Applications Guide Tracer Graphical Programming - Trane
Applications Guide Tracer Graphical Programming - Trane Applications Guide Tracer Graphical Programming - Trane
® Chapter 6 VAV AHU example Figure 112: Discharge air control program properties Controlling the mixed air and outdoor air damper Operation of the outdoor air damper and subsequent mixed air temperature control must satisfy a number of scenarios according to the sequence of operation. Modulate the outdoor air damper between the adjustable minimum position and fully open to maintain the discharge air cooling setpoint when all of the following are true: • The economizer is enabled. • The outdoor air temperature is less than the economizer changeover (or outdoor air temperature) setpoint. • The air handler is in cooling mode. Modulate the outdoor air damper closed, overriding the minimum position, to maintain the mixed air temperature at or above the mixed air setpoint. Control the outdoor air damper to its minimum position when either of the following is true: • The economizer function is disabled. • The air handler is in heating mode. 120 CNT-APG001-EN
® Writing the discharge air control program Figure 113: Determining whether to economize Close the outdoor air damper completely when any of the following is true: • The unit is in unoccupied mode. • The outdoor air temperature falls below the low setpoint for the outdoor air temperature. • The supply fan is off. • The sensor for the mixed air temperature is failed. Determining whether to economize Because the control of the outdoor air damper is potentially complex, you may simplify the program by separating the decision to economize from the actual control of the damper. Complete the first part of this program, as shown in Figure 113, to determine some factors important to control of the outside air damper. • Use a Deadband block to check the outside air temperature against thelowoutsideairtemperaturesetpoint.Youwillusethisinformation later in the program. • Use a second Deadband block to check the outside air temperature against the economizer changeover, or outside air temperature, setpoint. Combine the economizer enable setting and the heat/cool mode with the result of this deadband to determine whether conditions warrant economizer operation. • Use a Network Configuration Input (nci) block to access the outdoor air temperature setpoint associated with the DAC profile. CNT-APG001-EN 121
- Page 94 and 95: ® Chapter 4 Cooling tower with two
- Page 96 and 97: ® Chapter 4 Cooling tower with two
- Page 98 and 99: ® Chapter 4 Cooling tower with two
- Page 100 and 101: ® Chapter 4 Cooling tower with two
- Page 102 and 103: ® Chapter 4 Cooling tower with two
- Page 104 and 105: ® Chapter 5 Cooling tower with var
- Page 106 and 107: ® Chapter 5 Cooling tower with var
- Page 108 and 109: ® Chapter 5 Cooling tower with var
- Page 110 and 111: ® Chapter 5 Cooling tower with var
- Page 112 and 113: ® Chapter 5 Cooling tower with var
- Page 114 and 115: ® Chapter 5 Cooling tower with var
- Page 116 and 117: ® Chapter 5 Cooling tower with var
- Page 118 and 119: ® Chapter 5 Cooling tower with var
- Page 120 and 121: ® Chapter 5 Cooling tower with var
- Page 122 and 123: ® Chapter 5 Cooling tower with var
- Page 124 and 125: ® Chapter 5 Cooling tower with var
- Page 126 and 127: ® Chapter 5 Cooling tower with var
- Page 128 and 129: ® Chapter 5 Cooling tower with var
- Page 130 and 131: ® Chapter 6 VAV AHU example Review
- Page 132 and 133: ® Chapter 6 VAV AHU example contro
- Page 134 and 135: ® Chapter 6 VAV AHU example Table
- Page 136 and 137: ® Chapter 6 VAV AHU example Figure
- Page 138 and 139: ® Chapter 6 VAV AHU example Figure
- Page 140 and 141: ® Chapter 6 VAV AHU example Figure
- Page 142 and 143: ® Chapter 6 VAV AHU example Figure
- Page 146 and 147: ® Chapter 6 VAV AHU example Figure
- Page 148 and 149: ® Chapter 6 VAV AHU example Figure
- Page 150 and 151: ® Chapter 6 VAV AHU example Figure
- Page 152 and 153: ® Chapter 6 VAV AHU example Writin
- Page 154 and 155: ® Chapter 6 VAV AHU example Indica
- Page 156 and 157: ® Chapter 6 VAV AHU example Figure
- Page 158 and 159: ® Chapter 6 VAV AHU example Alarm
- Page 160 and 161: ® Chapter 6 VAV AHU example charge
- Page 162 and 163: ® Chapter 6 VAV AHU example In thi
- Page 164 and 165: ® Chapter 6 VAV AHU example Figure
- Page 166 and 167: ® Chapter 6 VAV AHU example Effect
- Page 168 and 169: ® Chapter 6 VAV AHU example Summar
- Page 170 and 171: ® Chapter 7 Constant-volume AHU ex
- Page 172 and 173: ® Chapter 7 Constant-volume AHU ex
- Page 174 and 175: ® Chapter 7 Constant-volume AHU ex
- Page 176 and 177: ® Chapter 7 Constant-volume AHU ex
- Page 178 and 179: ® Chapter 7 Constant-volume AHU ex
- Page 180 and 181: ® Chapter 7 Constant-volume AHU ex
- Page 182 and 183: ® Chapter 7 Constant-volume AHU ex
- Page 184 and 185: ® Chapter 7 Constant-volume AHU ex
- Page 186 and 187: ® Chapter 7 Constant-volume AHU ex
- Page 188 and 189: ® Chapter 7 Constant-volume AHU ex
- Page 190 and 191: ® Chapter 7 Constant-volume AHU ex
- Page 192 and 193: ® Chapter 7 Constant-volume AHU ex
®<br />
Chapter 6 VAV AHU example<br />
Figure 112: Discharge air control program properties<br />
Controlling the mixed air and outdoor air damper<br />
Operation of the outdoor air damper and subsequent mixed air temperature<br />
control must satisfy a number of scenarios according to the sequence<br />
of operation.<br />
Modulate the outdoor air damper between the adjustable minimum position<br />
and fully open to maintain the discharge air cooling setpoint when<br />
all of the following are true:<br />
• The economizer is enabled.<br />
• The outdoor air temperature is less than the economizer changeover<br />
(or outdoor air temperature) setpoint.<br />
• The air handler is in cooling mode.<br />
Modulate the outdoor air damper closed, overriding the minimum position,<br />
to maintain the mixed air temperature at or above the mixed air setpoint.<br />
Control the outdoor air damper to its minimum position when either of<br />
the following is true:<br />
• The economizer function is disabled.<br />
• The air handler is in heating mode.<br />
120 CNT-APG001-EN