Chapter 6 VAV AHU example<br />

Figure 116: Controlling the cooling valve<br />

Controlling the heating valve<br />

Consider the following specifications from the sequence of operation when<br />

writing the module for the heating valve.<br />

Modulatetheheatingvalvetomaintainthedischargeairtemperatureat<br />

the discharge air heating setpoint when both of the following are true:<br />

• The supply fan is on.<br />

• The air handler is in heating mode.<br />

Open the heating valve completely when both ofthefollowingaretrue:<br />

• The supply fan is off.<br />

• The outdoor air temperature falls below the adjustable freeze avoidance<br />

setpoint.<br />

Close the heating valve when any of the following is true:<br />

• The air handler is in cooling mode.<br />

• The supply fan is off.<br />

• The discharge air temperature sensor is failed.<br />

Like the cooling valve, the control of the heating valve consists of two<br />

parts: the decision and the control. However, a third requirement calls for<br />

the heating valve to open when the outdoor air temperature falls below<br />

the adjustable, low setpoint for the outdoor air temperature.<br />

124 CNT-APG001-EN