Applications Guide Tracer Graphical Programming - Trane

Applications Guide Tracer Graphical Programming - Trane Applications Guide Tracer Graphical Programming - Trane

28.09.2014 Views

® Chapter 6 VAV AHU example Figure 114: Controlling outdoor air damper position Determining the outdoor air damper position The next piece of the puzzle involves determining the required position of the outdoor air damper. Use the TGP module in Figure 114. • Use a Delay on Start block to implement a 1-minute delay prior to allowing the outdoor air damper to modulate. • UseaPIDlooptocontroltheoutdoorairdampertomaintainthedischarge air setpoint when economizing is permitted. • AddasecondPIDloopasbackupprotectiontomonitorthemixedair temperature. It determines the necessary outdoor air damper positions to maintain the mixed air temperature at the mixed air temperature (low limit) setpoint. • Use a Network Configuration Input (nci) block to access low limit setpoint for the mixed air associated with the DAC profile. • Compare the calculated positions from the PID loops. And allow mixed air control to overrule discharge air control when necessary to prevent freezing of the heating or cooling coils. 122 CNT-APG001-EN

® Writing the discharge air control program Controlling the cooling valve Take a closer look at the sequence of operation with regard to the cooling valve. Modulate the cooling valve to maintain the discharge air temperature at the discharge air cooling setpoint when all ofthefollowingaretrue: • The supply fan is on. • The air handler is in cooling mode. • The economizer function is not enabled. Or when all ofthefollowingaretrue: • The supply fan is on. • The air handler is in cooling mode. • The economizer function is enabled. • The outdoor air damper is open at least 90%. Close the cooling valve when any of the following is true: • The air handler is in heating mode. • The supply fan is off. • The discharge air temperature sensor is failed. It may help to think of control of the cooling valve in two parts. First, programthedecisiontooperatethecoolingvalveasshowninFigure115. • Use a combination of logic blocks to determine whether the cooling valve operates. • Apply the output of the economizer decision here. • Use a Deadband block and the position of the outdoor air damper. Figure 115: Operate the cooling valve? The output of this decision feeds into the actual control of the cooling valve using a PID loop (Figure 116 on page 124). CNT-APG001-EN 123

®<br />

Chapter 6 VAV AHU example<br />

Figure 114: Controlling outdoor air damper position<br />

Determining the outdoor air damper position<br />

The next piece of the puzzle involves determining the required position of<br />

the outdoor air damper. Use the TGP module in Figure 114.<br />

• Use a Delay on Start block to implement a 1-minute delay prior to<br />

allowing the outdoor air damper to modulate.<br />

• UseaPIDlooptocontroltheoutdoorairdampertomaintainthedischarge<br />

air setpoint when economizing is permitted.<br />

• AddasecondPIDloopasbackupprotectiontomonitorthemixedair<br />

temperature. It determines the necessary outdoor air damper positions<br />

to maintain the mixed air temperature at the mixed air temperature<br />

(low limit) setpoint.<br />

• Use a Network Configuration Input (nci) block to access low limit setpoint<br />

for the mixed air associated with the DAC profile.<br />

• Compare the calculated positions from the PID loops. And allow<br />

mixed air control to overrule discharge air control when necessary to<br />

prevent freezing of the heating or cooling coils.<br />

122 CNT-APG001-EN

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!