air handler and require a manual reset: • Discharge air or mixed air temperature sensor failure • Fan failure • High duct static pressure • Low mixed air temperature All alarms must be resettable at the operator display. First, set the program properties as shown in Figure 119 on page 129. 128 CNT-APG001-EN
® Writing the alarms program Figure 119: Alarms program properties Note that some alarms require the air handler to shut down, and others simply require an alarm indication. An alarm reset at the operator display resets all alarms. Taking this into consideration, create the following three modules within the alarms program: • Manual reset alarms • Auto-reset alarms • Alarm indication and reset CNT-APG001-EN 129
- Page 102 and 103: ® Chapter 4 Cooling tower with two
- Page 104 and 105: ® Chapter 5 Cooling tower with var
- Page 106 and 107: ® Chapter 5 Cooling tower with var
- Page 108 and 109: ® Chapter 5 Cooling tower with var
- Page 110 and 111: ® Chapter 5 Cooling tower with var
- Page 112 and 113: ® Chapter 5 Cooling tower with var
- Page 114 and 115: ® Chapter 5 Cooling tower with var
- Page 116 and 117: ® Chapter 5 Cooling tower with var
- Page 118 and 119: ® Chapter 5 Cooling tower with var
- Page 120 and 121: ® Chapter 5 Cooling tower with var
- Page 122 and 123: ® Chapter 5 Cooling tower with var
- Page 124 and 125: ® Chapter 5 Cooling tower with var
- Page 126 and 127: ® Chapter 5 Cooling tower with var
- Page 128 and 129: ® Chapter 5 Cooling tower with var
- Page 130 and 131: ® Chapter 6 VAV AHU example Review
- Page 132 and 133: ® Chapter 6 VAV AHU example contro
- Page 134 and 135: ® Chapter 6 VAV AHU example Table
- Page 136 and 137: ® Chapter 6 VAV AHU example Figure
- Page 138 and 139: ® Chapter 6 VAV AHU example Figure
- Page 140 and 141: ® Chapter 6 VAV AHU example Figure
- Page 142 and 143: ® Chapter 6 VAV AHU example Figure
- Page 144 and 145: ® Chapter 6 VAV AHU example Figure
- Page 146 and 147: ® Chapter 6 VAV AHU example Figure
- Page 148 and 149: ® Chapter 6 VAV AHU example Figure
- Page 150 and 151: ® Chapter 6 VAV AHU example Figure
- Page 154 and 155: ® Chapter 6 VAV AHU example Indica
- Page 156 and 157: ® Chapter 6 VAV AHU example Figure
- Page 158 and 159: ® Chapter 6 VAV AHU example Alarm
- Page 160 and 161: ® Chapter 6 VAV AHU example charge
- Page 162 and 163: ® Chapter 6 VAV AHU example In thi
- Page 164 and 165: ® Chapter 6 VAV AHU example Figure
- Page 166 and 167: ® Chapter 6 VAV AHU example Effect
- Page 168 and 169: ® Chapter 6 VAV AHU example Summar
- Page 170 and 171: ® Chapter 7 Constant-volume AHU ex
- Page 172 and 173: ® Chapter 7 Constant-volume AHU ex
- Page 174 and 175: ® Chapter 7 Constant-volume AHU ex
- Page 176 and 177: ® Chapter 7 Constant-volume AHU ex
- Page 178 and 179: ® Chapter 7 Constant-volume AHU ex
- Page 180 and 181: ® Chapter 7 Constant-volume AHU ex
- Page 182 and 183: ® Chapter 7 Constant-volume AHU ex
- Page 184 and 185: ® Chapter 7 Constant-volume AHU ex
- Page 186 and 187: ® Chapter 7 Constant-volume AHU ex
- Page 188 and 189: ® Chapter 7 Constant-volume AHU ex
- Page 190 and 191: ® Chapter 7 Constant-volume AHU ex
- Page 192 and 193: ® Chapter 7 Constant-volume AHU ex
- Page 194 and 195: ® Chapter 7 Constant-volume AHU ex
- Page 196 and 197: ® Chapter 7 Constant-volume AHU ex
- Page 198 and 199: ® Chapter 7 Constant-volume AHU ex
- Page 200 and 201: ® Chapter 7 Constant-volume AHU ex
®<br />
Chapter 6 VAV AHU example<br />
Writing the alarms program<br />
The alarms program indicates diagnostic conditions to the operator and<br />
protects the equipment from potential harm when such a condition exists.<br />
According to the sequence of operation, the following diagnostic conditions<br />
require an alarm indication:<br />
• Dirty filter<br />
• Duct static pressure high limit<br />
• Exhaust fan failure<br />
• Low outdoor air temperature<br />
• Low (mixed air) temperature detection<br />
• Sensor failure (including discharge air temperature, mixed air temperature,<br />
outdoor air temperature, space temperature, and duct static<br />
pressure)<br />
• Supply fan failure<br />
The following failures shutdown the air handler and require a manual<br />
reset:<br />
• Discharge air or mixed air temperature sensor failure<br />
• Fan failure<br />
• High duct static pressure<br />
• Low mixed air temperature<br />
All alarms must be resettable at the operator display.<br />
First, set the program properties as shown in Figure 119 on page 129.<br />
128 CNT-APG001-EN